IFM ID002A Manual


Læs gratis den danske manual til IFM ID002A (3 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 11 personer og har en gennemsnitlig bedømmelse på 5.0 stjerner ud af 6 anmeldelser. Har du et spørgsmål om IFM ID002A, eller vil du spørge andre brugere om produktet?

Side 1/3
Operating instructions
(Ex protection related part) for inductive sensors
according to EU directive 94/9/EC annex VIII (ATEX)
group II, equipment category 3D
ID002A / ID502A
UK
80233522 / 00 11 / 2015
2
Remarks for safe use in hazardous areas
Functions and features
Use in hazardous areas according to the classification
II 3D
(group II, category 3D, apparatus for dust atmosphere).
Complies with the reqirements of the standards EN 60079-0 and EN 60079-31.
Marking
II 3D Ex tc IIIC T90°C Dc X IP65
Permissible operating temperature of the application (proper usage):
Ta: -20°C...+60°C
Installation / Set-up
The units must only be installed, connected and set up by qualified staff. The qualified staff
must have knowledge of protection classes, regulations and provisions for apparatus in
hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable
for the application.
Installation remarks / Installation
Adhere to the relevant national regulations and provisions.
The relevant installation regulations must be adhered to. In particular, take into account the
requirements relating to the temperature limitation as regards the expected dust deposits.
Avoid electrostatic charging on housings and cables.
To avoid electrostatic charging steps must be taken to ensure the equalisation of potential
of metal parts (plug housing, fixing elements, etc.).
Protect the units and the cables efficiently against damage.
To avoid soiling, do not remove the dust caps from the cable glands or the plugs until
introducing the cables or attaching the socket.
It is the responsiibility of the user to determine the appropriate tightening torques for
the type of cable used. The cable glands and the cap nut have to be firmly tightened.
If the connection thread or the cap nut is overtightened or undertightened, the type of
connection, the tightness and the strain relief are impaired.
The housing screws are to be fastened with 0.5 Nm, the fixing screws with max. 4 Nm.
Maintenance intervals are application-specific and therefore need to be defined by the
operator depending on the operating conditions.
During maintenance, especially those parts on which the type of protection depends need
to be examined (e.g. integrity of the components of the cable gland, of the seals).


Produkt Specifikationer

Mærke: IFM
Kategori: Ikke kategoriseret
Model: ID002A

Har du brug for hjælp?

Hvis du har brug for hjælp til IFM ID002A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret IFM Manualer

IFM

IFM DX1041 Manual

28 Juli 2025
IFM

IFM TAD191 Manual

21 Juli 2025
IFM

IFM VVB302 Manual

20 Juli 2025
IFM

IFM UGT301 Manual

20 Juli 2025
IFM

IFM IEP201 Manual

20 Juli 2025
IFM

IFM AC2953 Manual

15 Juli 2025
IFM

IFM SU2050 Manual

11 Juli 2025
IFM

IFM SU9050 Manual

11 Juli 2025
IFM

IFM SU8651 Manual

10 Juli 2025
IFM

IFM SU2651 Manual

10 Juli 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer