CS102 SNMP Card
User Manual
5
Chapter 1 - Introduction
CS102 can manage UPS systems using their native serial protocols. User can use web browser or
any NMS, SNMP, or MODBUS manager to manage UPS via Ethernet.
The CS102 also provides shutdown schedules for different operating systems: for example, it can
send a shutdown command in the event of a scheduled shutdown, utility power failure, UPS low
battery condition, UPS overload, UPS overtemperature, and other alarms. All extinguishing events
are user configurable. The shutdown software will perform an orderly automatic shutdown to
avoid crashing clients or servers.
1.1. Features
Real-time UPS health monitoring
Comprehensive UPS management and flexible configuration via Web Browser, NMS, Telnet,
and SNMP.
Automatic events notification via E-mail, and SNMP Trap.
Graceful shutdown to protect up to 250 servers/workstations from data loss due to power
outa . ge
Assigned IP automatically via DHCP or BOO . TP
Scheduling shutdown/startup/reboot of UPS via remote control.
Regularly records UPS parameters for statistical analysis and event diagnosti . cs
Support for standard UPS MIB (RFC1628).
Auto-sense to works in the 10/100Mbps fast Ethernet network environme . nt
WOL function supported.
Configuration utility simplifies the firmware upgrade proce . ss
Support Radius and NTLM . V1
IPv4 and IPv6 dual ck. sta
CS102 SNMP Card
User Manual
6
1.2. CS102 System Application
The following diagram shows how the CS102 SNMP Web Card which can be used in a network
application. supports various kinds of protocol such as HTTP, SNMP, MODBUS, c It et
Through the SNMP NMS and Web Browser, user can obtain the UPS status, issue commands of
UPS and set up CS102 configuration via the network.
CS102 also provides shutdown software for sending the event notifications to the connected tool
clients. The shutdown software can be installed on various operating systems. It can
communicate with the CS102 automatically via a proprietary protocol. CS102 will issue the
shutdown command to shutdown software in the event of AC failure, battery low and scheduled
shutdown. Shutdown software will proceed to the shutdown process to prevent the abnormal
shutoff of host or server.
CS102 SNMP Card
User Manual
9
Step3. address to the same network Select the device and then click “Set IP” to change the IP
segment as your LAN.
Step4. Type in Account and Password . The default administrator and click on “Next” button
account is:
Account: admin
Password: cs102snmp
CS102 SNMP Card
User Manual
14
2. Enter the appropriate date and time information in the specified format and click to “Apply”
save the settings.
3.4. Network Protocols
By default, only strictly necessary network protocols are enabled.
Select “Network Protocols” from the main menu to enable the required additional network
protocols In case you are not sure what to enable, please leave the default. .
3.5. Network Configuration
1. from the main menu: Select “Network Network settings”
2. Enter the required information: IP address, Gateway, Subnet Mask, DNS
CS102 SNMP Card
User Manual
16
Chapter 4 - Web Interface
4.1. System Status
In this section you can check the real time operating status of the UPS, Schedule, Alarm and other s,
product information.
4.1.1. Dashboard
In the dashboard, you can check the operational status, scheduling, and other data of the UPS.
This page updates automatically.
Section
Power Flow Diagram
Voltage Real time Chart
Battery Real time Status
History Log of Output
Load
Schedule Calendar
Active Alarm List
CS102 SNMP Card
User Manual
20
Identification
UPS Identification
Item
UPS Model
UPS Name
UPS Serial Number
UPS Firmware Revision
CS102 Firmware Revision
UPS Type
UPS Protocol
UPS Baud Rate
Rating Group
Item
Input Rating Voltage
Input Frequency
Output Rating Voltage
Output Frequency
Output Rating Current
Rating Battery Voltage
Output Rating VA
Output Rating Watt
UPS Control
This section let you perform control such as stopping/starting the UPS and running a battery test.
Item
UPS Shutdown Delay
UPS Sleep Time
CS102 SNMP Card
User Manual
31
Buttons
Item
Description
Reset To Default
To reset the CS102 configuration to the factory default.
Reboot
Restart the CS102. It has no effect on the UPS.
Apply
To save the changes made in this page
Upload and Download
Item
Description
Download Root Certificate
To download the current certificate of the CS102
Download Configurations
Allows to create a backup file of the current CS102 configuration.
Upload Configurations
Allows to restore a configuration previously saved using
“Download Configurations” button
Upload CA file
To upload and use a custom certificate file.
CS102 SNMP Card
User Manual
34
4.3.3 Web Settings .
Web Settings
This page lets you configure the settings related to the Web monitor refresh interval and timeout
when you log in.
Item
Description
Web Refresh Time
The refresh interval (in seconds) of web pages.
Logs per page
Set the number of lines displayed on each log pages
"CS102 Event Log", "UPS Event Log", "History Log" (UPS Management
Alerts & Logs)
Web Timeout Interval
It specifies the time interval (in seconds), to log out the user if the user
has no action on the web page.
External Links Setup
This page describes setting up links to web pages and/or external websites. For example, another
UPS or the technical support home page. Up to four links can be set.
Item
Description
Screen Text
The description of the link name that will be displayed in the menu structure,
within the "External Links" menu.
Link Address
The real name of web page to be connected, in URL format.
Status
This field controls the visibility of the link on menu tree. Setting "Disable" will
make this link invisible from menu tree.
CS102 SNMP Card
User Manual
41
4.4.3 WakeOnLAN .
The Wake On LAN ("WOL") feature can turn on a PC or compatible device, via its MAC address.
After the clients shut down due to UPS shutdown events and after the shutdown events return to
normal, the WOL packet will be sent to the client to restart the PC.
Up to 24 client MAC addresses can be set.
Setting
Item
Description
Repeating Times
The repeat times of sending WOL packet to client. Range 1~99. :
Interval Timer
The time interval (in seconds) between two actions of sending the WOL
packet to the client. Range: 1~999 seconds.
WOL Table
Item
Description
Test
If this option is selected, the WOL packet will send to client to start up PC after
pressing the OL Test " button. "W
MAC Address
Enter the MAC address of the device you want to boot using a WOL packet.
Control
Enable, or disable, the WOL function.
Description
User description. The maximum length of the string is 31 characters.
CS102 SNMP Card
User Manual
46
Chapter 5 - Configuring the CS102 via SSH
The SSH protocol allows you to access the configuration of the CS102 without using the web
interface. For security reasons, the SSH protocol is disabled by default; you can enable it here:
[Network] [Protocols] [SSH Connection] → →
5.1. Login
Use SSH software (like PuTTY ) to connect to the CS102. When the following message appears “ ”
on the screen, enter your username and password:
Login as : admin
admin@192.168.53.23's password: *****
The CS102 Configuration Utility main menu will then be displayed.
5.2. CS102 s etup
From the main menu, digit page: ” to enter the 1 SNMP/WEB Card Settings
============================================================
CS102 Configuration Utility
[CS102 Legrand v0.90 a7]
============================================================
1. SNMP/WEB Card Settings
2. Reset Accounts/Passwords to Default
3. Reset Configuration to Default
4. Restart SNMP/WEB Card
0. Exit
Please Enter Your Choice => 1


Produkt Specifikationer

Mærke: Legrand
Kategori: Netværkskort/adapter
Model: CS102
Bredde: 68 mm
Dybde: 133 mm
Højde: 43 mm
Vægt: 69 g
Produktfarve: Grå
Opbevaringstemperatur (T-T): 0 - 60 °C
Relativ luftfugtighed ved drift (H-H): 20 - 95 %
Ethernet LAN-porte (RJ-45): 2
Ethernet LAN: Ja
Strømforbrug (typisk): 3 W
Driftstemperatur (T-T): 0 - 40 °C
Hurtig installationsvejledning: Ja
Forbindelsesteknologi: Ledningsført
Understøttede netværksprotokoller: IPv4, IPv6, DHCP, DNS, HTTP, HTTPS, SSH, NTP, SMTP, SNMP, MODBUS TCP, Wake on LAN, UPnP, RADIUS
LED-indikatorer: Fejl
Udgangsspænding: 5.5 - 40 V
Antal USB-porte: 2
Processorfrekvens: 180 MHz
Understøttede Windows-operativsystemer: Ja
Understøttede Linux-operativsystemer: Ja
Grænseflade: Ethernet
Intern: Ja
Maksimal dataoverførselshastighed: 1000 Mbit/s
Flashhukommelse: 8 MB
Ethernet-grænsefladetype: Gigabit Ethernet
Komponent til: Nødstrømsforsyning (UPS)
Monteringsbeslag inkluderet: Ja
Processor arkitektur: ARM9
Wake-on-LAN klar: Ja

Har du brug for hjælp?

Hvis du har brug for hjælp til Legrand CS102 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Netværkskort/adapter Legrand Manualer

Legrand

Legrand CS102 Manual

9 Oktober 2024

Netværkskort/adapter Manualer

Nyeste Netværkskort/adapter Manualer