Læs gratis den danske manual til Growatt Smart Meter (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 88 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 44.5 anmeldelser. Har du et spørgsmål om Growatt Smart Meter, eller vil du spørge andre brugere om produktet?

Side 1/4
Grid
L1
L2
L3
N
SDM630MCT ETL is a multi-functional din-rail meter designed for accurate measurement an d display of parameters i n 3P3W/3P4W power
grid systems, such as voltage, current, power, frequency, active power, reactiv e power, posi tive energy, reverse energy, total harmonics,
etc. It is an ideal choice for real-time power monitoring, featuring a wide range of functions and applications with high stability over
extended service life. The meter works with an external current transformer and can be applied in both high and low voltage power grid. It
comes with an RS485 communication interface, which supports a maximum baud rate of 38400 bps and enables remote communication.
TPM-CT-E-US (SDM630MCT ETL) Three-phase
Smart Meter Quick Guide
General Specifications
Rated voltage
3×277/480Vac
Rated frequency
50/60Hz
L-N voltage r ange
100 ~ 277Vac
L-L voltage range
100 ~ 480Vac
Auxiliary p ower voltage range
100 -277V
AC withstand voltage
4KV for 1min
Input current range
1A or 5A
Short-term overcurrent
20*IMAX for 0.5s
Max. Reading
9999999.9kWh/kVArh
Accuracy
Active powe r
1% of range maximum
Reactive po wer
±1% of range maximum
Environment
Regulated working temperature
range
- ℃~+ ℃25 55
Limited working tempe rature range
- ℃ 40 +70
Relative hu midity annual average
90
Installation category
CAT III
Degree of pol lution
RoHS compliant
Communica tion
Communica tion
RS485 output for Modbus RTU
Baud rate
9600bps (default)
Pulse
3200imp/kWh
Mechanics
Outline dimensions
3.72x2.83x2.56inch (LxWxH )
Din rail dimensions
DIN rail 1.38inch
Protection level
IP51 (indoor)
Item
Quantity
Description
A
1
Three-phase meter
B
1
Quick Insta llation Guide
C
1
RS485 cable (standard length: 15m)
D
3
Current Transformer
1
1
1
11.
.
.
..
Overview
2
2
2
22.
.
.
..
Technical Parameters
3
3
3
33.
.
.
..
Unpacking
Quick
inst
allation
man
ual
A B C D
4
4
4
44.
.
.
..
Dimensions (Unit: inch)
5
5
5
55.
.
.
..
Installation
1. The Growatt Stora ge Inverter and the Hybrid Inverter are hereinafter referred to as "the Storage/Hybrid Inverter".
2. The grid is on the right side and the c urrent flows from P1 to P2 (from the grid to the load).
Note:
Storage/
Hybrid
Inverter Grid
L1
L2
L3
N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
L N L N
Vol ta ge i np ut s
So Cu rr en t inpu tsRS 48 5
RS485-A
RS485-B
S2 S 1 S2 S1
3P3W
PE
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
L N LN
Vol ta ge i np ut s
So Cu rr en t inpu tsRS 48 5
RS485-A
RS485-B
S2 S 1 S2 S1 S2 S1
3P4W
PE
Storage/
Hybrid
Inverter
1.38
1.38
3.72
2.8 3
2.56
P2 P1 P2 P1
There are fou r touch buttons on the panel, arranged from top to bottom as follows: “ESC()V/A, “(Alt)MD/PH/HZ, “(Shift)P,
ENTER()E. These buttons can be operated in two ways: long press (pressing fo r more than two seconds) and short press ( pressing for
less than one s econd).
Button
Features
Viewable content(short pre ss)
Short press:
display voltage and current,
Long press: ESC
Phase voltage, Line voltage, Phase current, Neutral
current, Voltage harmonics, Current harmoni cs
Short press: display power factor and
frequency,
Long press: Alt
Phase(Total) frequency, Total power factor, Ph ase(Total)
maximum current demand
Short press: display power,
Long press: Shift
Phase(Total) active power, Phase(Total) reactive power,
Phase(Total) apparent power
Short press:
display electric energy,
Long press: Enter
Total active electric energy, Total reactive electric energy,
Positive active electric energy, Reverse active elec tric
energy, Positive reactive electric energy, Reverse
reactive electric energy
ESC
A. Voltage sampling and po wer supply wiring
3P3W:
Wiring of the L1 voltage sampling line: corresponding to meter Pin 4
Wiring of the L2 voltage sampling line: corresponding to meter Pin 1
Wiring of the L3 voltage sampling line: corresponding to meter Pin 2
3P4W:
Wiring of the L1 voltage sampling line: corresponding to meter Pin 4
Wiring of the L2 voltage sampling line: corresponding to meter Pin 3
Wiring of the L3 voltage sampling line: corresponding to meter Pin 2
Wiring of the N voltage sampling line: corresponding to meter Pin 1
B. Current transformer wiring
Please refer to the diagram above. The grid is on the right and the
current flows from K to T (from the grid to the load).
Wiring of the L1 CT: S1 Line correspondin g to meter Pin 16, S2 Line
corresponding to meter Pin 15
Wiring of the L3 CT: S1 Line correspondin g to meter Pin 20, S2 Line
corresponding to meter Pin 19
Wiring of the L1 CT: S1 Line correspondin g to meter Pin 16, S2 Line
corresponding to meter Pin 15
Wiring of the L2 CT: S1 Line correspondin g to meter Pin 18, S2 Line
corresponding to meter Pin 17
Wiring of the L3 CT: S1 Line correspondin g to meter Pin 20, S2 Line
corresponding to meter Pin 19
C.RS485 cable wiring
Connect the RS485A to Pin 14 and RS485B to Pin 13 (The network cables delivered with the inverter are labeled as 485-A and 485-B; if
you are using the cables purchased yourself, mak e sure to differentiate betwe en 485-A and 48 5-B.)
D. Connecting the meter to the Growatt Three-phase
Storage/Hybrid Inve rter E. When connecting the smart meter to the inverter, connect one
end of the cable to Terminal 13 (485B) and Terminal 14 (485A) of
the smart meter and the other end to Pin 6 (485A) and Pin 7 (4 85B)
of the COM1 port.
Note: In most c ases, the re d cable is used f or 485A and the black
cable for 485B.
G. The standard RS485 cable length is 15m. If a longer RS485
cable is required, plea se use an intact cable and make sure the
RS485 cable is less than 100m (the recommended length is less
than 25m).
F. Dismantle the 16-pin connector delivered with t he inverter and
set aside the water-proof plug. Route the cables through each part
sequentia lly, then connect them to Pin 6 and Pi n 7. Finally, connect
the connector to the COM1 port of the inve rter.
6
6
6
66.
.
.
..
Button Description and Display
Red(4 8 5A)- - -COM 1 (6)
Black( 48 5B)-- -COM1 (7)
COM1
COM1(6 7)


Produkt Specifikationer

Mærke: Growatt
Kategori: Ikke kategoriseret
Model: Smart Meter

Har du brug for hjælp?

Hvis du har brug for hjælp til Growatt Smart Meter stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Growatt Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer