Crestron CLX-2IND Manual


Læs gratis den danske manual til Crestron CLX-2IND (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 36 personer og har en gennemsnitlig bedømmelse på 4.2 stjerner ud af 18.5 anmeldelser. Har du et spørgsmål om Crestron CLX-2IND, eller vil du spørge andre brugere om produktet?

Side 1/4
CLT- & CLX-2IND/4IND
Terminal Block & Module Locations in Single-wide Enclosure
(CLT/CLX-4IND shown)
Functional Summary
TERMINAL BLOCK
(LEFT)
MODULE
GROUNDING
TERMINAL BLOCK
The CLT/CLX-2IND is a 2-inductor terminal block and
module kit while the CLT/CLX-4IND is a 4-inductor
terminal block and module kit. Inductor modules are
typically used to reduce hum from incandescent lamps
that are connected to dimmer modules in a Crestron
lighting system. These kits can be mounted in any
Crestron Automation Enclosure (CAEN-Series
Enclosures). The terminal block is for connecting wires
into and out of the inductor module. The inductor is wired
in series between the output of the dimmer module and
the load. The maximum load for any inductor in the
module is 16 amps.
Each of these Terminal Block and Module kits is
considered single entities and must be used together. The
terminal blocks (CLT-2IND and/or CLT-4IND) are
shipped separately from their respective modules
(CLX-2IND and CLX-4IND) to permit termination of the
field wiring to the terminal block prior to installation of
the module, as described in this guide.
Installation Terminal Block & Module Locations in Double-wide
Enclosure (CLT/CLX-4IND shown)
The terminal block and module must be mounted into a
Crestron Automation Enclosure by a licensed electrician,
in accordance with all national and local codes.
TERMINAL BLOCK
(LEFT)
MODULES TERMINAL BLOCK
(RIGHT)
GROUNDING
TERMINAL
BLOCKS
CAUTION: This equipment is for indoor use only.
Mount in a well-ventilated area. The ambient
temperature must be 32° ° ° °F to 104 F (0 C to 40 C).
The relative humidity must be 10% to 90% (non-
condensing).
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are
installed along the right side of single-wide enclosures
and side-by-side in the center of double-wide enclosures.
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so
that they can be properly wired. Refer to the illustrations
shown in the next column when considering the location
of terminal blocks and modules within an enclosure.
NOTE: Inductor modules and terminal blocks
should be installed above the dimmer modules,
towards the top of the CAEN enclosure.
Crestron Electronics, Inc. Installation Guide – DOC. 6315
15 Volvo Drive Rockleigh, NJ 07647 11.04
Tel: 888.CRESTRON
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Terminal Block & Module Crestron CLT- & CLX-2IND/4IND
Installation and Field Wiring Wiring CLX-2IND Terminal Block to the Feed and Load(s)
for Single-Wide Enclosure and Left Side of Double-Wide
Enclosure
1. Use the two supplied self-tapping pan Phillips
screws (8B x ¼” length) to secure the terminal
block and the appropriate (left or right) wiring
label to the Crestron Automation Enclosure. The
wiring label lies beneath the terminal block as
shown on this and the following page.
FROM DIMMER
TO LOAD
FROM DIMMER
TO LOAD
NOTE: Both left and right wiring labels are
provided. The left-side labels are common for both
single and double-wide enclosures. The right-side
labels are only used in double-wide enclosures since
the modules and terminal blocks along the right side
must be inverted when mounting.
NOTE: Use copper conductors only – rated 75°C
2. With the circuit breaker turned off, connect the
dimmer module output (IN) and the load (OUT)
wires to the IND terminal block per the markings
provided on the wiring label (as shown in the
following diagrams). Terminal blocks accept one
14 - 10 AWG wire. Wires should be stripped to
½ inch. Tighten terminal blocks to 9 in-lbs.
3. Test the circuit for electrical faults by turning on
the circuit breaker and checking that the breaker
does not trip and that the proper lighting loads
are energized.
Wiring CLX-2IND Terminal Block to the Feed and Load(s)
for Right Side of Double-Wide Enclosure
FROM DIMMER
TO LOAD
TO LOAD
FROM DIMMER
2
Terminal Block & Module: CLT- & CLX-2IND/4IND Installation Guide – DOC. 6315


Produkt Specifikationer

Mærke: Crestron
Kategori: Ikke kategoriseret
Model: CLX-2IND

Har du brug for hjælp?

Hvis du har brug for hjælp til Crestron CLX-2IND stil et spørgsmål nedenfor, og andre brugere vil svare dig