Broan FIN-6MD Manual

Broan Klimaanlæg FIN-6MD

Læs gratis den danske manual til Broan FIN-6MD (4 sider) i kategorien Klimaanlæg. Denne vejledning er vurderet som hjælpsom af 12 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 6.5 anmeldelser. Har du et spørgsmål om Broan FIN-6MD, eller vil du spørge andre brugere om produktet?

Side 1/4
1
FRESH IN
TM
FIN-6MD
INSTALLATION NSTRUCTIONS I
Please take note that this manual uses the following symbols to emphasize particular information:
WARNING
Identifies an instruction which, if not followed, might cause serious personal
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit
and/or its components.
💡 Indicates a supplementary information that may relate to optional parts or
simply aim to facilitate a task.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE
FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the
manufacturer.
2. Before cleaning this unit, turn off the power to the AHU at service panel. (Powered by AHU)
3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
4. Installation work must be done by qualified person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
5. When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. When cleaning or performing installation of this unit, it is recommended to wear safety glasses and gloves.
7. When applicable local regulation comprises more restrictive installation and/or certification requirements,
the aforementioned requirements prevail on those of this document and the installer agrees to conform to
these at his own expense.
8. The unit must be mounted at least 3.3 feet (1.0 meter) away from any accessible opening of the duct.
9. Must be powered using a Class 2 transformer rated 10VA or higher.
CAUTION
1. Please read specification label on product for further information and requirements.
2. Do not intake air into spaces within walls or ceiling or into attics, crawl spaces, or garage. Do not attempt
to recover the exhaust air from a dryer or a range hood.
3. Intended for residential installation only in accordance with the requirements of NFPA 90B.
4. When leaving the house for a long period of time (more than two weeks), a responsible person should
regularly check if the unit operates adequately.
5. At least once a year, the unit mechanical and electronic parts should be inspected by qualified service
personnel.
6. Since the electronic control system of the unit uses a microprocessor, it may not operate correctly because
of external noise or very short power failure. If this happens, turn power off at AHU service panel and wait
approximately 10 seconds. Then, restore the power to the unit.
7. Outdoor intake hood must be weather tight and comprise a bird screen.
8. Should you decide to dispose of this unit or of parts of it, do so in accordance with local laws and regulation.
RESIDENTIAL USE ONLY
For complete warranty statement, and to register your
product online, go to www.broan-nutone.com.
READ AND SAVE THESE
INSTRUCTIONS
1. PREPARATION
Before you start:
Choose the best location and installation type for the FIN-6MD according to the current system. Ducting
widely affects the performance of this type of device. Use the shortest, straightest duct run possible to
maximize the results.
CAUTION
Do not install in an area where the temperature may exceed 160°F.
The installer shall ensure that, if necessary, an in-line heater sized according to the required airflow and outside
design heating temperature from Manual J or ASHRAE table is installed to ensure that the air delivered to the
AHU is never below the minimum temperature allowed by the manufacturer. The in-line heater shall have an
integrated airflow sensor and an over temperature sensor to prevent heating in no-flow or low-flow conditions.
When deciding if a preheater is required and whether it should be installed BEFORE or AFTER the FIN-6MD,
consider the following:
The FIN-6MD’s minimum operating temperature is -4°F.
The temperature distributed to the AHU should never be below the temperature recommended by the
AHU manufacturer.
The minimum distance between the preheater and the FIN-6MD is 12 inches.
2. INSTALLATION
Always respect the orientation of the FIN-6MD and the direction of the airflow, as indicated on the
unit.
Direct-to-AHU is the fastest and easiest method:
1. Make a 6-inch diameter hole in the return duct of
your AHU.
2. Install the seal on the FIN-6MD port that will insert
the AHU ducting. Make sure that the direction of the
airflow indicated on the unit is respected.
3. Install the 3 installation brackets on the unit, as
illustrated.
4. Mark and drill holes for the brackets on the AHU
ducting and, using appropriate screws, secure the
FIN-6MD to the duct of the AHU, making sure it is
level horizontally.
💡 Use self-drilling screws (not included) to avoid
marking and drilling steps.
5. Follow steps in section 3 to connect the insulated
duct to the FIN-6MD.
6. Perform the electrical connection to the AHU following the wiring diagram in section 4.
Through a horizontal surface:
1. Make a hole in the surface that the duct will run
through. Size the hole so that the vapor barrier of the
insulated ducting is not damaged, and the insulation
not compressed.
2. Install the 3 installation brackets on the unit, as
illustrated.
3. Run a piece of insulated duct through the hole and
connect to the FIN-6MD following the steps in
section 3. Make sure the direction of the airflow as
indicated on the unit is respected.
4. Push the excess ducting on the other side of the
surface and, using appropriate screws, secure the
FIN-6MD to the surface.
5. Run the insulated duct to the AHU and connect to
the AHU ducting, making sure that the vapor barrier
sealing is leak-free.
6. Follow steps in section 3 to connect the second
insulated duct to the FIN-6MD.
7. Perform the connections to the AHU following the
wiring diagram in section 4.
Mounted under, above or beside a structure:
1. Install 2 installation brackets on the unit, as illustrated, according to the surface the unit will mount to.
2. Using appropriate screws, secure the FIN-6MD to the structure, making sure it is level horizontally. Make
sure the direction of the airflow as indicated on the unit is respected.
3. Follow steps in section 3 to connect both insulated ducts to the FIN-6MD.
4. Run the insulated duct to the AHU and connect to the AHU ducting, making sure that the vapor barrier
sealing is leak-free.
5. Perform the connections to the AHU following the wiring diagram in section 4.
UP
MOUNTED UNDER
MOUNTED ABOVE
MOUNTED BESIDE
SUSPENDED
LOGIC DIAGRAM
WIRING COLOR CODE
Reference : 1103507 rev. C
BLK BLACK
BLU BLUE
GRN GREEN
PNK PINK
RED RED
WHT WHITE
YEL YELLOW
Low voltage factory wiring
Low voltage field wiring
1
J1
1
1
J7
J9
1
J5
1
LED1
(power)
LED2
(Status)
1
J4
19
M2
RED
BLU
YEL
PNK
Damper Motor
Harness
Y
W
Gf
G
R
C
Standby Switch
SO
SI
AHU Wiring
A1
ELECTRONIC ASSEMBLY
Mode
Selection
CFM Ratio/
Damper
Selection
Power
Supply
(12V)
Low Voltage
(24VAC)
K2
R
C
G
Gf
PTC
J4-7
J4-6
J4-4
J4-5
Power
Supply
(3.3V)
MCU
K1
K2
M2
Stepper
Driver
J5-1,2,3,4
WIRING DIAGRAM
Not Used
J6
Humidity/
Temperature
Sensor
S1
GRN
RED
WHT
BLK
MCU
+24VAC Supply
Mode
Accessory
FIN-DCS
Accessory Kit
Voltage
Detection
K1
J1-2
J1-1
Accessory
24VAC
(optional)
3. CONNECTING THE INSULATED DUCTS TO THE UNIT
CAUTION
Always use insulated ducting of a minimum R-4 insulation factor.
1. Slide the inner flexible duct over the port and secure it using a tie wrap.
2. Pull the insulation over the flexible duct and port without compressing it.
3. Use duct tape to seal the outer membrane of the insulated duct to the outer ring of the port.
WARNING
Make sure the outdoor intake hood is at least 18 inches above the ground and 6 feet away
from any of the following: Dryer exhaust, high-efficiency furnace vent, central vacuum vent,
gas meter exhaust, gas barbecue-grill, any exhaust from a combustion source, garbage bin
and any other source of contamination.
💡 Make sure that the outdoor intake hood is easily accessible for annual maintenance. If located above the
first floor, place it close to a window or balcony to allow easy access.
4. WIRING DIAGRAM
WARNING
Risk of electric shock. Electrical wiring must be done by qualified personnel in
accordance with all applicable codes and standards. Before connecting wires, switch off
the power to the AHU at service panel and lock service disconnecting means to prevent
power from being switched on accidentally.
CAUTION
Faulty connections can cause damage to the AHU, to the thermostat and/or to this unit.
Always double check connections before turning power back on.
Scan to view our
installation video.
5011110
CONFORM TO
UL STD. 1995
💡 The terminal block can
be removed for easier
connection.
💡 Use the included tie
wrap and the loop
above the terminal
block to secure the
wires and reduce
the risk of broken
connections.
Seal
AHU wiring next page
1103500D
2
4.1 AHU WIRING
Synchronize the FIN-6MD operation with the heating and cooling run-time to prevent unnecessary central fan
operating time (refer to the dotted lines in the above diagram).
5. SETTING UP THE UNIT
When powered ON, the FIN-6MD performs a 30-second booting sequence followed by a 30-minute period
where is stays OFF, but will activate if a heating or cooling call is sent to the AHU.
Refer to local building codes to determine the required airflow.
1. Doublecheck the wiring, and turn power back ON to the AHU.
2. Set the thermostat to send a heating or cooling call, or jump R and Y on the terminal block. This will
force the ventilation ON for at least 5 minutes.
3. Measure the airflow.
If it needs adjustment, perform steps 4. If the airflow does not need adjustment, go to step 5.
4. The damper is factory set to fully open position. To adjust it, set the left pot to DAMPER
ADJUSTMENT to start the AHU blower, and wait 5 seconds. The LED will blink continuously to
indicate the unit is in DAMPER ADJUSTMENT mode.
While measuring the airflow, adjust the damper using the RUN TIME % pot until you’ve reached the
desired value.
5. Select the desired mode according to the table and map in section 7.3. Doing so also saves the
damper adjustment made in the previous step if applicable.
6. Set the RUN TIME % pot.
7. Install the supplied cover to protect the adjustment pots and
prevent an accidental change of settings. Note that the hole may
be hidden by the label.
6. TESTING
When powered ON, the FIN-6MD performs a 30-second booting sequence followed by a 30-minute period
where it stays OFF, but will activate if a heating or cooling call is sent to the AHU.
6.1 BLOWER DOOR TEST FORCE THE DAMPER CLOSED ( )
If the access to the integrated switch OR to the remote switch (if
applicable) is , set the integrated switch OR remote switch to easy
OFF.
If the access to the switch is , such as in an attic:not easy
1. Turn OFF the power to the AHU at the service panel.
2. Turn the power to the AHU back ON at the service panel.
3. Wait 30 seconds for the booting sequence to execute.
4. Make sure that the thermostat will not send a heating or cooling
call.
5. Unit is OFF with its damper closed for 30 minutes, but will
activate if a heating or cooling call is sent to the AHU.
6.2 VENTILATION TEST FORCING THE UNIT ( ON):
1. Turn OFF the power to the AHU at the service panel, and make sure that the integrated or remote switch
is set to ON.
2. Turn the power back ON at the service panel.
3. Wait 30 seconds for the booting sequence to execute.
4. Set the thermostat to send a heating or cooling call, or jump R and Y on the terminal block. This will force
the ventilation ON for at least 5 minutes.
7. USER INFORMATION
7.1 INTEGRATED AND REMOTE SWITCHES
This unit is equipped with an integrated ON/OFF switch. For more
convenience, your FIN-6MD can also be connected to a remote
switch.
To use a remote switch, disconnect the integrated switch and
connect the remote switch in the same manner that the integrated
one was connected.
7.2 USER ERVICING NSTRUCTIONS S I
Inspect the outdoor air intake at least once a year.
These recommendations may change according to the environmental conditions in your area.
Y
W
G
F
G
R
C
COM
NC
NO
Internal
Logic
CFIS
System
Y
W
G
R
C
Y W G R C
Thermostat
Optional Installation Wiring for Synchronization
AHU
AHU Wiring Options
J4
Mandatory Installation Wiring
CFIS Internal Hard Connections
Ref. : 1103507 rev. C
Damper
fully open
Damper
half open
Run time % =
Required Airflow
Example : Run Time % =
60 CFM
= 50%
Measured Airflow 120 CFM
ON
Integrated switch
ON
Integrated switch
7.3 COMFORT ODE M
Should the air inside your house become too humid, or if such conditions want to be prevented, the operation
mode of your FIN-6MD can be changed from a Code-Compliant one (modes 1 and 2) to a Comfort Mode
(modes A to E). Refer to the map below to make the right choice.
When making such change, make sure to only change the Mode and to leave the Run time % as it was set by
your installer. If in doubt, refer to your HVAC contractor.
7.4 TROUBLESHOOTING
A LED indicator is located to the right of the terminal block on the unit and communicates the different states
of the unit. Blinking patterns and ways to address them, if applicable, are as follows:
Sensor error 1 blink Disconnect the terminal block, and connect again. If the error
persists, replace the unit.
Damper error 2 blinks Disconnect the terminal block.
Open unit (see image below).
Perform a visual inspection and remove any debris hindering
damper movement.
Close unit and put the terminal block back in place.
If error persists, replace the unit.
Damper
adjustment mode
Continuous blink This is normal while the unit is in adjustment mode.
Learning mode 1 s ON, 10 s OFF This is normal. Will blink for 48 hours after being powered ON.
VN0012A
5B
5A
Selected mode* Climate Zones**
1 - Ashrae 2010/IRC/IMC (factory set)
Zones 1-5
2 - Ashrae 2016/2019
Zones 1-5
A - Comfort mode Hot / Humid #1
Zones 2A and 1
B - Comfort mode Hot / Humid #2
Zones 1 and 2A
C - Comfort mode Hot / Dry
Zone 2B
D - Comfort mode Mixed / Humid
Zones 3A, 4A, 5A, 3C and 4C
E - Comfort mode Mixed / Dry
Zones 3B, 4B and 5B
*Refer to the label on the unit for the full limits table.
**As defined by the Department of Energy.
OFF
20
30
40
5060
70
80
90
100
MODE RUN
TIME %
Damper
adjustment
(wait 5 sec.)
1
2
A B
C
D
E
Internal insulation
8. AVAILABLE ACCESSORIES
1. Service Parts
You can order the S1103502 replacement hardware kit, which includes the same components as the one
included with the unit.
2. Dry Contact Synchronization
Your FIN-6MD can also be synchronized with other HVAC units via a 24 VAC dry contact.
• Output mode: To activate other units operation. Requires a separate 24 VAC relay.
• Input mode: To activate your FIN-6MD operation.
Look for the FIN-DCS option kit that can be ordered separately.
NOTE: If the unit is turned off, this functionality will not work.