Elsner Cala KNX T 201 Sunblind Manual

Elsner Ikke kategoriseret Cala KNX T 201 Sunblind

Læs nedenfor 📖 manual på dansk for Elsner Cala KNX T 201 Sunblind (42 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 39 personer og blev bedømt med 4.4 stjerner i gennemsnit af 20 brugere

Side 1/42
EN
Installation and Adjustment
Cala KNX T 201 Sunblind,
Cala KNX T 202 Sunblind
Temperature Controller,
Button for Shading
Cala KNX T 201 Sunblind
Item numbers
70990 (white),
70992 (black)
Cala KNX T 202 Sunblind
Item numbers
71050 (white),
71052 (black)
1 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 OstelsheimGermany
Cala KNX T 201/202 Sunblind push buttonfrom application 1.0
Status: 04.10.2021 • Technical changes and errors excepted.
1. Description ........................................................................................... 3
1.0.1. Area function ................................................................................................. 4
1.1. Scope of delivery ...................................................................................................... 4
1.2. Technical specifications ........................................................................................... 5
1.2.1. Accuracy of the measurement ..................................................................... 5
2. Installation and commissioning ........................................................... 5
2.1. Installation position .................................................................................................. 6
2.2. Composition of the device ....................................................................................... 7
2.3. Installation of the sensor ......................................................................................... 8
3. Commissioning .................................................................................... 8
4. Addressing of the device at the bus .................................................... 8
5. Display and operation at the device .................................................... 8
5.1. Adjust room temperature (using the example Cala KNX T 201 Sunblind) .......... 8
6. Maintenance ....................................................................................... 10
7. Disposal ............................................................................................. 10
8. Transmission protocol ....................................................................... 11
8.1. List of all communication objects ......................................................................... 11
9. Setting the parameters ...................................................................... 15
9.1. Behaviour on power failure/ restoration of power .............................................. 15
9.2. General settings ..................................................................................................... 15
9.3. Temperature measured value ............................................................................... 15
9.4. Temperature threshold values .............................................................................. 16
9.4.1. Threshold value 1, 2 ................................................................................... 16
9.5. Temperature PI controller ...................................................................................... 18
9.5.1. Heating control stage 1/2 ........................................................................... 24
9.5.2. Cooling control stage 1/2 ........................................................................... 26
9.6. LEDs ......................................................................................................................... 28
9.7. Buttons .................................................................................................................... 29
9.7.1. Drive ............................................................................................................. 30
9.7.2. Control modes for drive control ................................................................ 34
9.8. Logic ........................................................................................................................ 35
9.8.1. AND logic outputs 1/2 and OR logic outputs 1/2 ...................................... 36
2 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.
3 Description
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
1. Description
The Cala KNX T 201/202 Sunblind push button has touch-sensitive buttons with
which functions can be called up in the KNX building bus system. The glass surface is
printed with areas for setting the temperature and solar protection. White LEDs are in-
tegrated in these areas and their behaviour can be adjusted.
A temperature sensor is integrated into Cala KNX T 201/202 Sunblind. An external
temperature reading can be received via the bus and processed with its own data to
create a total temperature (mixed value).
The Cala KNX T 201/202 Sunblind has a PI controller for heating and cooling. The
setpoint temperature can be changed using the "+" and "-" touch buttons.
Communication objects can be linked via AND and OR logic gates.
The device is supplemented with a frame of the switch series used in the building, and
thus fits seamlessly into the interior fittings.
Functions:
Operating zone for temperature control with 2 areas (warmer, cooler)
LEDs can be set. All LEDs Off, all LEDs as ambient lighting, all LEDs
individually controllable
Area function when touching two or more push buttons. Can be configured
as switch, selector switch, as 8 or 16 bit encoder or for scenario recall
Temperature measurements. Mixed value from own measured value and
external values (proportion can be set by percentage), output of minimum and
maximum values
PI-controller for heating (one or two-level) and cooling (one or two-level)
according to temperature. Regulation according to separate setpoints or basic
setpoint temperature
2 AND and 2 OR logic gates each with 4 inputs. 8 logic inputs (in the form
of communications objects) can be used as inputs for the logic gates. The
output from each gate can be configured optionally as 1-bit or 2 x 8-bit
Additional functions Cala KNX T 201 Sunblind:
1 operating zone for blinds, awnings, shutters or windows with 2 areas (up/
down with short/long distinction)
Additional functions Cala KNX T 202 Sunblind:
2 operating zones for blinds, awnings, shutters or windows with 2 areas
(up/down with short/long distinction)
Configuration is made using the KNX software as of ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu. There you will also find the
product manual.
4 Description
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
1.0.1. Area function
If the area function in ETS has been activated, another function is available alongside
the regular key functions. This is triggered by touching multiple keys, e.g. if you touch
the sensor with the palm of your hand.
Using the area function
If a key is pressed and another (different) key is touched within 0.2 seconds, the action
set in the ETS is performed for the area operation (See Fig. 1 a) and b)). The keys are
then blocked for 0.5 seconds.
Using the normal key function
If a key is pressed and no other key is touched within 0.2 seconds, the normal key
function is enabled/provided for 5 seconds (See Fig. 1 c) and d)). This is extended for 5
seconds with each push of the button.
If the area function in the ETS is disabled, the keys can be used normally at any time.
1.1. Scope of delivery
Push button in casing
Key function readiness
Key function readiness
Fig. 1
0s 0.2s 5.2s
Key Y
Key X
Key X
Design
Function Y
Key function readiness
Area function
Examples of normal key functions
0.5 s blockKey X
Design
Area function
Key Y
Design
Function X
a)
b)
c)
d)
Key X
Key Y 0.5 s block
Design
Area function
Area function examples
readiness
5 Installation and commissioning
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
Base plate
Additionally required (not included in the deliverables):
Device socket according to DIN 49073
Frame (for insert 55 x 55 mm), compatible to the switch scheme used in the
building
1.2. Technical specifications
The product conforms with the provisions of EU guidelines.
1.2.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter
Installation position) can be corrected in the ETS in order to ensure the specified
accuracy of the sensor (offset).
When measuring temperature, the self-heating of the device is compensated.
2. Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
Casing Genuine glass, plastic
Colours • similar to RAL 9010 pure white
• similar to RAL 9005 deep black
Installation on device socket according to DIN 49073
Degree of protection IP 20
Dimensions Housing approx. 55 x 55 (W x H, mm),
Installation depth approx. 10 mm,
Base plate approx. 71 x 71 (W x H, mm),
Total weight approx. 50 g
Ambient temperature Operating 0…+55°C, storage -30…+85°C
Ambient humidity 5…95% RH, avoid condensation
Operating voltage KNX bus voltage
Bus current max. 20 mA
Data output KNX +/- Bus plug-in terminal
Group addresses max. 167
Allocations max. 167
Communication objects Cala KNX T 201 Sunblind: 92
Cala KNX T 202 Sunblind: 98
Temperature measurement
range
0…+55°C
Temperature resolution 0.1°C
6 Installation and commissioning
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating
instructions. Improper use, modifications to the device or failure to observe the
operating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and
after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.1. Installation position
The Cala KNX T 201/202 Sunblind push button is installed on a device socket.
May be installed and operated in dry interior rooms only.
When selecting an installation location, ensure that the measurement results are
affected as little as possible by external influences. Possible sources of interference
include:
Direct sunlight
Drafts from windows and doors
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
Fig. 2: Sectional drawing.
The Cala KNX T 201/202 Sunblind push
button fits in a standard connector socket (Ø
60 mm, depth 42 mm).
The frame is not included in the delivery!
Installation depth
27 mm
Construction depth
10 mm
7 Installation and commissioning
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected in
the ETS in order to ensure the specified accuracy of the sensor (offset).
2.2. Composition of the device
2
3
1
1
1
1
2
3
3
Cala KNX T 201 Sunblind Cala KNX T 202 Sunblind
Fig. 3: Front
1 Ventilation slit (top and bottom)
2 „Temperature“ area with 2 touch surfaces and temperature display
3 „Sun protection/drive“ area with 2 touch surfaces per channel
Fig. 4: Back
1 Base frame
2 KNX terminal BUS +/-
3 Programming button (recessed) for
teaching the device
4 Programming LED (recessed)
5 Catches
5
1
3
2
4
8 Commissioning
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
2.3. Installation of the sensor
First install the windproof socket with feed line. Seal the inlet tubes as well, in order to
prevent draughts.
Then screw the base plate to the socket and place the switch program frame. Connect
the bus cable +/- to the plug (black-red).
Insert the device firmly onto the metal frame using the catches so that the device and
the housing are fixed together.
3. Commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electronics.
You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase last-
ing a few seconds. During this phase no information can be received or sent via the
bus.
4. Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another ad-
dress into the ETS by overwriting the 15.15.255 address or by teaching via the pro-
gramming button.
5. Display and operation at the device
5.1. Adjust room temperature (using the example
Cala KNX T 201 Sunblind)
Depending on the setting of the "Display mode" parameter in the device application,
the Cala KNX T 201/202 Sunblind push button displays the current room
temperature value (or mixed value), the target value or the shift in relation to the basic
setpoint. The display can be dimmed and switched off via the bus so that no value is
displayed.
Option A: Display of actual temperature (room temperature)
The current room temperature is displayed. It is not possible to change the room
temperature manually using the +/- buttons.
Option B: Display of target temperature or basic setpoint shift
Depending on the setting, the current target value or the shift relative to the base
setpoint is displayed. The temperature can be changed by touching the +/- buttons.
9 Display and operation at the device
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
Target value display (absolute value):
Display of the basic setpoint shift (change compared to the basic setpoint of the
control):
Option C: Display of actual temperature and target temperature/basic
setpoint shift
During normal operation, the current room temperature is displayed. By touching the
buttons, the display jumps to the target temperature or to the basic setpoint shift,
depending on the presetting. Changes with + or - are visible. The display returns to the
room temperature if no button is touched for 7 seconds.
Tap +:
Increase room temperature
(target temperature is
increased)
Tap -:
Lower room temperature
(target temperature is lowered)
Tap +:
Increase room temperature
(Basic setpoint shift direction
PLUS)
Tap -:
Lower room temperature
(Basic setpoint shift direction
MINUS)
10 Maintenance
Cala KNX T 201/202 Sunblind push buttonVersion: 04.10.2021 • Technical changes and errors excepted.
Touch the + or - button briefly: The current target temperature (or the basic setpoint
shift) is displayed.
Tap +: Increase room temperature
(target temperature/basic setpoint shift is increased).
Tap -: Lower room temperature
(target temperature/basic setpoint shift is lowered).
General:
The step size for the change and the possible setting range are defined in the device
application (ETS). There you can also define whether the manually changed values are
retained after a mode change (e.g. Eco mode overnight) or reset to the stored values.
The button functions can be locked due to operating mode with priority 1.
6. Maintenance
Ventilation slits must not be dirty of covered. As a rule, it is sufficient to wipe the device
with a soft, dry cloth as required.
7. Disposal
After use, the device must be disposed of in accordance with the legal regulations. Do
not dispose of it with the household waste!
or
11 Transmission protocol
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
8. Transmission protocol
Units:
Temperatures in degrees Celsius
8.1. List of all communication objects
Abbreviations Flags:
C Communication
R Read
W Write
T Transmit
U Update
No Text Function Flags SizeDPT type
0 Software version Output R-CT [217.1] DPT_Version 2 Bytes
20 Temperature sensor: malfunc-
tion
Output R-CT [1.1] DPT_Switch 1 Bit
21 Temperature sensor: meas-
ured value external
Input -WCT [9.1] DPT_Value_Temp 2 Bytes
22 Temperature sensor: meas-
ured value
Output R-CT [9.1] DPT_Value_Temp 2 Bytes
23 Temperature sensor: meas-
ured value total
Output R-CT [9.1] DPT_Value_Temp 2 Bytes
24 Temperature sensor: meas-
ured value min./max. query
Input -WC- [1.17] DPT_Trigger 1 Bit
25 Temperature sensor: meas-
ured value minimum
Output R-CT [9.1] DPT_Value_Temp 2 Bytes
26 Temperature sensor: meas-
ured value maximum
Output R-CT [9.1] DPT_Value_Temp 2 Bytes
27 Temperature sensor: meas-
ured value min./max. reset
Input -WC- [1.17] DPT_Trigger 1 Bit
30 Temp. thresholdV 1: Absolute
value
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
31 Temp. thresholdV 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 Bit
32 Temp. thresholdV 1: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 Bytes
33 Temp. thresholdV 1: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 Bytes
34 Temp. thresholdV 1: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
35 Temp. thresholdV 1: Switching
output block
Input -WC- [1.1] DPT_Switch 1 Bit
36 Temp. thresholdV 2: Absolute
value
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
12 Transmission protocol
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
37 Temp. thresholdV 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 Bit
38 Temp. thresholdV 2: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 Bytes
39 Temp. thresholdV 2: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 Bytes
40 Temp. thresholdV 2: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
41 Temp. thresholdV 2: Switching
output block
Input -WC- [1.1] DPT_Switch 1 Bit
50 Temp.control: HVAC mode (pri-
ority 1)
Input /
Output
RWCT depending on setting 1 Byte
51 Temp.control: HVAC mode (pri-
ority 2)
Input /
Output
RWCT depending on setting 1 Byte
52 Temp.control: Mode frost/heat
protection activt.
Input RWCT [1.1] DPT_Switch 1 Bit
53 Temp.control: Block (1 = Block-
ing)
Input -WC- [1.1] DPT_Switch 1 Bit
54 Temp.control: Current setpoint Output R-CT [9.1] DPT_Value_Temp 2 Bytes
55 Temp.control: Switch. (0: Heat-
ing | 1: Cooling)
Input -WC- [1.1] DPT_Switch 1 Bit
56 Temp.control: Setpoint Com-
fort heating
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
57 Temp.control: Setpoint Com-
fort heat.(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 Bit
58 Temp.control: Setpoint Com-
fort cooling
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
59 Temp.control: Setpoint Com-
fort cool.(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 Bit
60 Temp.control: Basic 16-bit set-
point shift
Input -WC- [9.1] DPT_Value_Temp 2 Bytes
61 Temp.control: Setpoint
Standby heating
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
62 Temp.control: Setpoint
Standby heat.(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 Bit
63 Temp.control: Setpoint
Standby cooling
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
64 Temp.control: Setpoint
Standby cool. (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 Bit
65 Temp.control: Setpoint Eco
heating
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
66 Temp.control: Setpoint Eco
heating (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 Bit
67 Temp.control: Setpoint Eco
cooling
Input /
Output
RWCT [9.1] DPT_Value_Temp 2 Bytes
No Text Function Flags SizeDPT type
14 Transmission protocol
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
Only for Cala KNX T 202 Sunblind
94 LED 3 on/off Input -WC- [1.1] DPT_Switch 1 Bit
95 LED 3 Block Input -WC- [1.1] DPT_Switch 1 Bit
96 LED 4 on/off Input -WC- [1.1] DPT_Switch 1 Bit
97 LED 4 Block Input -WC- [1.1] DPT_Switch 1 Bit
For all models
99 Area operation on/off Input -WC- [1.1] DPT_Switch 1 Bit
100 Area operation Output: Switch Output R-CT depending on setting 2 Bytes
101 Drive 1 Long-term Output R-CT [1.8] DPT_UpDown 1 Bit
102 Drive 1 Short-term Output R-CT [1.10] DPT_Start 1 Bit
Only for Cala KNX T 202 Sunblind
103 Drive 2 Long-term Output R-CT [1.8] DPT_UpDown 1 Bit
104 Drive 2 Short-term Output R-CT [1.10] DPT_Start 1 Bit
For all models
107 Logic input 1 Input -WC- [1.2] DPT_Bool 1 Bit
108 Logic input 2 Input -WC- [1.2] DPT_Bool 1 Bit
109 Logic input 3 Input -WC- [1.2] DPT_Bool 1 Bit
110 Logic input 4 Input -WC- [1.2] DPT_Bool 1 Bit
111 Logic input 5 Input -WC- [1.2] DPT_Bool 1 Bit
112 Logic input 6 Input -WC- [1.2] DPT_Bool 1 Bit
113 Logic input 7 Input -WC- [1.2] DPT_Bool 1 Bit
114 Logic input 8 Input -WC- [1.2] DPT_Bool 1 Bit
117 AND logic 1: 1 bit switching
output
Output R-CT [1.2] DPT_Bool 1 Bit
118 AND logic 1: 8 bit output A Output R-CT depending on setting 1 Byte
119 AND logic 1: 8 bit output B Output R-CT depending on setting 1 Byte
120 AND logic 1: Block Input -WC- [1.1] DPT_Switch 1 Bit
121 AND logic 2: 1 bit switching
output
Output R-CT [1.2] DPT_Bool 1 Bit
122 AND logic 2: 8 bit output A Output R-CT depending on setting 1 Byte
123 AND logic 2: 8 bit output B Output R-CT depending on setting 1 Byte
124 AND logic 2: Block Input -WC- [1.1] DPT_Switch 1 Bit
125 OR logic 1: 1 bit switching out-
put
Output R-CT [1.2] DPT_Bool 1 Bit
126 OR logic 1: 8 bit output A Output R-CT depending on setting 1 Byte
127 OR logic 1: 8 bit output B Output R-CT depending on setting 1 Byte
128 OR logic 1: Block Input -WC- [1.1] DPT_Switch 1 Bit
129 OR logic 2: 1 bit switching out-
put
Output R-CT [1.2] DPT_Bool 1 Bit
No Text Function Flags SizeDPT type
15 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
9. Setting the parameters
9.1. Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
9.2. General settings
Set the basic properties of the data transmission.
9.3. Temperature measured value
Select, whether a malfunction object is to be sent if the sensor is faulty.
Use Offsets to adjust the readings to be sent.
The unit can calculate a mixed value from its own reading and an external value. Set
the mixed value calculation if desired. If an external portion is used, all of the following
settings (threshold values, etc.) are related to the overall reading.
130 OR logic 2: 8 bit output A Output R-CT depending on setting 1 Byte
131 OR logic 2: 8 bit output B Output R-CT depending on setting 1 Byte
132 OR logic 2: Block Input -WC- [1.1] DPT_Switch 1 Bit
Transmission delay after reset/bus restora-
tion
5 s • ... • 300 s
Maximum message rate • 1 message per second
• ...
• 10 messages per second
• ...
• 50 messages per second
Use malfunction object No • Yes
Offset in 0.1°C -50…50; 0
Use external measured value No • Yes
Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100%
No Text Function Flags SizeDPT type
17 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
Threshold value setpoint using a communication object:
Beforehand, enter how the threshold value will be received from the bus. Basically, a
new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined which will be valid un-
til the first call with a new threshold value. For units which have already been taken into
service, the last communicated threshold value can be used. Basically, a temperature
range is given in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in so that it is retained in the event of a power supply failure and
will be available again once the power supply is restored.
Set the hysteresis independently of the type of threshold value setting.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setpoint using Parameter • Communication objects
Start threshold value in 0.1°C
valid until first Communication
-300 … 800; 200
Object value limit (min) in 0.1°C -300…800
Object value limit (max) in 0.1°C -300…800
Type of threshold value change Absolute value • Increase/decrease
Interval
(upon increase/decrease change)
0.1 °C • ... • 5°C
Hysteresis setting in % • absolute
Hysteresis in % of the threshold value 0 … 50; 20
Hysteresis in 0.1°C 0 … 1100; 50
When the following conditions apply, the
output is
(TV = Threshold value)
TV above = 1 | TV - Hyst. below = 0
LV above = 0 |LV - hysteresis below = 1
TV below = 1 |TV + hysteresis above = 0
TV below = 0 |TV + hysteresis above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
18 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
Block
The switching output can be blocked using an object.
Set the cases in which threshold vlaues and delay times received per object are to be
retained.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
9.5. Temperature PI controller
Activate the controller if you want to use it.
Switching output sends on change
on change to 1
on change to 0
on change and periodically
on change to 1 and periodically
on change to 0 and periodically
Cycle
(is sent only if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block No • Yes
Assessment of the block object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first Commu-
nication
0 • 1
Switching output behaviour
On blocking • Do not send message
• 0 Send
• 1 Send
On release
(with 2 second release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change • Do not send message
• Send switching output status
Switching output sends on change to 1 • Do not send message
• if switching output = 1 send 1
Switching output sends on change to 0 • Do not send message
• if switching output = 0 send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
if switching output = 1 send 1
Switching output sends on change to 0 and
periodically
if switching output = 0 send 0
Use controller No • Yes
19 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
General rules
Decide in which cases nominal values and delay times received per object are to be
kept. The parameter is only taken into consideration if the setting by object is activated
further down. Please note that the setting "After power restoration and programming"
should not be used for the initial start-up, as the factory settings are always used until
the first call (setting via objects is ignored).
For an adequate regulation of the indoor temperature, comfort, standby, eco and build-
ing protection modes may be used.
Comfort when present,
Standby when absent,
Eco as a night-time mode and
Frost / heat protection (building protection) e.g. when the window is open.
The settings for the temperature control include the setpoint temperatures for the in-
dividual modes. Objects are used to determine which mode is to be selected. A change
of mode may be triggered manually or automatically (e.g. by a timer, window contact).
The mode may be switched with two 8 bit objects of different priority. Objects
„... HVAC mode (Prio 2)“ for switching in everyday operation and
„... HVAC mode (Prio 1)“ for central switching with higher priority.
The objects are coded as follows:
0 = Auto
1 = Comfort
2 = Standby
3 = Eco
4 = Building protection
Alternatively, you can use three objects, with one object switching between eco and
standby mode and the two others are used to activate comfort mode or frost/heat pro-
tection mode. The comfort object then blocks the eco/standby object, and frost/heat
protection objects have the highest priority. Objects
„... Mode (1: Eco, 0: Standby)“,
„... comfort activation mode" and
„... frost/heat protection activation mode"
Select the mode to be activated after reset (e.g. power failure, reset of the line via
the bus). (Default).
Then configure a temperature control block using the blocking object.
Switch mode via • two 8-bit objects (HVAC modes)
• three 1-bit objects
Mode after reset • Comfort
• Standby
• Eco
• Building protection
Behaviour of the blocking object with value • 1 = Block | 0 = release
• 0 = block | 1 = release
Value of the blocking object after reset 0 • 1
20 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
Specify when the current control variables are to be sent to the bus. Periodic trans-
mission is safer if a message does not reach a recipient. You may also set up periodical
monitoring by the actuator with this setting.
The status object reports the current status of the output (0 = OFF, 0 = ON) and may
for example be used for visualisation, or to switch off the heating pump as soon as the
heating is switched off.
Then define the type of setting. Heating and/or cooling may be controlled in two
stages.
General setpoint values
You may enter separate setpoint values for each mode or use the comfort setpoint as
a basic value.
If you are using the controls for both heating and cooling, you may also select the set-
ting "separately with switching object". Systems used for cooling in the summer and
for heating in the winter can thus be switched from one to the other.
If you are using the basic value, only the deviation from the comfort setpoint value is
listed for the other modes (e. g., 2°C less for standby mode).
Send control variable • on change
• on change and periodically
from change of (in % absolute) 1...10; 2
Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Send status objects • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Type of control • Single stage heating
• Dual-stage heating
• Single-stage cooling
• Single-stage heating + single-stage cool-
ing
• Dual-stage heating + single-stage cooling
• Dual-stage heating + dual-stage cooling
Keep modified setpoints after mode
change
No • Yes
Setting the nominal values • separate with switching object
• separate without switching object
• with comfort setpoint as a basis with
switching object
• with comfort setpoint as a basis without
switching object
21 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
The grades for the setpoint changes is predefined. Whether the change remains active
only temporarily (do not store) or remains stored even after restoration of power (and
programming) is determined in the first section of "General controller". This also ap-
plies to a comfort extension.
The controller can be switched from eco mode, i.e. night mode, to comfort mode via
the comfort extension. This means that the comfort setpoint can be maintained for
longer, for example when having guests. The duration of this comfort extension period
is set. After the comfort extension period is terminated, the system returns to eco
mode.
Setpoint Comfort
Comfort mode is usually used for daytime mode when people are present. A starting
value is defined for the comfort setpoint as well as a temperature range in which the
nominal value may be modified.
If setpoint values are entered separately:
If the comfort setpoint value is used as a basis:
If the comfort setpoint is used as the basis, the increase/decrease of this value is indi-
cated.
Analysis of the status object /
Behaviour of the switching object at value
• 0 = Heating | 1 = Cooling
• 1 = Heating | 0 = Cooling
Switching object value
before first Communication
( )only if switching object is used
0 • 1
Grading for setpoint changes
(in 0.1 °C)
1… 50; 10
Storage of setpoint(s) • not be retained
• after power restoration
• after restoration of power and program-
ming
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600
Initial heating/cooling setpoint (in 0.1 °C)
valid until first Communication
(not upon saving the target value after pro-
gramming)
-300…800; 210
Min. object value heating/cooling (in 0.1 °C) -300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Minimum base setpoint (in 0.1°C) -300…800; 160
Maximum base setpoint (in 0.1°C) -300…800; 280
23 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
If the comfort setpoint value is used as a basis:
If the comfort setpoint is used as the basis, the increase/decrease of this value is indi-
cated.
Setpoint values for frost/heat protection (building protection)
The building protection mode is used, for example, as long as windows are open for
ventilation. Setpoints for frost protection (heating) and heat protection (cooling) are
determined which may not be modified from outside (no access via operating devices
etc.). The building protection mode may be activated with delay, which allows you to
leave the building before the controls switch to frost/heat protection mode.
General variables
This setting appears for the control types "Heating and Cooling" only. This is where you
can decide whether to use a common variable for heating and cooling. If the 2nd stage
has a common variable, this is also where you determine the control mode of the 2nd
stage.
When using the variable for a 4/6 way valve:
0%...100% Heating = 66%...100% variable
OFF = 50% variable
0%...100% Cooling = 33%...0% variable
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 50
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 60
Nominal value frost protection\r\n(in 0,1°C) -300…800; 70
Activation delay no • 5 s • ... • 5 min • … • 2 h
Nominal value heat protection (in 0,1°C) -300…800; 350
Activation delay no • 5 s • ... • 5 min • … • 2 h
For heating and cooling • separate variables are used
• common variables are used for
Stage 1
• common variables are used for
Stage 2
• common variables are used for
Stage 1+2
Use variable for 4/6-way valve
(only with common variable at stage1)
No • Yes
Control type
(for stage 2 only)
• 2-point-control
• PI control
Regulating variable of the 2nd Stage is on
(only for stage 2 with 2-point control)
• 1-bit object
• 8-bit object
24 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
9.5.1. Heating control stage 1/2
If a heating control mode is configured, one or two setting sections for the heating
stages are displayed.
In the first stage, heating is controlled by a PI controller which allows to either enter
control parameters or select predetermined applications.
In the second stage (therefore only in case of 2-stage heating), heating is controlled via
a PI or a 2-point-control.
In stage 2, the setpoint deviation between the two stages must also be specified, i.e.
beyond which setpoint undershoot the second stage is then added.
PI controller with control parameters:
This setting allows individual input of the parameters for PI control.
Specify the deviation from the setpoint value at which the maximum control variable
value is reached, i.e. the point at which maximum heating power is activated.
The reset time shows how quickly the controller responds to deviations from the set-
point. In case of a short reset time, the control responds with a fast increase of the con-
trol variable. In case of a long reset time, the control responds somewhat less urgently
and needs longer until the necessary control variable for the setpoint deviation is
reached.
You should set the time appropriate to the heating system at this point (observe man-
ufacturer's instructions).
Now specify what should be sent when the control is blocked. Set a value greater 0
(=OFF) to receive a basic heating stage, e.g. for floor heating.
On release, the control variable follows the rule again.
Setpoint difference between stages 1 and 2
stages (in 0.1°C)
(At stage 2)
0...100; 40
Control type
(at stage 2, no common variables)
• 2-point-control
• PI control
Control variable is on
(for stage 2 with 2-point control, no com-
mon variables)
• 1-bit object
• 8-bit object
Control type PI control
Setting of the controller by Controller parameter
• specified applications
Maximum control variable is reached
at setpoint/actual difference of (in °C)
1...5
Reset time (in min.) 1...255; 30
When blocked, the control variable should • not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
25 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for frequent applications.
Now specify what should be sent when the control is blocked. Set a value greater 0
(=OFF) to receive a basic heating stage, e.g. for floor heating.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
2-point-control (only stage 2):
2-point-control is used for systems which are only set to ON or OFF.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range.
Control type PI control
Setting of the controller by • Controller parameter
specified applications
Application • Warm water heating
• Floor heating
• Convection unit
• Electric heating
Maximum control variable is reached
at setpoint/actual difference of (in °C)
Warm water heating: 5
Floor heating: 5
Convection unit: 4
Electric heating: 4
Reset time (in min.) Warm water heating: 150
Floor heating: 240
Convection unit: 90
Electric heating: 100
When blocked, the control variable should • not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
Control type
(is determined at a higher stage for com-
mon variables)
2-point-control
Hysteresis (in 0.1°C) 0...100; 20
27 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
reached. You should set the time appropriate to the cooling system at this point (ob-
serve manufacturer's instructions).
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for a cooling ceiling
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
2-point-control (only stage 2):
2-point-control is used for systems which are only set to ON or OFF.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range.
Maximum control variable is reached
at setpoint/actual difference of (in °C)
1...5
Reset time (in min.) 1...255; 30
When blocked, the control variable should • not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
Control type PI control
Setting of the controller by • Controller parameter
specified applications
Application • Cooling ceiling
Maximum control variable is reached
at setpoint/actual difference of (in °C)
Cooling ceiling: 5
Reset time (in min.) Cooling ceiling: 30
When blocked, the control variable should • not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
Control type
is determined at a higher stage for com-
mon variables
2-point-control
Hysteresis (in 0.1°C) 0...100; 20
28 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
If separate variables are used, select whether the variable of the 2nd stage is a 1-bit ob-
ject (on/off) or an 8-bit object (on with percentage value/off).
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
9.6. LEDs
Set the LED mode.
All LEDs as ambient lighting
If all LEDs are to be used as ambient lighting, illuminate all simultaneously. Set the
brightness of the LEDs, whether objects are used and whether the LEDs switch off au-
tomatically after pushing the button.
Control variable is on 1-bit object
• 8-bit object
Value (in %)
(for 8-bit object)
0...100
When blocked, the control variable should • not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
LED mode • All LEDs off
• All LEDs as ambient lighting
• All LEDs individually controllable
LED mode All LEDs as ambient lighting
Brightness 0 ... 100%; 30%
Use objects No • Yes
Object value on/off after reset
( )if objects are used
0 • 1
Use automatic switch-off after pressing a
button
No • Yes
Switch off after (is automatic switch off is
used)
1 ... 255; 30 secs. after pressing
LEDs for temperature display display actual value only
• display only target value/base shift
• display actual value and target value/base
shift
29 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
All LEDs individually controllable
This is where you set the brightness of the LEDs, whether objects are used, whether
the LEDs switch off automatically after pushing the button and what the LEDs for tem-
perature display should indicate.
9.7. Buttons
Cala KNX T 201/202 Sunblind has an area control, i.e. if you touch 2 or more but-
tons at the same time, you can activate another function. The value (0 or 1) can be set
for the evaluation of the activation of the surface operation.
Set whether you want to use the screen control.
LED mode All LEDs individually controllable
Brightness 0 ... 100%; 30%
Use objects No • Yes
Object value on/off after reset
( )if objects are used
0 • 1
Function LEDs for temperature display always OFF
• On after pressing button for settable time
• On for object value = 1 /
Off for object value = 0
Lighting period after pressing (if "On after
pressing button for a settable time")
1 ... 5 seconds ; 3 seconds
Object value after reset (if "On for object
value = 1 / Off for object value = 0)
0 • 1
Use block object (if "On for object value = 1
/ Off for object value = 0)
No • Yes
LEDs for temperature display display actual value only
• display only target value/base shift
• display actual value and target value/base
shift
Function LED 1 (top left) / 2 (top right) / 3
(bottom left) / 4 (bottom right)
[LED 3 and 4 only for Cala KNX T 202 Sun-
blind]
• always OFF
• On after pressing button for settable time
• On for object value = 1 /
Off for object value = 0
Lighting period after pressing (if "On after
pressing button for a settable time")
1 ... 5 seconds ; 3 seconds
Object value after reset (if "On for object
value = 1 / Off for object value = 0)
0 • 1
Use block object (if "On for object value = 1
/ Off for object value = 0)
No • Yes
Use screen control No • Yes
Use screen control Yes
Activation object assessment Value 1 = active | Value 0 = inactive
• Value 0 = active | Value 1 = inactive
31 Setting the parameters
Cala KNX T 201/202 Sunblind Push Button • Version: 04.10.2021 • Technical changes and errors excepted
Comfort mode:
Dead man switch:
Shutter
Standard:
Standard inverted:
Comfort mode:
Dead man switch:
Push-button is pressed and
released before expiry of Time 1
Maintained for longer than Time 1
Triggered between Times 1 and 1 + 2
Triggered after Times 1 + 2
Stop/Step
Up | Down
Stop
No more stop
Time 1 (in 0.1 sec) 0 ... 50; 4
Time 2 (in 0.1 sec) 0 ... 50; 20
Press button Up | Down command
Release button Stop command
Function Shutters
Swap Up/Down No • Yes
Control mode • Standard
• Standard inverted
• Comfort mode
• Dead man switch
Behaviour for button actuation (up): short = Stop | long = Up
Behaviour for button actuation (down): short = Stop | long = Down
Behaviour for button actuation (up/down): short = Stop | long = Up/Down
Time between tap and hold (0.1 sec) 0 ... 50; 10
Behaviour for button actuation (up): long = Stop | short = Up
Behaviour for button actuation (down): short = Stop | long = Down
Behaviour for button actuation (up/down): short = Stop/Step | long = Up/Down
Time between tap and hold (0.1 sec) 0 ... 50; 10
Repetition of the step command upon
extended button press (only for up)
none • every 0.1 s • ... • every 0.5 s • ... •
every 2 s
Push-button is pressed
released before expiry of Time 1
Maintained for longer than Time 1
Triggered between Times 1 and 1 + 2
Triggered after Times 1 + 2
Stop
Up | Down | Up/Down
Stop
No more stop
Time 1 (in 0.1 sec) 0 ... 50; 4
Time 2 (in 0.1 sec) 0 ... 50; 20


Produkt Specifikationer