READ AND SAVE THESE INSTRUCTIONS
MODEL DEV1200
EXTERIOR MOUNTED VENTILATOR
FOR USE WITH VIKING VCWH, VICH, DBCV, DICV, DCWH, DCWL, DCWN,
DTWS AND DCIH RANGE HOODS. 30" TO 66" WIDE, 9" TO 18" HIGH.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manu-
facturer. If you have questions, contact the manufac-
turer or your distributor.
2. Before servicing or cleaning unit, switch power off at
service panel and lock the service disconnecting means
to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a
tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction
codes and standards.
4. Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American Soci-
ety for Heating, Refrigeration and Air Conditioning Engi-
neers (ASHRAE), and the local code authorities.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive material and vapors.
2. To avoid motor bearing damage and noisy and/or unbal-
anced impellers, keep drywall spray, construction dust, etc.
off power unit.
3. Please read specification label on product for further informa-
tion and requirements.
4. Electrical circuit, including speed control, (if used), must be
rated 6 AMPS minimum.
PLAN THE
INSTALLATION
1. Locate the ventilator so
the length of the duct run
and number of elbows
needed are kept to a mini-
mum.
2. Where possible, ventilator
should be centered be-
tween wall studs or roof
rafters.
3. Avoid pipes, wires, or other
ductwork that may be run-
ning through the wall.
ALL INSTALLATIONS
MODEL VOLTS AMPS CFM DUCT SIZE
DEV1200 120 3.0 1200 10" DIA.
SPECIFICATIONS
INSTALLER: Leave This Manual With The Homeowner
HOMEOWNER: Use And Care Information On Page 4
TYPICAL ROOF MOUNTED INSTALLATION TYPICAL WALL MOUNTED INSTALLATION
5. When cutting or drilling into wall, or ceiling, do not
damage electrical wiring or other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce risk of fire, use only metal ductwork.
8. This unit must be grounded.
WARNING
MODEL DEV1200
EXTERIOR VENTILATOR
10" ROUND
DUCT
SOFFIT
WALL HOOD
CANOPY
(island canopy available)
MODEL
DEV1200
EXTERIOR
VENTILATOR
10" ROUND DUCT
SOFFIT
10" ROUND ELBOW
WALL HOOD
CANOPY
(island canopy available)
Blower Dimensions
22 x 30.828 x 12.724
11" dia.
11" dia.
11" dia.
11" dia.
hole
hole
hole
hole
22"
22"
22"
22"
Guide hole
Guide hole
Guide hole
Guide hole
(centered between studs)
(centered between studs)
(centered between studs)
(centered between studs)
22"
29½"
29½"
29½"
29½"29½"
1411
/
16 "
11
11
11
1113
13
13
13
/
/
/
/
16
16
16
16"
"
"
"11 13
/
16"
17"
17"
17"
17"
Wall Stud
Wall Stud
11" dia.
hole
17"
1¼" dia.
1¼" dia.
1¼" dia.
1¼" dia. hole
hole
hole
hole1¼" dia. hole
3
"
Ø
Ø
Ø
ØØ
Ø
Ø
Ø
ØØ
REMO
REMO
REMO
REMOVE
VE
VE
VE
SIDING
SIDING
SIDING
SIDING
REMOVE
SIDING
Guide hole
(centered between studs)
1. Choose a position on the outside wall. Make sure that no
wall studs, pipes or wires run through the opening area.
2. From inside, mark and drill a guide hole centered
between wall studs.
PREPARE THE INSTALLATION
LOCATION
ROOF INSTALLATIONS
22" 2"
7"
29-1/2"
2"
WALL INSTALLATIONS
1. Locate the ventilator on the rear slope of the roof. Place
it in a location to minimize duct run. The location should
be free of obstacles (T.V. leads, electrical lines, etc.). If
the ventilator top is level with the roof peak, it will not be
seen from the street. Keep this approximate location in
mind as you work from within the attic.
2. Mark and drill a guide hole centered between roof
rafters.
2
3. From the outside, use the guide hole as a starting point
to lay out the installation:
A. Use a T-square to measure 913/16" to the left of the
guide hole, then up 1211/16" to locate the top-left
corner of the layout.
B. Starting from the top-left corner, mark the rectan-
gular cutout (18" W x 20½" H) and remove only the
shingles in this area.
C. Mark an 11" diameter hole centered on the guide
hole. Cut this hole through the roof board(s).
D. Mark and cut a 1¼" diameter hole through the roof
board(s) where shown.
4. For flat roof installations, build a curb that will mount the
ventilator at a minimum pitch of 2/12. Discharge end of the
ventilator should be pointed away from prevailing winds.
PREPARE THE INSTALLATION
LOCATION
11" dia.
11" dia.
11" dia.
11" dia.
hole
hole
hole
hole
20½"
20½"
20½"
20½"
11" dia.
hole
1"
Ø
Ø
Ø
Ø
Ø
9
9
9
9
11
11
11
11
/
/
/
/
16
16
16
16"
"
"
"
20½"
Ø
Ø
Ø
Ø
Ø
15"
9
13
/
16"
18"
18"
18"
18"
12
12
12
12 11
11
11
11
/
/
/
/
16
16
16
16"
"
"
"
1¼" dia.
1¼" dia.
1¼" dia.
1¼" dia. hole
hole
hole
hole
1¼" dia. hole
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
Roof Rafter
REMO
REMO
REMO
REMOVE SHINGLES
VE SHINGLES
VE SHINGLES
VE SHINGLES
REMOVE SHINGLES
Roof Rafter
Guide hole
Guide hole
Guide hole
Guide hole
(centered
(centered
(centered
(centered
between rafters)
between rafters)
between rafters)
between rafters)
Guide hole
(centered
between rafters)
12 11
/
16"
18"
3. From the outside, use the guide hole as a starting point
to lay out the installation:
A. Use a T-square to measure 1113/16" to the left of the
guide hole, then up 1411/16" to locate the top-left
corner of the layout.
B. Starting from the top-left corner, mark the rectan-
gular cutout (22" W x 29½" H) and remove only the
siding in this area.
C. Mark an 11" diameter hole centered on the guide
hole. Cut this hole through the roof board(s).
D. Mark and cut a 1¼" diameter hole through the roof
board(s) where shown.


Produkt Specifikationer

Mærke: Viking
Kategori: Emhætte
Model: DEV1200S

Har du brug for hjælp?

Hvis du har brug for hjælp til Viking DEV1200S stil et spørgsmål nedenfor, og andre brugere vil svare dig




Emhætte Viking Manualer

Viking

Viking TVWH480DB Manual

6 Oktober 2024
Viking

Viking VWH3610RE Manual

9 September 2024
Viking

Viking VCIH56608SS Manual

25 August 2024
Viking

Viking VWH530481DG Manual

24 August 2024
Viking

Viking TVWH480BW Manual

19 August 2024
Viking

Viking TVWH360FW Manual

15 August 2024
Viking

Viking TVWH660AW Manual

12 August 2024

Emhætte Manualer

Nyeste Emhætte Manualer

Candy

Candy CSD9MX Manual

14 August 2025
Candy

Candy CSD6MX Manual

14 August 2025
Candy

Candy CPY5MWP-07 Manual

14 August 2025
Candy

Candy CPY5MXP-07 Manual

14 August 2025
Candy

Candy CDG6CBGP-07 Manual

14 August 2025
Candy

Candy CVMI970LX/UK Manual

14 August 2025
Candy

Candy CPY7MX-UK Manual

14 August 2025
Candy

Candy CBT60RX-07 Manual

14 August 2025
Candy

Candy CBT60RWG-07 Manual

14 August 2025