Design 30 Consumer Unit
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
instructions prior to energizing this board. This check should include
factory made connections which may have loosened in transit.
Good workmanship and proper materials must be applied by the installer.
The cable entry method shall, as far as reasonably practical, maintain the
non-combustable arrangement of the enclosure. Account shall be taken of
these instructions.
Easy t front cover assembly allows the cover to be located at the
top of the board and locked Into place that enables the cover to stay
secure when replacing or removing during an installation. The units have multiple xing points that will suit No.8 & No.10 screws
Where Electrical Knockouts are provided for top or bottom cable entry
are sized and positioned to suit standard trunking i.e 100x50mm,
50x50mm & 40x25mm, grommet strip is provide to protect the cables
when entering the board.
Rear cable entries shall enter thorough selected rear Knockout; once
the Knockout is removed the cable protector bracket can be tted
to allow safe installation of the cables. Grommet strip lengths: Small
EKO – 79mm, – 127mm – 255mmLarge EKO Rear EKO
Note: Only BASEC approved cable should be used
1.0mm2 to 16mm2 for outgoing cables
up to 35.0mm2 for incoming live cables
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Removal of front
cover:
Wall Fixing:
Cable entry facilities:
For additional cable protector plates please use:
Insulated ref. VM02CE
Metal ref. VM01CE
GB
1 ZD0813 - Issue 6 10-15
ZD0813ZD0813


Produkt Specifikationer

Mærke: Hager
Kategori: Ikke kategoriseret
Model: VM206K
Kode for international beskyttelse (IP): IP2XC
Bredde: 221 mm
Dybde: 102 mm
Højde: 240 mm
Husmateriale: Stål
Monteringstype: Overflade