Safety switch (RCCB's) 25 - 100 A
|
6LE003036Ad - 145822
OFF
green
z
For the tripping times verication tests, in an
electrical installation, Hager certies that the RCDs, of
the Hager brand, conforming to standards EN 61008-
2-1, EN 61009-2-1, trip under a current of 5*IΔn in
accordance with the times imposed in table 41.1 of
standard DIN VDE 0100-410 (VDE 0100-410) 2018-10.
Position contact indication.
Test
1, 3, 5...12
Fev.
Test
OFF
yellow
or
Earth leakage fault indication.
Please note the following
1 - The current rating per pole of the RCCB must not be
exceeded by the maximum demand of the protected
circuits.
2 - If RCCB trips OFF after installation, locate and repair
faulty appliances (cumulative leakage from a number
of appliances may exceed the RCCB tripping
current, causing RCCB to trip OFF).
3 - The “main neutral” and “main earth” should be
checked to ensure good connection.
4 - If RCCB trips intermittently will not reset, or test
button will not work, check for low insulation
resistance between neutral & earth wiring.
5 - RCCB may be fed in any position:
LOAD and LINE circuits may be connected top or
bottom.
Electrical connection for P+N or for three phase only.
Three phase & neutral use
or Three phase use
Single phase use
Two circuits
L1
L1
T
2 4 6 8
1 3 5 7
N
N
N
N
1
1
/ 1 1/
/ 1 1/
7
/
1
1
/
/
/
/
/ 1
1
One circuit
Electrical connection 2 pole.
For an RCD where two or three circuits are to be protected, the Hager neutral link KM03A
may be connected to the outgoing N terminal for the convenient splitting of the neutrals.
N1 N2 L2L1
2
1 3 N
Neutral Link
4 N
T
L1 circui- t
Safety instructions
The installation and mounting of electrical
appliances must only be performed by qualied
electricians, in compliance with installation
standards and in accordance with the guidelines,
provisions and safety and accident prevention
regulations in force in the country concerned.
14 mm max. 16 - 63 A 80 - 100