Læs gratis den danske manual til Haier AU482FIERA(DC) (3 sider) i kategorien Aircondition. Denne vejledning er vurderet som hjælpsom af 26 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 13.5 anmeldelser. Har du et spørgsmål om Haier AU482FIERA(DC), eller vil du spørge andre brugere om produktet?

Side 1/3
Haier Commercial Air Condition
ADDRESS: NO.1 Haier Road,Hi-tech Zone, Qingdao 266101 P.R.China Haier reserves the right to make change without any notice.
Web: Http://www.haier.com
Submittal Data Sheet
MRV SI
AU482FIERA(G)
• DC inverter twin rotary compressor and DC motor
• Compact size
• Wider operation range from -5~43°C
• PID control enables precise refrigerant ow and temperature.
FEATURES & BENEFITS
Haier Commercial Air Condition
ADDRESS: NO.1 Haier Road,Hi-tech Zone, Qingdao 266101 P.R.China Haier reserves the right to make change without any notice.
Web: Http://www.haier.com
Submittal Data Sheet
Outdoor unit name:
Outdoor unit model:
Type:
Unit combination:
Rated cooling conditions:
Rated heating conditions:
Rated piping length (m):
Rated height difference(m):
Rated cooling capacity (kW):
Nom cooling capacity (kW):
Cooling input power (kW):
EER:
Rated heating capacity (kW):
Nom heating capacity (kW):
Heating input power (kW):
COP:
Power supply(V/Hz/Ph):
Power supply connections:
Min. circuit Amps MCA (A):
Max. starting current MSC(A):
Rated load Amps RLA(A):
Dimensions(H×W×D) (mm):
Net weight(kg):
Compressor type:
Capacity control range (%):
Capacity index limit:
Airow rate (H) (m3/h):
Gas pipe connection (mm):
Liquid pipe connection (mm):
High pressure gas pipe connection (mm):
Oil equalization connection (mm):
Sound pressure (H) (dBA):
Sound power level (dBA):
Max. No. of indoor units:
MRV SI
AU482FIERA(G)
Heat pump
/
/
0
220-230/50/60/1
L,N, Ground
31.30
32.00
2
21.20
1250×960×340
105
DC inverter rotary
10~100
15.00
15.00
4.20
3.57
17.00
17.00
4.00
4.25
50~130
6500
Φ19.05
Φ9.52
/
/
59
70
8
Indoor(°C DB/WB):27/19
Ambient(°C DB/WB):35/24
Indoor(°C DB/WB):20/14.5
Ambient(°C DB/WB):7/6
PERFORMANCE
OUTDOOR UNIT DETAILS
Max. overcurrent protection
(MOP)(A)
Refrigerant type:
Holding refrigerant charge (kg):
Additional charge (kg):
Pre-charge piping (length) (m):
Max. pipe length (total) (m):
Max. height separation (IDU to IDU) (m):
Cooling operation range (°C DB):
Heating operation range (°C DB):
Max. height separation (IDU to ODU)(m):
Cooling adjustable range (°C DB):
Heating adjustable range (°C DB):
R410A
3.6
Piping length
caculation amount
0
100
10
-5~43
-15~21
30
16~30
16~30
SYSTEM DETAILS


Produkt Specifikationer

Mærke: Haier
Kategori: Aircondition
Model: AU482FIERA(DC)

Har du brug for hjælp?

Hvis du har brug for hjælp til Haier AU482FIERA(DC) stil et spørgsmål nedenfor, og andre brugere vil svare dig




Aircondition Haier Manualer

Haier

Haier ESA412R Manual

5 Januar 2025
Haier

Haier QPSA13 Manual

4 Januar 2025
Haier

Haier QHM10 Manual

4 Januar 2025
Haier

Haier QHM18 Manual

4 Januar 2025
Haier

Haier HPFD12XHP Manual

4 Januar 2025
Haier

Haier QHM15 Manual

4 Januar 2025
Haier

Haier HWR05XCR Manual

4 Januar 2025
Haier

Haier QHC18 Manual

4 Januar 2025

Aircondition Manualer

Nyeste Aircondition Manualer