Læs gratis den danske manual til Daikin KRP928A2S (1 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 4.7 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Daikin KRP928A2S, eller vil du spørge andre brugere om produktet?

Side 1/1
Installation Manual
Remote Control PC-Board Set <KRP928B2S, KRP928BA2S>
3 P 1 5 7 7 0 4 - 2 B
Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies precautions into WARNING and CAUTION.
WARNING :
Failure to follow WARNING is very likely to result in such grave
CAUTION : Failure to follow CAUTION may result in serious injury or
property damage, and in certain circumstances, may result in
a grave consequence.
Be sure to follow all the precautions below ; they are all important for
ensuring safety.
3.Names of Parts and Electric Wiring
WARNING
CAUTION
After installation is complete, test the operation of the PCB set to check
for problems, and explain how to use the set to the end-user.
1.Overview, Features and Compatible Models
This kit is the interface required when connecting the central controller and a Daikin Room Air
Conditioner. Use of the central controller makes it possible to perform the following monitoring
and operations. It is compatible with room air conditioners which have an HA connector S21.
Precaution
1.When reading the Operating / error signals, a separate external power source
(DC 12V) is needed.
2.A separate timer power source (DC 16V) is needed when using the schedule
timer independently, and not in conjunction with other central controllers.
3.The range of temperatures that can be set from the central controller is 18 C to °
32 C in cooling and 14 C to 28 C in heating.° ° °
4.
Fan operation cannot be selected from the central controller or wired remote controller.
5.
Group control (i.e., control of multiple indoor units with a single remote controller) is
not available.
6.Monitoring is not available of the thermo status, compressor operating status,
indoor fan operating status, electric heater, or humidifier operating status.
7.Forced thermo off, filter sign display and reset, fan direction and speed settings,
air conditioning fee management, energy savings instructions, low-noise
instructions, and demand instructions cannot be made.
1.Run / stop for the central controller and wired remote controller, operating mode
selection, and temperature can be set.
2.The operating status, any errors, and the content of those errors can be monitored
from the central controller and wired remote controller.
3.Run / stop for the central controller and wireless remote controller, operating mode
selection, and the temperature setting can be limited by the central controller.
4.Zone control can be performed from the central controller.
5.The unit can remember the operating status of the air conditioner before a power
outage and then start operating in the same status when the power comes back
on.
6.Card keys, operating control panels, and other constant / instantaneous
connection-compatible equipment can be connected.
7.The Operating / error signals can be read.
8.HA JEM-A-compatible equipment can be connected.
9.The indoor temperature can be monitored from the Ve-up controller.
2.Component Parts and Separately-Sold Parts which are Required
This kit includes the following components. Check to ensure that none of
these are missing.
4.Switch Settings
5.Control Codes
7.Combining Equipment
6.Read Operating / Error Display Signal
1234 1234
1234
1
0
ON
OFF
ON
OFF
SW1
S16
S19
S6
F1
SW2
SW3
LED1
Tes1
S1 S8 S5
F2
Once the switches are set and
the wiring complete, secure the
case using the included
screws.
A cable field supply A cable field supply
In case that the device coping
with HA JEM-A is connected
Connecting a Wired
Remote Controller
In case that a central remote
controller is connected
Connecting a Momentary / constant
Contact Input Equipment
Reading the Operating / error Display
¡Tele-con (Field supply)
¡Remote controller
BRC944 Series
¡Card key
(Field supply)
¡Operating control panel
(Field supply)
KRC65, KRC72,
KDC100A10, and KDC101B
Series cannot be connected.
The adapter included with the
remote controller is not used.
DAIKIN
<Wiring procedure>
Supplied connection harness
¡Installation should be left to the dealer or another qualified professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
¡Install the set according to the instructions given in this manual.
Incomplete or improper installation may cause malfunction, electrical shock, or fire.
¡Be sure to use the standard attachments or the genuine parts.
Use of other parts may cause malfunction, electrical shock, or fire.
¡Disconnect power to the connected equipment before starting installation.
Failure to do so may cause malfunction, electrical shock, or fire.
¡An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
¡
Do not install the set in a location where there is danger of exposure to
inflammable gas.
Gas accumulated around the unit at the worst may cause fire.
¡To prevent damage due to electrostatic discharge, touch your hand to a
nearby metal object (doorknob, aluminum sash, etc.) to discharge static
electricity from your body before touching this kit.
Static electricity can damage this kit.
¡Lay this cable separately from other power cables to avoid external
electrical noises.
Screw cover
Non polarity
Included in the Drain
Up Kit.
Separately sold remote control code (quadplex)
KRCW101A Series
¡Operating monitoring
equipment
(Field supply)
Turn the power on after all the switches have been set.
Settings made while the power is on are invalid.
NOTE
Overseas ON
¡
“Automatic” operation is available from the central controller.
Japan
Destination
SW3-3 setting What Happens
OFF
(Factory setting)
Open the Kit’s case and set the switches on the circuit board.
(1) For Overseas / Japanese unit setting (SW3-3)
Room air conditioners, different methods are used for setting the temperature in
automatic mode, so this switch needs to be set.
When using a central remote controller, the operating codes can be used to limit
operation from wireless remote controllers.
: permitted; : prohibited×
The Operating / error signals can be read from the contact output (S5).
Output specs
M1: Turn MR 1 ON when the air conditioner is running.
M2: Turn MR 2 when a communication error has occurred between the KRP928B2S and
the air conditioner, or MR 1 is ON and the unit has stopped after an error.
MR 2 is not turned ON during a warning.
(2) Group number settings (SW1 and SW2-1 to SW2-3)
Set these when using the central controller. (Set to the side.) Do not set more
than one unit to the same number.
However, these settings do not need to be made when using the schedule timer
independently.
(The settings are needed when used in conjunction with another DCS Series
central controller.)
In this case, the schedule timer performs an auto address after the power is turned
on, so new group numbers are automatically set. Settings made using the switches
will be overwritten.
(3) Settings when recovering from a power outage (SW2-4)
This selects whether to restart operation when the power comes back on after a
power outage occurred during operation. This setting is given priority in cases
where the indoor unit has an auto start ON / OFF jumper. Note also that
regardless of whether switch SW2-4 is on or off, the operating mode, set
temperature, fan direction and speed settings, and remote control prohibition
status are stored.
NOTE1: Since central equipment and HA JEM-A-compatible equipment both use
last command priority, the contact status and operating status of the air
conditioner might not match sometimes.
Example: If the unit is run from the central controller while the air
conditioner is stopped with an open contact, the contact will be
open and the unit will be running.
NOTE2: Operating mode and fan direction and speed settings can be changed.
(4) Contact input function settings (SW3-1 to SW3-2)
When using contact input (S1), choose one of the following functions.
NOTE also that a separate timer power source is needed when using the
schedule timer independently.
Power source specs: DC 16V, +10%, -15%, 200mA.
Recommended power source: Omron S82J-01015A. (Should be used with the
output voltage adjusted to the center, DC 16V.)
Upper
group NO.
1—
2—
3—
4—
5—
6—
7—
8—
1
123
0
123
123
123
123
123
123
123
SW1
setting
Lower
group NO.
0 0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
1
123
0
123
123
123
123
123
123
123
4
4
4
4
4
4
4
4
SW1
setting
Lower
group NO.
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
123
123
123
123
123
123
123
123
4
4
4
4
4
4
4
4
Stops if the unit was stopped before the power outage
and runs if it was running.
Stops after recovering from a power outage
OFF
(Factory setting)
ON
SW2-4 setting What Happens
ON / OFF control is rejected
(operate / stop / timer prohibition)
(NOTE 2).
During a forced stop, all
remote controller actions
are prohibited.
Last command priority
Contact - Open to close: air condition stops
(forced stop). Close to open: no change in
operating status.
Contact - Open to close: air condition runs.
Close to open: air conditioner is stopped
(NOTE 1).
Constant contact input
Forced stop or remote
controller permission input
The operating status of the air conditioner
is reversed by an instantaneous input of
100 msec or more.
Instantaneous contact
input (factory setting)
What Happens Control mode
S1
operating mode
SW3-2
setting
SW3-1
setting
OFF
OFF
ON
ON
Invalid
Run / stop Input
Contact specs
No-voltage minute electric current contact
(Minimum applicable load DC 12V, 1mA or lower)
Total wire length max: 100m
KRP928B2S
S1
CA
CB
Forced stop
Timer operation
is accepted by
remote controller
Last command priority
Only OFF control
is accepted
ON / OFF control
is rejected
Control mode
Constant
contact mode
Instantaneous
contact mode
S1
operating
mode
Operations from
central controller,
contact input and
HA JEM-A input
10,11
6,7
8
9
2
12–19
0,1,3
4
5
4
8
2,10-19
0,1,3,5-7
Control
code
“Stop” control from the
central controller
“Run” control from the
central controller
Operations from the remote controller
× ×
×
××
×
××
Central priority
×
×
*
**
×
×
×
×
×
×
×
×
×
××
×
×
*
**
×
×
××
×
×
*
×
×
×
×
×
×
Run / timer
Run / timer
Fan direction
and fan speed
Fan direction
and fan speed
Stop
Stop
Operating mode
temperature
Operating mode
temperaturet
×
Wireless Remote Controller
××
Wired Remote Controller
×
HA JEM-A-compatible equipment
×××
Instantaneous contact input
×××
Constant contact input
×××
Forced stop contact input
××
D-BIPS
××
Schedule timer
ON / OFF controller
ON / OFF controller
Central Remote Controller
S8 Power supply for relay (DC 12V)
Power source
for display
Relay specs (MR1 and MR2)
Coil voltage: DC 12V
Coil resistance: 160 10% ±
(Matsushita Electric HC
Relay, Omron MY Relay)
Wiring length
Max: 100m
KRP928B2S
S5
MC
M1
M2
(+)
(–)
(–)
MR1
MR2
Operating Display
Abnormality display
Operating control panel (Field supply)
MR1
MR2
Parts
Kit assy
PCB is in the housing.
Q’ty Q’ty
1
Parts
Connection harness (about 1.6m)
Mounting screws
Binding band
Installation manual
1set
3pcs.
1pc.
1set
The remote controller permission / prohibition settings using the Ve-up controller are as
follows.
: permitted; : prohibited×
Forced stop
Constant
contact mode
Constant
contact mode
Instantaneous
contact mode
Instantaneous
contact mode
Last command
priority
Does not affect settings
permitted/prohibited
permitted/prohibited
×
×
×
× ×
prohibited
permitted
prohibited
permitted
××××
Operations from
central controller,
contact input and
HA JEM-A input
permitted/prohibited
permitted/prohibited
permitted
prohibited
×
×
prohibited
permitted
Only OFF
control is
accepted
permitted/prohibited
permitted/prohibited
permitted
prohibited
×
×
×
×××
×
×
×
prohibited
permitted
ON / OFF
control is
rejected
Start / stop
Change operating
mode
Change set
temperature
Run / timer
Operating mode
temperature
Fan direction
and fan speed
Stop
Operations from the remote controllerVe-up controller settings
Instantaneous
contact mode
Constant
contact mode
S1 pin
operating mode
permitted/prohibited
permitted/prohibited
×
×
×
×
×
prohibited
permitted
Room air conditioner indoor unit
To HA connector (S21)
Cable available field supply
(See the installation manual of
the central remote controller)
Lower group number
switch (SW1)
Upper group number
switch (SW2-1to 3)
Operation when recovering
from a power outage mode
switch (SW2-4)
Service monitor (LED1: green)
When the CPU is working
properly, the LED flashes.
Power supply terminal (S8)
Connect an external DC 12V power
supply only when reading the
Operating / error display.
Japanese unit / Overseas unit
Setting switch (SW3-3)
Momentary contact / constant contact
Selection switch (SW3-2)
Forced stop
Settings switch (SW3-1)
Central controller equipment
¡DCS302 Series
¡DCS301 Series
¡DCS601 Series
¡DST301 Series
¡
“Automatic” operation is not available from the central controller.
When using “automatic” operation using the wireless remote
controller, the central controller displays automatic cooling
(heating) and 25 C. Even if the temperature is changed, it will °
return to 25 C after a while.°
SW2
setting
Central Remote Controller
Schedule timer
D-BIPS
Forced stop contact input
Constant contact input
Instantaneous contact input
HA JEM-A-compatible equipment
Wired Remote Controller
Wireless Remote Controller
The central controller can be combined with the following devices.
9
*
×
×
×
*Onlyduringtimeroperation
3P157704-1B,2B 2006.11.09 02:11 PM ページ2


Produkt Specifikationer

Mærke: Daikin
Kategori: Ikke kategoriseret
Model: KRP928A2S

Har du brug for hjælp?

Hvis du har brug for hjælp til Daikin KRP928A2S stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Daikin Manualer

Daikin

Daikin KRP928A2S Manual

24 December 2025
Daikin

Daikin FWQ04AAT Manual

23 December 2025
Daikin

Daikin EBSX11P50DG Manual

20 August 2025
Daikin

Daikin RRDQ220V1 Manual

18 August 2025
Daikin

Daikin RXL20K3V1B Manual

17 August 2025
Daikin

Daikin KRP1C65 Manual

13 August 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Sabrent

Sabrent EC-UK30 Manual

24 December 2025
LevelOne

LevelOne FVT-1103 Manual

24 December 2025
Yamazen

Yamazen YWD-182PK Manual

24 December 2025
Eurosound

Eurosound VS4K-SC Manual

24 December 2025
Yamazen

Yamazen SUT-302 Manual

24 December 2025
Auza

Auza Multiverts Manual

24 December 2025
Viking

Viking VICDP30 Manual

24 December 2025