Læs gratis den danske manual til Danfoss SonoMeter 40 (12 sider) i kategorien Måling. Denne vejledning er vurderet som hjælpsom af 48 personer og har en gennemsnitlig bedømmelse på 4.8 stjerner ud af 24.5 anmeldelser. Har du et spørgsmål om Danfoss SonoMeter 40, eller vil du spørge andre brugere om produktet?

Side 1/12
© Danfoss | 2021.10 AQ39012919462001en-010101 | 1
SonoMeter 40
Wired M-Bus protocol description
Operating guide
Table of Contents 1. General structure of protocol 2 ................................................................................................
1.1. General features of protocol 2 ........................................................................................................................
1.2. Data strings 2 ........................................................................................................................................................
2. Selection of the data type 3 ......................................................................................................
2.1. Selection of the data type All data” 3 .........................................................................................................
2.2. Selection of the data type “User data 3 .....................................................................................................
2.3. Selection of the data type “Simple billing” (Years logger) 3 ...............................................................
2.4. Selection of the data type “Enhanced billing” (Days logger) 3 ..........................................................
2.5. Selection of the data type “Multi tariff billing” (Months logger) 3 ...................................................
2.6. Selection of the data type “Instantaneous values” 3 .............................................................................
2.7. Selection of the data type “Load management values for management” (Hours logger) 3 ..
2.8. Selection of the data type “Installation and startup 3 .........................................................................
2.9. Selection of the data type Testing” 4 .........................................................................................................
2.10. Parameter list for preselecting 4 ....................................................................................................................
3. Data request ............................................................................................................................ 4
3.1. Data request 4 ..............................................................................................................................................................
3.2. Meter data coding 5 ..................................................................................................................................................
3.3. CRC16 checksum calculation algorithm ......................................................................................................... 10
4. Settings the parameters of meter ........................................................................................ 11
4.1. Changing the identification number ............................................................................................................... 11
4.2. Changing the identification number, Manufacturer ID and Medium ................................................. 11
4.3. Changing the primary address .......................................................................................................................... 11
4.4. Changing the data and time of the meter ..................................................................................................... 11
4.5. Changing the yearly set day ............................................................................................................................... 11
4.6. Changing the monthly set day .......................................................................................................................... 11
4.7. Changing the baud rate ........................................................................................................................................ 11
5. Secondary addressing ............................................................................................................ 12
5.1. Selecting of the meter ................................................................................................................................... 12
5.2. Communication with selected meter ...................................................................................................... 12
5.3. Deselection of secondary addressing mode ......................................................................................... 12
2 | AQ39012919462001en-010101 © Danfoss | 2021.10
Operating guide SonoMeter 40 - Wired M-Bus protocol description
1. General structure of
protocol
1.1. General features of
protocol
Meter uses a M-bus protocol .
Default baud rate: 2400 bps, Even, 1 Stop.
Baud rate can be changed.
Protocol is the same for Mbus interface and for optical interface.
Primary address of Mbus is individual for Mbus interface and for optical interface.
1.2. Data strings Data string to meter SND_NKE:
1 2 3 4 5
10h 40h A CS 16h
A - M-bus primary address of meter
CS – control sum (the youngest byte of amount of 2-nd and 3-rd bytes)
Data string to meter SND_UD2
1 2 3 4 5 6 7 8...n-2 n-1 n
68h 68hL L 53h
73h A 51h Data
bytes CS 16h
L - length of string (the number of bytes from 5-th to n-2 byte)
A - M-bus primary address of meter
CS – control sum (the youngest byte of amount of 5-th to n-2 bytes)
Data string to meter REQ_UD2:
1 2 3 4 5
10h 5Bh
7Bh A CS 16h
A - M-bus primary address of meter
CS - control sum (the youngest byte of amount of 2-nd and 3-rd bytes)
Answer of the meter CON:
E5h
Answer of the meter RSP_UD2:
1 2 3 4 5 6 7 8...11 12, 13 14 15 16 17 18,19
68h 68hL L C A CI ID Man Vrs Md TC St Sign
20 ... ... ... ... ... ... n-2 n-1 n
DIF VIF Data DIF VIF Data CS 16h
L - length of string (the number of bytes from 5-th to n-2 byte)
C – „C field“ (08)
A - M-bus primary address of meter
CI - „CI field“
IDidentification number of meter (BSD8, used for secondary addressing, can be changed - see
paragraph 4.1),
Man – Manufacturer code (Danfoss A/S manufacturer code is „DFS“, 10 D3)
Vrs – number of protocol version (0Bh)
Md – code of medium (for „heat / cold energy“: 0Dh)
TC – counter of telegrams
St - meter status code
Sign - 00 00
The bytes 20...n-2 is data from meter:
DIF – code of data format
VIF – code of data units
Data– values of data
CS – control sum (the youngest byte of amount of 5-th to n-2 bytes).