
.
F1 F2
F3
F4
Buzzer and backlight
XI. Detecting Phase Sequence(See Figure 6)
Figure 6
Figure 7 Figure 8
L1
L2
L3
Black
green
red
Understanding F1-F4 Buttons:
F1 F2
F3
F4
Backlight
Invalid
InvalidInvalid
XI. Measuring Loop Impedance/Prospective Fault Current
(See Figure 7, 8)
1.Measuring Loop/Line
Impedance/RCD/Socket
Voltage
2.Measuring Loop Impedance/
Line (L-N) Impedance
Understanding F1-F4 Buttons:
F1 F2
F3
F4
Backlight
InvalidInvalidInvalid
.
Caution
XIII. Measuring Line Impedance/Prospective Short Current
(See Figure 7, 8)
Understanding F1-F4 Buttons:
F1 F2
F3
F4
Not usedNot usedNot used
Backlight/L-N/L-PE
Caution
XIV. Taking Auto RCD Tests (See Figure 7)
F1 F2
F3
F4
Backlight
AC/DC/time RCL
I n
XV. Taking Regular RCD Tests (See Figure 7)
Understanding F1-F4 Buttons:
F1 F2
F3
F4
AC/DC/time
I n
Not used
Backlight/0 /180
1/2*I n
1*I n
2*I n(only for UT595)
5*I n
10mA 30mA 100 mA 300 mA 500Ma
Caution
XVI. Measuring RCD Trip Current (See Figure 7)
F1 F2
F3
F4
AC/DC/time
I n
Not used
Backlight/0 /180
10mA 30mA 100 mA 300 mA 500Ma
Full wave
Half wave
Caution
XVII. Replacing the Battery
Danger
Danger
XVIII. Maintenance & Repair
Cleaning the Casing:
●Clean the Tester surface with soft cloth or sponge dampened with little water.
●To avoid damage to the Tester, do not submerge it into the water.
●Dry the Tester before storing it if it is wet.
**END**
2) Insert red test lead into “Red” input terminal and black test lead into “Black” terminal.
3) Connect red & black alligator clips or probes firmly to tested circuits. The Tester will
automatically identify AC/DC voltage and show measured voltage and frequency
readings on the LCD.
Or connect as shown in Figure 7:
1) Insert three connectors of specified one-plug test leads to three input terminals of the
Tester (red to red, green to green, black to black).
2) Insert the plug of the test leads into the socket of test circuits, the Tester will automa
-tically identify AC/DC voltage and show measured voltage and frequency readings
on the LCD.
Understanding F1-F4 Buttons:
Invalid Invalid Invalid
F1: Long press F1 for 2 seconds to turn on/off the backlight.
F2, F3,F4: all are invalid. TEST is invalid too.
Caution
Caution
● Do not input voltage higher than 440V or 440Vrms. It may be possible to display the
voltage value, but it may pose hazard to the Tester.
● To avoid electric shock, please take extreme caution when working with high voltage.
● Remove the test leads away from tested circuits and disconnect them from the input
terminals of the Tester after completing the measurements.
● Do not measure with the battery cover opened.
To Detect Phase Sequence:
(1) Turn the rotary switch to Phase Rotation position.
(2) Insert three connectors of three test leads into input terminals of the Tester(red to red,
green to green, black to black).
(3) Then connect three test leads into three-phase AC system(black to L1, green to L2,
red to L3, refer to Figure 6 for details), after that, the Tester will indicate the phase
sequence and open phase result on LCD.
F1: Long press for 2 seconds to turn on/off the backlight.
F2, F3, F4: all are invalid; TEST button is invalid too.
● Do not input voltage higher than 440V or 440Vrms. It may be possible to display the
voltage value, but it may pose hazard to the Tester.
● To avoid electric shock, please take extreme caution when working with high voltage.
● Remove the test leads away from tested circuits and disconnect them from the input
terminals of the Tester after completing the measurements.
● Do not measure with the battery cover opened.
To measure Loop Impedance/ Prospective Fault Current:
(1) Turn the rotary switch to LOOP.
(2) Insert three connectors of one-plug test leads or three separate test leads into three
input terminals of the Tester (red to red, green to green, black to black).
(3) Plug the plug into domestic 220V socket or connect the test probes to the tested lines.
(4) Press TEST button to start.
F1: Long press F1 for 2 seconds to turn on/off the backlight.
F2, F3, F4: all are invalid.
● Please make sure domestic 220V in the power socket is normally supplied. If the soc
-ket is unable to be powered normally or de-energized, L-PE and L-N icons on lower
left part of LCD will flash simultaneously.
● Ensure the socket is properly grounded. If the socket has bad grounding or isn’t grou
-nded, L-PE and N-PE icons on lower left part of LCD will flash simultaneously.
● Ensure the neutral terminal of the socket is firmly connected. If the neutral terminal is
badly or not connected, L-N and N-PE icons on lower left part of LCD will flash simult
-aneously.
● Ensure live and neutral terminals of the power socket are not reversely connected
when measuring loop impedance/prospective fault current, otherwise L-PE, L-N and
N-PE icons on the lower left part of LCD will flash simultaneously.
● Please take extreme caution when making the measurement, for it is performed under
high-voltage status.
To measure Line Impedance/Prospective Short Current:
(1) Turn the rotary switch to NO-TRIP position;
(2) Insert three connectors of one-plug test leads or three separate test leads into three
input terminals of the Tester (red to red, green to green, black to black).(Refer to
Figure 6, 7, 8)
(3) Plug the plug into domestic 220V socket or connect the test probes to the tested lines.
(4) Press TEST button to start.
F1: Long press F1 for 2 seconds to turn on/off the backlight; short press to switch between
L-N and L-PE measurements.
F2, F3, F4: all are invalid.
● Please make sure domestic 220V in the power socket is normally supplied. If the socket
is unable to be powered normally or de-energized, L-PE and L-N icons on lower left
part of LCD will flash simultaneously.
● Ensure the socket is properly grounded. If the socket has bad grounding or isn’t grounded,
L-PE and N-PE icons on lower left part of LCD will flash simultaneously.
● Ensure the neutral terminal of the socket is firmly connected. If the neutral terminal is
badly or not connected, L-N and N-PE icons on lower left part of LCD will flash simult
-aneously.
● Ensure live and neutral terminals of the power socket are not reversely connected when
measuring line impedance/prospective short current, otherwise L-PE, L-N and N-PE
icons on the lower left part of LCD will flash simultaneously.
● Please take extreme caution when making the measurement, for it is performed under
high-voltage status.
To Test RCD Automatically:
(1) Turn the rotary switch to AUTO position;
(2) Insert three connectors of one-plug test leads into three input terminals of the Tester
(red
to red, green to green, black to black).(Refer to Figure 7)
(3) Plug the plug into domestic 220V socket.
(4) Press TEST button to start.
Tips:
Auto RCD Test is designed to measure trip times in one time just by pressing one button
down. The Tester will complete all RCD measurements before proceeding into next test.
All these test data will be saved in the Tester; pressing F3 can review all the data. RCD
measurements are taken in following order:
Understanding F1-F4 Buttons:
UT593: 1. 1/2*I△n/0 UT595: 1. 1/2*I△n/0
2. 1/2*I△n/180 2. 1/2*I△n/180
3. 1*I△n/0 3. 1*I△n/0
4. 1*I△n/180 4. 1*I△n/180
5. 5*I△n/0 5. 2*I△n/0
6. 5*I△n/180 6. 2*I△n/0
7. 5*I△n/0
8. 5*I△n/180
F1: Long press for 2 seconds to turn on/off the backlight.
F2: Press to toggle between RCD types and Timer mode.
RCD Types: AC and DC(full-and half-wave)
Timer: under this mode, press down TEST button and the Tester will count down
from 30s to 0s before enabling RCD test;
F3: Press to recall all saved data from the whole test;
F4: Press to select RCD test current.
Caution
● Please make sure domestic 220V in the power socket is normally supplied. If the so
-cket is unable to be powered normally or de-energized, L-PE and L-N icons on lower
left part of LCD will flash simultaneously.
● Ensure the socket is properly grounded. If the socket has bad grounding or isn’t grou
-nded, L-PE and N-PE icons on lower left part of LCD will flash simultaneously.
● Ensure the neutral terminal of the socket is firmly connected. If the neutral terminal is
badly or not connected, L-N and N-PE icons on lower left part of LCD will flash simult
-aneously.
● Ensure live and neutral terminals of the power socket are not reversely connected
when testing RCD, otherwise L-PE, L-N and N-PE icons on the lower left part of LCD
will flash simultaneously.
● Please take extreme caution when taking auto RCD tests, for it is performed under
high-voltage status
To take regular RCD test:
(1) Turn the rotary switch to1/2*I△n, 1*I△n, 2*I△n(for UT595 only) or 5*I△n position;
(2) Insert three connectors of one-plug test leads into three input terminals of the Tester
(red to red, green to green, black to black).(Refer to Figure 7)
(3) Plug the plug into domestic 220V socket.
(4) Press TEST button to start.
F1: Long press for 2 seconds to turn on/off the backlight; short press to toggle between
0 /180
F2: Press to toggle between RCD types and Timer mode.
RCD Types: AC and DC (full-and half-wave)
Timer: under this mode, press down TEST button and the Tester will count down
from 30s to 0s before enabling RCD test;
F3: invalid
F4: Press to select RCD rated test current, refer to rated options in following order:
Tips:
The leakage current will be different depending on the selected current multiplier. Refer
to the following table for detailed relationship.
● Please make sure domestic 220V in the power socket is normally supplied. If the so
-cket is unable to be powered normally or de-energized, L-PE and L-N icons on lower
left part of LCD will flash simultaneously.
● Ensure the socket is properly grounded. If the socket has bad grounding or isn’t grou
-nded, L-PE and N-PE icons on lower left part of LCD will flash simultaneously.
● Ensure the neutral terminal of the socket is firmly connected. If the neutral terminal is
badly or not connected, L-N and N-PE icons on lower left part of LCD will flash simul
-taneously.
● Ensure live and neutral terminals of the power socket are not reversely connected
when testing RCD, otherwise L-PE, L-N and N-PE icons on the lower left part of LCD
will flash simultaneously.
● Please take extreme caution when taking regular RCD tests, for it is performed under
high-voltage status
To measure trip current:
(1) Turn the rotary switch to ▲Ramp position.
(2) Insert three connectors of one-plug test leads into three input terminals of the Tester
(red to red, green to green, black to black).(Refer to Figure 7)
(3) Plug the plug into domestic 220V socket.
(4) Press TEST button to start.
Understanding F1-F4 Buttons:
F1: Long press for 2 seconds to turn on/off the backlight; short press to toggle between
0 /180
F2: Press to toggle between RCD types and Timer mode.
RCD Types: AC and DC (full-and half-wave)
Timer: under this mode, press down TEST button and the Tester will count down
from 30s to 0s before enabling RCD test;
F3: invalid
F4: Press to select RCD rated leakage test current, refer to rated options in following
order.
Tips:
The leakage current will be different depending on the selected waveform. Refer to the
following table for detailed relationship.
● Please make sure domestic 220V in the power socket is normally supplied. If the so
-cket is unable to be powered normally or de-energized, L-PE and L-N icons on lower
left part of LCD will flash simultaneously.
● Ensure the socket is properly grounded. If the socket has bad grounding or isn’t gro
-unded, L-PE and N-PE icons on lower left part of LCD will flash simultaneously.
● Ensure the neutral terminal of the socket is firmly connected. If the neutral terminal
is badly or not connected, L-N and N-PE icons on lower left part of LCD will flash
simultaneously.
● Ensure live and neutral terminals of the power socket are not reversely connected
when testing RCD trip current, otherwise L-PE, L-N and N-PE icons on the lower left
part of LCD will flash simultaneously.
● Please take extreme caution when testing RCD trip current, for it is performed under
high-voltage status.
● To avoid electric shock, remove away all test leads from the Tester before replacing
the battery.
● Do not measure with the battery cover opened.
● Do not mix old and new batteries for use.
● When low battery indicator “ ” shows on LCD, please replace the battery timely.
To replace the battery, follow steps as below:
(1) Power off the Tester (set the rotary switch to OFF) and remove away the test leads.
(2) Unscrew the battery cover, remove the battery cover and replace the batteries with
8pcs new batteries.
(3) Screw up the battery and tighten up the screws.
Repair:
When it become necessary to calibrate or repair the Tester, please have it serviced by
qualified professional personnel or designated service center.
P/N:110401108117X DATE:2018.12.26 REV.6