Læs gratis den danske manual til ENTES AKC-01A (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 4 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 2.5 anmeldelser. Har du et spørgsmål om ENTES AKC-01A, eller vil du spørge andre brugere om produktet?

Side 1/4
Genel
AKC-01A / AKC-03A Aþýrý Akým Koruma Rölesi; motorla ve sistemleri aþýrý
akýma karþý korumak için tasarlanmýþtýr. Bir akým ayarý (Iset) ve iki gecikm e
ayarýna (baþlama ve açma) sahiptir. Baþlama (start) gecikmesi, motor
kalkýþ (demeraj) akýmý nedeniyle oluþabilecek hatalý açmalarý önlemek
amacýyla geliþtirilmiþtir.
Çalýþma Prensibi
AKC-01A / AKC-03A motor veya koruduðu sistemin akýmýný ölçer ve bu
koruduðu sistemi devreden çýkarmak için kullanýlýr.
Akým deðerinin altýnda ise çýkýþ rölesi çekili (ON) konumdadýr. ÞayetIset
akým deðerinin üzerinde bir deðere ulaþýrsa ayarlanabilir bir açmaIset
gecikmesi sonunda röle býrakýr (OFF) ve baðlý olduðu motoru veya sistem i
devreden çýkarýr.
Aþaðýdaki grafiklerde bu durumlar açýklanmýþtýr.
Akým deðeri Iset derini aþtýðýnda, motor veya sistemin kalkýþ (start) akým ý
etkisi ile hatalý açmasý 1-6 sn ayarlý baþlama (start) gecikmesi ile önlenir.
AÞIRI / DÜÞÜK AKIM KORUMA RÖLELERÝ
AKC SERÝSÝ
AKC-01A / AKC-03A AÞIRI AKIM KORUMA RÖLESÝ
Boyutlar
DÝKKAT: CT-25 Akým trafosunun içerisinden 1’den fazla tur
geçirilecekse izolasyonlu kablo kullanýnýz.
CT-25 Akým trf. cihazla birlikte satýlmaktadýr.
AKC-01D / AKC-03D DÜÞÜK AKIM KORUMA RÖLESÝ
Güvenli Kullaným ve Kurulum Ýçin Uyarýlar
Aþaðýdaki talimatlara uyulmama halinde yaralanma veya ölümle sonuçlanabilece k
durumlar ortaya çýkabilir.
Cihaz üzerindeki herhangi bir iþlemden önce tüm besleme gerilimlerini kesiniz .
Cihaz þebekeye baðlý iken ön paneli çýkarmayýnýz.
Cihazý solvent veya benzeri maddelerle temizlemeyiniz. Cihazý temizlemek i n
sadece kuru bez kullanýnýz.
Cihazý çalýþtýrmadan önce baðlantýlarýnýn doðru olduðunu kontrol ediniz .
Cihazý panoya monte ediniz.
Cihazýnýzdaki herhangi bir sorunda yetkili satýcýnýzla temas kurunu z.
Genel
AKC-01D / AKC-03D Düþük Akým Koruma Rölesi; motorlarý ve sistemleri
düþük akýma karþý korumak için tasarlanmýþtýr. Bir akým ayarý ve iki(Iset)
gecikme ayarýna (baþlama ve açma) sahiptir. Baþlama (start) gecikmesi,
motor kalkýþ (demeraj) aký nedeniyle oluþabilecek hatalý malarý önlemek
amacýyla geliþtirilmiþtir.
Çalýþma Prensibi
AKC-01D / AKC-03D motor veya koruduðu sistemin akýmýný ölçer ve bu
ölçülen akým deðeri ayarlanan akýmýn altýnda ise motoru veya(Iset)
koruduðu sistemi devreden çýkarmak için kullanýlýr.
Akým Iset deðerinin üzerinde ise çýkýþ lesi çekili (ON) konumdadýr. Þaye t
akým deðerinin altýnda bir deðere ulaþýrsa ayarlanabilir bir açmaIset
gecikmesi sonunda röle býrakýr (OFF) ve baðlý olduðu motoru veya sistem i
devreden çýkarýr.
Aþaðýdaki grafiklerde bu durumlar açýklanmýþtýr.
Uyarý ýþýklarý
ON (Güç)
: Besleme varsa yanar.
OUT (Röle)
: Röle çekili iken yanar.
I>Iset
: Akým ayarlanan akým deðerinin üzerinde ise LED yanar.
Ýþletme Gerilimi (Un) : .Cihazýn üzerindeki etikete bakýnýz
Ýþletme Aralýðý : n(0.9 -1.1) x U
Ýþletme Frekansý : z50 / 60 H
Akým Ayar Aralýðý : )0.5 - 5A(AC
AKC-03 zserisi in tablo 1’e baký
Akým Trafosu
Çevirme Oraný
: 5A ).../ (AKC-01A/AKC-01D için
: )CT-25 (AKC-03A/AKC-03D için
Baþlama Gecikmesi : .1 - 6 sn
Açma Gecikmesi : .0.5 - 2.5 sn
Çýkýþ Kontaklarý : 1 C/O, 8 A, 2000 VA, (Cosϕ=1)
Ortam Sýcaklýðý : -5
0
C ; +55
0
C
Koruma Sýnýfý : 0IP 2
Boyutlar : 8Tip PK 25 ve PK 2
Baðlantý Þekli : Pano içine dikey veya klemens rayýna
Aðýrlýk : g0.3 k
Teknik Bilgi
AKC-01A/AKC-01D Baðlantý Þemasý
*Sistem akýmýnýz 5A’i aþýyorsa AKC-3A / AKC-3D serisi cihazlarý kullanýnýz.
AKC-03A/AKC-03D Baðlantý Þemasý
AKC-03A AKC-03 / D
sadece CT-25 aký m
trafosu ile kullanýlýr .
O p t i m u m ç ö z ü m e
ulaþmak için; CT-25 aký m
trafosunu yandaki verile n
akým aralýklarýnda ve tu r
sayýlarýnda kullanýnýz .
Tablo 1
AKC-03 Serisi cihazý 2-20A aralýðýnda kullanacaksanýz;
Akýmýn geçtiði kabloyu CT-25 akým trafosuna 3 tur sarýn,
bu esnada öndeki Iset skalasý þu deðerleri alacaktýr.
1,5x=2A, 3x=4A, 6x=8A, 9x=12A, 12x=16A, 15x=20A
Tablo 1’e göre
1,5-15 A
x=4
I Set Skalasý Akým ý Tur SayýsýAralýð
(1 tur)6-60 A
3-30 A
2-20 A
(4 tur)
(3 tur)
(2 tur)x=2
x=4/3
x=1
Yukarýdaki önlemlerin uygulanmamasý sonucu doðabilecek istenmeye n
durumlardan üretici firma hiç bir þekilde sorumlu tutulamaz.
T
1
N
C
1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1
L2
L3
N
k I
K L
M
3 ~
Un
N L1
l k 2 3 1
Stop
Start
C
1
AKC-01A
AKC-01D
C
1
T
1
Tip PK 25 Tip PK 28
T
1
N
C
1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1
L2
L3
N
k I
K L
M
3 ~
Un
N L1
l k 2 3 1
Stop
Start
C
1
AKC-03A
AKC-03D
C
1
T
1
CT-25
kl
lk
K L
CT-25
Tip PK 25 Tip PK 28
TÝP PK25
35 mm
90 mm
45 mm
62 mm
58 mm
32 mm
48 mm
35 mm
TÝP PK 28
CT-25
16mm
15.5mm43mm
500mm2x0,35mm
2
Motor
Akýmý
Normal
Çalýþma
Akýmý
Aþýrý Akým Durumu
(Normal Akýmdan Fazla)
Yüksek Akým Ayarý
(Iset)
Baþlangýç
Gecikmesi
Akýma Duyarlý
Röle Gecikmeden
Sonra Motoru Durdurur.
(Röle: OFF)
Aþýrý Akým Koruma Rölesi (AKC-01A/03A)
Zaman
Açma
Gecikmesi
Baþlama Akýmý
Motor Çalýþmasý Baþlangýç
Gecikmesi Baþlangýcý
Baþlangýç
Gecikmesi Sonu
Bekleme
Gecikme
Baþlangýcý
Bekleme
Gecikme
Sonu
Düþük Akým Koruma Rölesi (AKC-01D/03D)
Baþlama Akýmý
(Iset)
Düþük Akým Durumu
(Normal Akýmdan Düþük)
Akýma Duyarlý
Röle Gecikmeden
Sonra Motoru Durdurur.
(Röle: OFF)
Normal
Çalýþma
Akýmý
Düþük Akým Ayarý
Baþlangýç
Gecikmesi
Açma
Gecikmesi
Motor Çalýþmasý Baþlangýç
Gecikmesi Baþlangýcý
Baþlangýç
Gecikmesi Sonu
Bekleme
Gecikme
Baþlangýcý
Bekleme
Gecikme
Sonu
Zaman
Motor
Akýmý
“Bu ürün, 30.05.2008 tarih ve 26891 sayýlý resmi gazetede yanlanan
EEE Yönetmeliðinin Madde 2 ve Ek-1A madde 9 kapsamýndadýr.”
Not: Kontak dayaný omik yükte r: Akkor flemanlý ampul, Rezistanslý cihazlar) 8A'dir. Endükti f
r AC motor, florasan (Sargýlý balaslý), vb..) ya da Kapasitif (ör Led rüler,UPS = = ,
florasan(Elektronik Balastlý), vb..) k anahtarlanacaksa kontaktör kullanýlmasý tavsiye edilir .
Aksi taktirde cihazýn röle kontaklarýnda yapýþma meydana gelebilir.
0.5
1
3x
1.5x
OUT
ON
OUT
ON
I>I tse
AKC-03A/D
2.5
1.5
2
t(s)
Iset
15x12x
9x
6x
1
2
3
6
5
4
3
2
1
t(s)
start
0.5
1
1
0.5
OUT
ON
OUT
ON
I>I tse
AKC-01A/D
2.5
1.5
2
t(s)
Iset
5
4
3
2
1
2
3
6
5
4
3
2
1
t(s)
start
General
AKC-01A /AKC-03A Over Current Monitoring Relays are designed to protect
motors and systems against over current with a ocurrent adjustment and tw
delay adjustments (start-up and tripping). Start-up delay is developed in
order to prevent false contact turn-off arising from initial motor start-up
(inrush) currents.
Operation Principles
AKC-01A / AKC-03A device measures the current of motor or protected
systems and are utilized to turn-off the motor or protected systems when the
measured curren t is above the adjusted level.
When the current value is lower than Iset value, the output relay is switche d
on. When the current value becomes higher than Iset value, the output rela y
is switched off after an adjustable tripping delay time and the motor or
protected system is turned off.
Please see following figures.
For circumstances that the current value becomes higher than value,Iset
start-up delay (adjustable: 1-6 sec. ) is developed in order to prevent false
contact turn-off arising from initial motor start-up currents.
OVER / UNDER CURRENT MONITORING RELAYS
AKC SERIES
AKC-01A / AKC-03A OVER CURRENT MONITORING RELAY
Dimensions
TYPE PK25
35 mm
90 mm
45 mm
62 mm
58 mm
32 mm
48 mm
35 mm
WARNING: If CT-25 current transformer has more than 1 turn,
isolated cable must be used.
CT-25 current transformer is selling with the device.
AKC-01D / AKC-03D UNDER CURRENT MONITORING RELAY
General
AKC-01D / AKC-03D Under Current Monitoring Relays are designed to
protect motors and systems against under current with current a adjustment
and two delay adjustments (start-up and tripping). Start-up delay is developed
in order to prevent false contact turn-off arising from initial motor start-up
(inrush) currents.
Operation Principles
AKC-01D / AKC-03D device measures the current of motor or protected
systems and is utilized to turn-off the motor or protected systems when
measured current is below the adjusted level.
When the current value is higher than Iset value, the output relay is switche d
on. When the current value becomes lower than value, the output relayIset
is switched off after an adjustable tripping delay time and the motor or
protected system is turned off.
Please see following figures.
Start-up delay (adjustable: 1-6 sec.) is developed in order to prevent false
contact turn-off arising from initial motor start-up currents.
Warning leds
:ON when power existsON
OUT :ON When the output relay is switched on.
I>Iset
:LED turns ON when current value is over adjusted level
Rated Voltage (Un) : .Please look at the table on the device
Operating Range : n(0.9 -1.1) x U
Operating Frequency : z50 / 60 H
Current Adjustment Interval : )0.5 - 5A(AC
Please refer to table 1 for AKC-03
Current Transformer Ratio : A (for AKC-01A/AKC-01D).../ 5
: CT-25 (for AKC-03A/AKC-03D)
Start-up Delay : .1 - 6 sec
Tripping Delay : .0.5 - 2.5 sec
Output Contacts : 1 C/O, 8 A, 2000 VA, Cosϕ=1
Ambient Temperature : -5
0
C ; +55
0
C
Protection Class : 0IP 2
Dimensions : 8Type PK 25 and PK 2
Installation : .Surface mounting or on the mounting rails
Weight : g0.3 k
Techn cal i Data
AKC-01A/AKC-01D Connection Diagram
AKC-3A / AKC-3D series must be used if current exceeds 5A.
AKC-03A/AKC-03D Connection Diagram
AKC-03A AKC-03D is onl / y
used with CT-25 curren t
tra former. In order to reachns
the solution; CT-25 curren t
transformer must be use d
with turn numbers in th e
current intervals as in th e
table.
Table 1
must be encircled with 3 turns of the cable that current flows. At that
time, I set scale takes the values below.
1,5x=2A, 3x=4A, 6x=8A, 9x=12A, 12x=16A, 15x=20A
According to Table 1
Precautions For Installation and Safe Use
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front panel.
Do not try to clean the device with solvent or the like.
Only clean the device with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Mount device to the panel
No responsibility is assured by the manufacturer or any of its subsidiaries
for any consequences arising out of the use of this material.
1,5-15 A
x=4
I Set Scale Current Interval Turn Number
(1 turn)6-60 A
3-30 A
2-20 A
(4 turns)
(3 turns)
(2 turns)x=2
x=4/3
x=1
TYPE PK 28
CT-25
16mm
15.5mm43mm
500mm2x0,35mm
2
T
1
N
C
1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1
L2
L3
N
k I
K L
M
3 ~
Un
N L1
l k 23 1
Stop
Start
C
1
AKC-01A
AKC-01D
C
1
T
1
Type PK 25 Type PK 28
T
1
N
C
1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1
L2
L3
N
k I
K L
M
3 ~
Un
N L1
l k 2 3 1
Stop
Start
C
1
AKC-03A
AKC-03D
C
1
T
1
CT-25
kl
lk
K L
CT-25
Type PK 25 Type PK 28
Note: The contact resistance at ohmic load (eg: Incandescent bulb, Resistance
devices) is 8A.It is recommended to use a contactor if the inductive load (eg:
AC motor, fluorescent, etc.) or capacitive load (eg : Led Drivers, UPS,
Fluorescent (Electronic Ballast), etc.) switch. Otherwise adhesion may occur
in relay contacts
0.5
1
3x
1 x.5
OUT
ON
OUT
ON
I>I tse
AKC-03A/D
2.5
1.5
2
t(s)
Iset
15x12x
9x
6x
1
2
3
6
5
4
3
2
1
t(s)
start
0.5
1
1
0.5
OU T
ON
OU T
ON
I>I set
AKC-01A/D
2.5
1.5
2
t(s)
Iset
5
4
3
2
1
2
3
6
5
4
3
2
1
t(s)
start


Produkt Specifikationer

Mærke: ENTES
Kategori: Ikke kategoriseret
Model: AKC-01A

Har du brug for hjælp?

Hvis du har brug for hjælp til ENTES AKC-01A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret ENTES Manualer

ENTES

ENTES AKC-01A Manual

28 August 2025
ENTES

ENTES MPR-46S-L Manual

27 August 2025
ENTES

ENTES MM-202 Manual

27 August 2025
ENTES

ENTES SR-05E Manual

27 August 2025
ENTES

ENTES EMR-53S Manual

27 August 2025
ENTES

ENTES SR-10E Manual

27 August 2025
ENTES

ENTES EMR-53SL Manual

27 August 2025
ENTES

ENTES RGI-12W Manual

27 August 2025
ENTES

ENTES DCA-11C Manual

27 August 2025
ENTES

ENTES TV-111 Manual

27 August 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer