Læs gratis den danske manual til Eltako DSZ15WD-3x5A (2 sider) i kategorien Måleudstyr. Denne vejledning er vurderet som hjælpsom af 45 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 23 anmeldelser. Har du et spørgsmål om Eltako DSZ15WD-3x5A, eller vil du spørge andre brugere om produktet?

Side 1/2
CT operated energy meter with settable CT ratio and MID.
Maximum current 3x5 A. Standby loss 0.5 watt per path only.
Modulair device for DIN-EN 60715 TH35 rail mounting in distribution
cabinets with IP51 protection class.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With SO interface as standard.
This three-phase energy meter measures active energy by means of the
current between input and output.
The internal power consumption of 0.5 watt active power per path is neither
metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is 10mA. The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh.
On the right next to the display are the keys MODE and SELECT. Press them
to scroll through the menu. First the background lighting switches on. The
display then shows the total active energy, the active energy of the resettable
memory as well as the instantaneous values of consumption, voltage and
current per phase.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a
bridge over the terminals which are marked with 'JUMPER'. To adjust the CT
ratio to the installed transformer, remove the bridge and reset the energy meter
according to the the display guide, right on this manual. Then block it again
with the bridge. Adjustable current transformer ratios: 5:5, 50:5, 100:5,
150:5, 200:5, 250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5,
1250:5 and 1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false'
and the corresponding phase conductor are indicated on the display.
Important ! Before working on the current transformers disconnect the voltage
paths of the energy meters.
Three-phase energy meter DSZ15WD-3x5A
with display and MID approval
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
28 305 015 - 1
GB
.
Typical connection:
4-wire-connection 3x230/400V
Connect the current transformer terminals on the secondary part to the
phase cunductors which are metered. These connections for the voltage
supply of the energy meters must be secured according to the local
installation regulations.
JUMPER
MODE
SELECT
k
l
K
L
k
l
K
L
k
l
K
L
S0 output
Menu guidance
Technical data
Rated voltage, extended range 3x230/400V, 50 Hz,
-2O%/+15%
Reference current Iref (Limiting current Imax) 3x0.05 - 5(6)A
Internal consumption active power 0.5W per path
Display LC display 7 digits,
therefrom 1 digit after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 1OmA
Operating temperature -25/+5C
Interface Pulse interface S0 according to DIN EN 62053-31,
potential free by opto-coupler,
max. 30 V DC/2OmA and min. 5V DC,
impedance 100 ohms,
pulse length 30 ms, 10Imp./kWh
Terminal cover sealable Terminal cover claps
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section
1) N and L terminals 16 mm2,
S0 terminals and jumper terminals 6mm
2
Recommended torque2) L- and N terminals 1,5Nm (max. 2,0Nm)
S0 terminals and jumper terminals 0,8Nm (max. 1,2Nm)
EC type examination certificate 0120/ SGS0314
The energy meter is used indoors.
Mechanical environmental conditions class M1
Electromagnetic environmental conditions class E2
1) The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2) The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal
must not be exceeded!
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
23/2020 Subject to change without notice.
Must be kept for later use!
We recommend the housing for operating instructions GBA12.


Produkt Specifikationer

Mærke: Eltako
Kategori: Måleudstyr
Model: DSZ15WD-3x5A

Har du brug for hjælp?

Hvis du har brug for hjælp til Eltako DSZ15WD-3x5A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Måleudstyr Eltako Manualer

Måleudstyr Manualer

Nyeste Måleudstyr Manualer

Uni-T

Uni-T UT220 Manual

3 April 2025
Uni-T

Uni-T UT681C Manual

3 April 2025
Uni-T

Uni-T UT216C Manual

3 April 2025
Uni-T

Uni-T UT611 Manual

3 April 2025
Uni-T

Uni-T UT210D Manual

3 April 2025
Uni-T

Uni-T UT210C Manual

3 April 2025
Uni-T

Uni-T UT210B Manual

3 April 2025
Uni-T

Uni-T UT682 Manual

3 April 2025
Uni-T

Uni-T UT275 Manual

3 April 2025
Uni-T

Uni-T UT08A Manual

3 April 2025