Læs gratis den danske manual til Tripp Lite HCINT350SNR (5 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 10 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 5.5 anmeldelser. Har du et spørgsmål om Tripp Lite HCINT350SNR, eller vil du spørge andre brugere om produktet?

Side 1/5
17-12-143 - EN Revised by V Li 08/22/2017 .
HC350S, HCINT350S Series Power Module Application Guidelines
Series AGSM5396, AGRT0829
SAVE THESE INSTRUCTIONS IMPORTANT SAFETY This manual contains
INSTRUCTIONS for that should be followed during installation and maintenance of the
UPS and batteries.
The HC350S and HCINT350S series of hospital cart power modules are designed to
provide AC voltage output power from either utility provided AC input voltage or from
inverting 12VDC power from a sealed lead acid battery. To ensure proper operation the
following guidelines should be observed:
1. The power module can support AC loads up to a maximum of 400VA or 300W.
2. The power module charger is intended to be used with a 12V sealed lead acid
absorbed glass mat (AGM) battery with a 33AH to 66AH rating. Batteries rated
at less than 33AH are not recommended since the charger current of 12A would
reduce the battery cycle life of smaller batteries.
3. Adequate provision for airow needs to be provided at both the inlet and outlet
vents of the power module. There should be at least 0.5 inches of clear space
on the fan end and on the vented end of the power module. A bae or air
deector is recommended at the fan end so that the air intake is raised at least 6
inches above oor level to prevent dust accumulation inside the power module.
4. The power module may be mounted in any orientation. Four 8-32 threaded
inserts are provided on the surface with the AC input cord to facilitate mounting.
5. The AC voltage input and output connections are made with user supplied cables
to the IEC input and output connectors on the power module. Use only with
approved plug/cord sets according to the equipment electrical ratings. No
external fusing is needed since safe operation is assured by internal non-
replaceable 10A fuses. However, if a customer wishes to prevent the internal
fuses from blowing in the event of an extreme overload, then an external fuse or
circuit breaker rated at 6A to 10A (120VAC models) or 3A to 5A (230V models)
should be provided on the AC voltage input.
6. The 12V battery input is made with a user supplied cable to the Anderson DC
connector on the power module. Proper polarity must be observed. The
recommended wire size is 8AWG in order to keep the voltage drop in the cable to
less than 0.1V. The length of cable between the battery and the power module
should be less than 30 inches. A user supplied 40A to 50A automotive style fuse
is required in the positive lead of the battery (within 18 inches of the battery
positive terminal).
7. Additional bonding is needed to connect the battery negative terminal to the case
of the power module. The wire (or metal frame of the cart) should be short (less
than 18 inches) and preferably of the same gauge as the other battery wires
17-12-143 - EN Revised by V Li 08/22/2017 .
(although a minimum gauge of 16AWG has been acceptable). This bonding
connection is necessary to prevent internal damage to the power module in the
event of any accidental reversed polarity connections or accidental connections
between the battery positive wiring and the case of the power module.
8. A Remote User Interface (RUI) module must be connected to the power module
using two CAT-5 cables. The COMM1 jacks should be connected together and
the COMM2 jacks should be connected together. If the cables are not connected
or if they are interchanged, the power module will not operate. The RUI may be
either a Tripp Lite RUI or a customer designed RUI that meets Tripp Lite
specications.
9. The power module includes a low voltage cuto (LVC) function that will remove
any load on the battery when the battery is depleted. The LVC level is about
10.5V to assure optimum battery cycle life. If any other DC loads are present in
the system, they need to include their own LVC function in order to prevent
damage to the battery due to over discharge.
10. The power module will not turn on unless connected to a battery that has a
voltage greater than 9.6V. If the battery voltage is less than 9.6V, it is assumed
to be defective and the charger is inhibited in order to prevent possible
outgassing of the battery.
11. The power module reports % Battery Capacity through its USB port. This data is
most accurate when a 55AH sealed lead acid absorbed glass mat (AGM) battery
is used. Batteries of other capacities may be used, but the accuracy of the
% Battery Capacity report will be reduced.
12. After connecting a battery to the power module, the power module should be
allowed to charge the battery to full capacity in order to initialize the % Battery
Capacity report and the % Battery Capacity LED’s (on the RUI). This will take at
least 4 hours, even with fresh battery. The % Battery Capacity report and LED’s
will not be accurate until after the initial charge has been completed. After
initialization, the power module will properly indicate the % Battery Capacity as
the battery is repeatedly discharged and recharged. However, each time the
battery is replaced, the initialization will need to be repeated.