AirGo 16-32A Manual


Læs gratis den danske manual til AirGo 16-32A (2 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 2 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 1.5 anmeldelser. Har du et spørgsmål om AirGo 16-32A, eller vil du spørge andre brugere om produktet?

Side 1/2
R
S
C
Compressor
Run
Capacito
r
To Fan
Star
t
Run
Common
Contactor
1P/2P
Field
Supply
H
C
F
SC
SR
HH
Run
Common
Start
R
R
S
S
C
C
Run
Capacito
r
Field
Supply
To
Fan
(Color May Vary
)
CC
FF
rr
otcatnoCo tcatnoC
pp2/p/1
CompressorCompressor
Run Winding(R
)
Run Capacitor( RC
)
Active( T2
)
Start Winding( S)
Not Used
Compressor Common (C
)
SureStart®
SureStart® 115/230V
Instruction Guide
SSxB Series / Single Phase
Parts List:
1 x SureStart Soft starter
1 x Red Lead
1 x Blue Wire
1 x Black Wire
Field Wiring Specifications:
Wire Range: 8 to 12 AWG Cu, stranded, for terminals (Run Winding (R) and Active(T2))
12 to 16 AWG Cu, stranded, for terminals (Run Capacitor (RC), Start Winding (S), and Compressor/Motor Common (C), these are supplied)
Tightening Torque: 11.5 LBSIN LARGE TERMINALS, 4.5LBSIN SMALL TERMINALS.
Field wiring conductors shall be rated 167°F [75°C]
Minimum end use enclosure size: 10” x 8” x 6”
LED Flash Codes:
1/2
DMSxxx
Instruction Guide
1 x Brown Wire
1 x Mounting Bracket
1 x Green Connector
1 x Pack of two Ferrules
Caution& Warning:
1 All voltage to equipment MUST be disconnected before removing any devices.
2 Allow 2 minutes to discharge run capacitor before disconnecting.
3 Do not swap the Run & Start Windings.
4 Prior to installation, be sure all start capacitors & start relays, along with hard-starters and/or any other start-assist devices, are removed.
5 The start capacitor is built into the soft starter.
6 Loose terminals can lead to heating & subsequent damage to the soft starter. As per, UL508 standard, ensure below tightening torques.
7 OPENING OF THE SOFT STARTER UNIT WILL VOID THE WARRANTY!
Flash Code Time to re-start attemptDefinition
Low Voltage
Lockout on 3 failed starts
Lockout on overcurrent
Cycle delay / Faults
Rapid Flash (10 / 1 sec)
Triple Flash (3 / 3 secs)
Slow Flash (1 / 3 secs)
Steady Flash (1 / 1 sec
)
3 min
50 min
10 min
3 min
[NOTE: LED fault indicator remains off in normal running mode.]
SureStart
Installation
Sample Wiring Schematic
CRIMP CORRECT SIZED FERRULES TO ENSURE PROPER TERMINATION
INSERTION LENGTH OF FERRULE “D”: 11 ± 1 MM 0.43 ±0.04”
CABLE BEND RADIUS “R” > 38MM 1.5” MINIMUM
SureStart® 115/230V HVAC installation SSxB Series:
This model SureStart® functions only as a soft starter, a contactor is still required. This model can be suitable for a wide range of applications. Some
degree of care is needed to determine the correct wiring.
* ST Start Thermistor
* SR Start Relay
* SC Start Capacitor
Note: If installed, remove all of the above
devices(May be factory installed)
L
T
LT
Eltwin Group
sales@eltwin-hyper.com
eltwin-hyper.com
Technical Contact: techsupport@eltwin-hyper.com
AG
AIRGO SOFT START 120/240V
MES Group, LLC 414-507-7661 emily.sensiba@mesgrp.com installcentral.com
INSTRUCTION GUIDE | SINGLE PHASE
LED FLASH CODES:
FIELD WIRING SPECIFICATIONS:
Wire Range: 8 to 12 AWG Cu, stranded, for terminals (Run
Winding (R) and Active(T2)) 12 to 16 AWG Cu, stranded,
for terminals (Run Capacitor (RC), Start Winding (S), and
Compressor/Motor Common (C), these are supplied)
Tightening Torque: 11.5 LBS-IN LARGE TERMINALS, 4.5LBS-
IN SMALL TERMINALS.
Field wiring conductors shall be rated 167°F [75°C]
Minimum end use enclosure size: 10” x 8” x 6”
• CRIMP CORRECT SIZED
FERRULES TO ENSURE PROPER
TERMINATION
• INSERTION LENGTH OF FERRULE
“D”: 11 ± 1 MM (0.43 ±0.04”)
• CABLE BEND RADIUS “R” > 38MM
(1.5”) MINIMUM
APPLICATIONS
Residential AC
Commercial AC
• Marine
• RV
PARTS LIST:
1 x AirGo soft starter
1 x Red Wire
1 x Blue Wire
1 x Black Wire
1 x Brown Wire
1 x Mounting Bracket
1 x Green Connector
1 x Pack of Two Ferrules
AIRGO 120/240 HVAC INSTALLATION:
The AirGo a/c soft starter functions only as a soft starter, a contactor
is still required. this model is suitable for a wide range of applications.
Some degree of care is needed to determine correct wiring.
CAUTION/WARNING:
1. All voltage to equipment MUST be disconnected
before removing any devices.
2. Allow 2 minutes to discharge run capacitor before
disconnecting.
3. Do not swap the Run & Start Windings.
4. Prior to installation, be sure all start capacitors &
start relays, along with hard-starters and/or any
other start-assist devices, are removed.
5. The start capacitor is built into the soft starter.
6. Loose terminals can lead to heating & subsequent
damage to the soft starter. As per, UL508 standard,
ensure below tightening torques.
7. OPENING OF THE SOFT STARTER UNIT WILL VOID
THE WARRANTY!
Flash Code Denition Time to re-start attempt
Rapid Flash (10/1 sec) Low voltage 3 minutes
Triple Flash (3/3 sec) Lockout on 3 failed starts 50 minutes
Slow Flash (1/3 sec) Lockout on overcurrent 10 minutes
Steady Flash (1/1 sec) Cycle delay / faults 3 minutes
Note: LED fault indicator remains o in normal running mode
Sample schematic is not a reection of all HVACR units in
the eld. If the wiring differs from the base schematic or if it
needs to be wired through a control board, please contact us:
cramermes@gmail.com or 262-893-4375


Produkt Specifikationer

Mærke: AirGo
Kategori: Ikke kategoriseret
Model: 16-32A

Har du brug for hjælp?

Hvis du har brug for hjælp til AirGo 16-32A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret AirGo Manualer

AirGo

AirGo 16-32A Manual

10 December 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Waterstone

Waterstone 5410 Manual

11 December 2025
Extron

Extron EDID 121 Manual

11 December 2025
Ozito

Ozito PXCLS-1500 Manual

11 December 2025
Berkel

Berkel Icon Line 170 Manual

11 December 2025
Crosley

Crosley Enzo CF1133 Manual

11 December 2025
Schlage

Schlage L9056 Manual

11 December 2025
Bosch

Bosch SMS4HCI19E Manual

10 December 2025