! ATTENTION
This user manual contains information necessary for the safe and correct operation of the device. Before
mounting the device, please read this user manual carefully and pay attention to warnings.
Safety and Warnings
! ATTENTION Do not open the device under any circumstances. An opened device’s warranty will
become void.
! ATTENTION The device must be mounted only by qualied personnel with necessary precautions
against electric shock in place. Incorrect connection may create dangerous result for people and
environment. Incorrect connection may result in permanent damage to the performance of the device.
- Before you energize the device or remove the device from mains, make sure that the supply
cable isn’t connected to mains.
- Supply input of the device must be connected according to EN60950 standards.
! A supply voltage greater than 265V AC may result in an explosion in the device or in damages to
the user.
- Device supply must be at a sucient power capacity and must comply with security standards.
- Cables connected to the outputs of PS-362 must be suitable for the maximum current that
PS-362 can provide.
- After device connection is nished, connection points must be protected against accidental contacts.
- Mounting of the device must be done vertically as shown in Figure-1, with AC supply input
at the bottom side and the DC output at the top side.
1- Introduction
1.1 Applications : PS-362 is a 36 W high eciency SMPS which was designed according to DIN case
standards for easy installation in panels. It can be safely used in industrial and building
automation applications.
1.2 General Features :
- Wide input voltage range 85-265V AC (50-60 Hz) / 110-350V DC
- Adjustable DC output voltage 21.6 ...27.6V DC
- 36 W output power (1.5A DC @24V DC)
- Status notication LED (yellow)
- Overload notication LED (red)
-
NC output contact (contact is closed in normal operation) 10A @250V AC / 5 A @30V DC (resistive load)
- High eciency operation at >85%
- Low/High input voltage protection
- Short circuit, overload protection
- Thermal protection
- Class 2 device, no earth connection is necessary
- DIN4 case
- IP20 Protection class
- CE, EN 60950,EN 61204
1- Input Voltage
2- DC Output
3- NC Output Contact
4- Setting Range of the Output Voltage
5- Output OK LED
6- Overload LED
1.3 Operation : The part of the device which is numbered as 1 in Figure-1 is the input voltage
connection point of PS-362 and it is shown with L (Line) and N (Neutral) on the device body. Connect
the supply voltage to these points. The part of the device which is numbered as 2 in Figure-1 is the DC
output connection point of PS-362 and its polarity is shown with + and - on the device body. PS-362
supplies adjustable DC voltage from these connection points. When supply voltage is applied to PS-362,
the yellow LED which is numbered as 5 in Figure-1 will light up. When this is LED is lit, it indicates that
PS-362 is working and it generates an output voltage. The part of the device which is numbered as 4 in
Figure-1 is the DC voltage adjustment trimpot of the device. After the device has been energized, the
output voltage is increased by turning the adjustment trimpot clockwise and is decreased by turning
the adjustment trimpot is turned counterclockwise. This way, the output voltage can be adjusted in the
specied range.The device will turn itself o to protect itself during cases of overload, overheating and
shortcircuit at the output contacts. When the error state is resolved, it will activate itself
automatically.
2- Block Diagram
2.1 Input (1)
- The part which is numbered as 1 in Figure-2 is the Line and Neutral supply inputs of PS-362.
- 100-240V AC input voltage can be connected by using the L and N terminals.
- 110-350V DC input voltage can be connected by using the L and N terminals.
- The device is protected by an internal fuse. However, an appropriate external fuse can be used if a DC
supply voltage is going to be applied to the device.
2.2 Output (2)
- The part which is numbered as 1 in Figure-2 is the DC voltage output of PS-362.
- Positive and negative parts of the output voltage are shown with (+) and (-).
- Output voltage is 24V DC.
- Output voltage can be adjusted between 21.6-27.6V DC values by using the adjustment trimpot on
the device.
- Device output is protected against short circuit.
- When the output is shorted circuited, device turns o completely and turns on again after the short
circuit condition is resolved.
- The device switches to protection under nominal load during high temperature. The red LED lights
up together with the yellow LED during protection. Until the device is cool again, it doesn’t generate
an output voltage.
- The device can operate up to an ambient temperature of +55 C.
3.3 Contact Output (3)
PS-362 devices have contact output. When the device is operating normally, contact output is short
circuited. During overload or thermal protection situiations, contact output is open circuited. During
overvoltage on output, the device waits for this error to be resolved by constantly turning itself on and
o. During this, contact output will be constantly open and short circuited at each try.
PS-362 has LED indicator (Parts 5 and 6 in Figure-1).
- When there’s no energy : Output OK and Overload LEDs are o.
- Normal operation mode : Output OK LED is on.
- Short circuit : Output OK and Overload LEDs are o. If short circuit situation is resolved, the
device starts to work again.
- Overload : If overload is drawn from device at normal temperature, Output OK and Overload
LEDs turn o. The device makes blinks. When the load condition returns to normal, the device
starts to opening again.
- Overheating + Overload : All LEDs turn on. Device cuts the supply, doesn’t generate voltage.
- Overvoltage on Output : Output OK LED blinks.
3- Connection and Mounting
3.1 Wire Connection
- AC Input (1): Under nominal load, PS-362 draws maximum 0.9A AC and minimum 0.4A AC.
Wire thickness must be selected according to these values. Maximum 14 AWG stranded
wire (2.5 mm) or 12 AWG solid wire (4 mm ) can be connected to the input terminal.
- DC output (2): Output current is 1.5A DC. Wire thickness must be selected according to
this value. Maximum 14 AWG stranded wire (2.5 mm ) or 12 AWG solid wire (4 mm ) can be
connected to the output terminal.
- Contact output (3): Contact current is maximum 10A AC. Wire thickness must be selected
according to this value. Maximum 14 AWG twisted wire (2.5 mm ) or 12 AWG solid wire
(4 mm) can be connected to the output terminal.
- In terms of complying with standards, use copper wires that can operate at 75 C.
3.2 Mounting (Figure 2)
- PS-362 can be mounted on DIN rails which comply with EN50022 standards.
- Mount the device vertically. When mounting the device, it is recommended that the DC
output side stays on top side.
- Mind the device’s ventilation when mounting the device. After the mounting, it is
recommended to leave a 1 cm space between PS-362 and devices next to it.
4- Technical Properties:
Input
Nominal input voltage 100-240 VAC / 130-320 VDC
Input voltage range 85-265 VAC / 110-350 VDC
Frequency 45-65 Hz / 0 Hz
Generated current (@36W) 0.4-0.9A AC (±10%)
Starting current <15A
Internal fuse 1.6A
Estimated opening time after
nominal voltage is supplied <1 s (@220V AC - 36W)
Mains butering >20 ms (@220V AC - 36W)
Transient surge
Voltage protection Varistor
Line ragulation <1% (@24V DC)
Output
Nominal output voltage 24V DC (± 1% )
Output voltage range 21.6 - 27.6V DC
Nominal output current 1.5A DC (<55°C)
Maximum output current 3A DC
Eciency >82% @85V AC
>85% @265V AC
Residual uctuation <50 mV (under nominal load)
Overload protection max. 3A (@25°C)
Short circuit protection Hysteresis turn o
Thermal protection >55°C (@1.7A DC)(under nominal load)
Series connection Yes
Parallel connection Yes (by connecting ORing diode)
Load regulation < 1%
Indicators
Output OK Yellow LED
Overload Red LED
General Information
Operating Temperature -20°C...+55°C
Humidity <95% (@25°C)
Mounting Type Rail mount (EN 50022)
Rail mounting spaces 1 cm horizontally, 5 cm vertically
(spacing between other devices)
Connection Terminals with xed screws
compatible with Phillips screw drives
Connection wire max. 12 AWG (4mm )solid
wire, 14 AWG(2.5mm ) stranded wire
Protection class IP20
Pollution Degree Class 2
Overvoltage protection class 3
Dimensions DIN4 (72*95*60) mm
Casing Nylon 6
Weight 250 gr
Product Standards
Product standard EN61204-1, EN61204-3,
EN61204-4, EN61204-7
SMPS transformer standard EN61558-1
Electric safety EN60950, EN61558-2-17
Insulation voltage (input/output) 4 kV
Insulation resistance >5 MW (between input-output)
Surge voltage 3 kV Criterion A EN61000-4-5
Burst voltage 4 kV Criterion B EN61000-4-4
ESD
Air discharge 8 kV Criterion A EN61000-4-2
Contact discharge 4 kV Criterion A EN61000-4-2
Sag in input voltage (@220 VAC)
0% 20ms Criterion A EN61000-4-11
70% 500ms Criterion A EN61000-4-11
Other EN 61000 3 -2, EN 6 1 0 00 6-2, E N 55 0 1 1, EN 5 5 0 22