Daikin KRCS01-5B Manual


Læs gratis den danske manual til Daikin KRCS01-5B (1 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 3.8 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Daikin KRCS01-5B, eller vil du spørge andre brugere om produktet?

Side 1/1
3P657596-1
KRCS01-5B 3P657596-1
DAIKIN Air Conditioners
Be sure to read this installation manual before conducting the installation
of this product. Installation must be conducted according to this manual.
Installation Manual
Remote
Caution
remote sensor.
● SECOND CODE No. change must be conducted according to following table,
from “02” to “01”.
Local setting for case of SkyairIMPORTANT
Mode No. FIRST CODE No. SECOND CODE No.
Changed
Default
15 (25) 10 02 01
Setting detail be refer to .
● Make sure the no errors be sure to operation test after local setting.
Notes) Comfortable eco-dry control function is not work in case of installing to
comfortable eco-dry control function by humidity detection supported models.
Accessories description
Name
Shape
Quantity
Clamp
Check it the following accessories are attached to this product.
Sensor box
Extension cable
(2-core, 12m)
Mounting screw
(M4×16)
Installation
manual
Other
1 pc.
1 pc.
1 pc.2 pcs. 2 pcs.
Mounting the Sensor box
(1) Selection of mounting location.
Sensor box (1) have thermistor for temperature detection built-in.
Select the mounting location taking the following cautions into account.
1. Where the average temperature of an air conditioned room can be detected.
2. Where it is not exposed to the direct sunlight.
3. Where it is not influenced by other heat sources.
4. Where it is not exposed to the direct discharge air from the air conditioner.
5. Where it is not exposed to the outdoor air infiltrated into the room by opening
the door.
(2) Mounting
● Remove the cover of the sensor box (1).
Insert a flat blade screw driver into the
sensor box (1) concave part (2 locations).
Remove the cover pushing up the hook
to the cover of the sensor box (1).
<Cautions>
Do not push the nail powerfully with a narrow flat blade
screw driver, because you may break off the hook.
about 6mm width
flat blade screw driver
Sensor box (1)
tool. Pass the extension cable (2) through the hole and fasten the wires to the
terminals with screws.
● To avoid tensile force on the terminals, pass the attached clamp (3) through
the holes shown in the below right figure and tighten the extension cable (2)
with the attached clamp (3) at the sheathed part.
(The knot must come to the box inside.)
<Cautions>
● When wiring the extension cable (2), the air holes of sensor box (1) will not be
blocked.
● When the extension cable is longer than necessary, cut it to the appropriate
length, peel the insulation, attach the ring type crimp style terminal for M3
(field supplied) and carry out the wiring. The length of insulation to be peeled
off is as shown below.
(Work carefully so that the connector side may not be cut.)
For M3
RING TYPE CRIMP STYLE TERMINAL
(field supplied)
<Procedure>
1. When wiring to the indoor unit PCB, remove the existing sensor from
PCB (X16A).
2. Extension cable (2) connect to PCB (X16A).
4. Fit the sensor box cover into the sensor box (1).
After the sensor is installed and the wiring is completed, conduct cooling and
heating operation in order to make sure of detecting temperature accurately
(not to be uncooled or unheated).
Local setting
Clamp hole
Sheathed part
Sensor box (1)
Clamp (3)
(knot)
Extension cable (2)
Fasten the terminals with
care to prevent the wires
from touching each other.
Switch box
(for single unit)
(field supplied)
Sensor
box cover
Mounting screw (4)
Sensor
box (1)
Metal plate
(for single unit without hole)
(field supplied)
Mounting frame which
matches with the switch box
(field supplied)
Extension cable (2)
Through hole
Sheathed part
Clamp (3)
(knot)
Sensor
box (1)
Thermal insulation material
2
For embedded wiring
Figure 2
Holes to be tapped in the
metal plate on site (unit: mm)
2-M4
(70)
(120)
42
21
32
Sheathed part
45
Connector
connectionExtension cable (2)
Terminal connection
Sensor box (1)
Extension
cable (2)
1. Remove
2. Connect
Existing sensor
Indoor unit
Indoor unit
Printed circuit board (PCB)
Operation test after mounting the sensor
● Make sure the completing all work of indoor and outdoor unit.
● Make sure the closing switch box cover of indoor unit, casing for outdoor unit
and cover for piping.
Set the local setting by remote controller after turn on.
After changed to settings, Turn off and turn on again.
Local setting
Mode No.
Changed
15 (25) 10 02 01
(Notes)
● Local setting set by changing three of “Mode No.”, “FIRST CODE No.”,
“SECOND CODE No.”.
● Setting procedure and operating method refer to installing manual attach to
remote controller.
Notes) “Mode No.” setting be done to group together.
Case of each indoor units setting or setting confirmation,
set to number in ( ) of “Mode No.”.
● SECOND CODE No. change must be conducted according to following
table, from “02” to “01”.
X16A
Please cut excess clamp for base after fixing.
● Screw the sensor box (1) to the wall surface with mounting screw (4)
(M4×16, 2 places).
Wall surface mounting holes dimension refer to .
If the sensor box cannot be screwed to wall surface, tear off the released
paper and mount it on the wall surface.
Figure 1
Terminal
Sensor
SECOND CODE No.
(1)
(2)
(3) (4)
3. Make sure to securely connect the connectors.
Defective connection may result in incorrect detection of room temperature
or malfunction.
4. Do not splice wires.
5. Lay and clamp the extension cable (2) inside the indoor unit switch box just
like the low voltage line (cord for remote controller).
And do not pass where the extension cable inside the indoor unit switch
box may be affected by the power line (cord for the indoor unit and the
other electric line).
FIRST CODE No. SECOND CODE No.
Default
SECOND CODE No.
Thermal insulation
material
Knockout hole
for cable
Air hole
Released
paper
Sensor box (1)
Sensor box cover
Mounting screw (4)
1
When mounting on the wall
Figure 1
Wall surface mounting holes
(unit mm)
2-M4
42
32
Wiring method
Caution
Connect the extension cable (2) connector side to the indoor unit PCB
(printed circuit board) For connection to the indoor unit, follow the procedure
shown below.
1. Make sure to turn off the power supply before starting the wiring work and
do not turn on until all the work is completed.
Read also the installation manual and the wiring diagram of the indoor unit
when carrying out the work.
2. When wiring the extension cable (2), do not pass where the extension
cable (2) may be affected by the power line or noise.
3. Lay and clamp the extension cable (2) inside the indoor unit switch box
just like the low voltage wire (remote controller wiring).
When doing this work, keep a certain distance between the high voltage
wiring and the low voltage wiring to avoid error of sensor.
Provide protection of the existing cable for sensor without touching indoor
unit PCB.
Indoor unit
Printed circuit board (PCB)
Extension cable (2)
connect to PCB (X16A)
Hook(1)
Hook(2)
● Tap M4 screw holes in the metal plate
(field supplied) as shown in the right drawing
and mount the switch box on the metal plate.
Refer to .
Figure 2
● Pass the extension cable (2) through the sensor
box (1) cable hole and carry out the wiring.
● Pass the attached clamp (3) through the clamp
holes and tighten the extension cable (2) at the
sheathed part as shown in the upper right figure.
Please cut excess clamp for base after fixing.
Please cut excess clamp for base after fixing.
Clamp (3)
(kont)
Pass the cable
through the cable hole
of the indoor unit
Pass the extension
cable (2) through
the hook(1),(2)
≪Wireing method≫


Produkt Specifikationer

Mærke: Daikin
Kategori: Ikke kategoriseret
Model: KRCS01-5B

Har du brug for hjælp?

Hvis du har brug for hjælp til Daikin KRCS01-5B stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Daikin Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer