Installaon Manual
Type:
:
:
::NDR DIN rail power supply Series NDR-75,
(
(
(
(( :
:
:
:: 120, 240, 480)
)
)
))
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 6.3A DR 75 12 100 12
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 3.2A DR 75 24 100 24
N - - INPUT: -240VAC 1.6A 50/60Hz OUTPUT: V 1.6A DR 75 48 100 24
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V A DR 12 100 12 10
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V 5A DR 24 100 24
N -120- INPUT: -240VAC 2.6A 50/60Hz OUTPUT: V 2.5A DR 48 100 48
NDR-240- INPUT: -240VAC 2.8A 50/60Hz OUTPUT: V A 24 100 24 10
NDR-240- INPUT: -240VAC 2.8A 50/60Hz OUTPUT: V 5A 48 100 48
NDR-480- INPUT: -240VAC 5.3A 50/60Hz OUTPUT: V A 24 100 24 20
NDR-480- INPUT: -240VAC 5.3A 50/60Hz OUTPUT: V A 48 100 48 10
Introducon
NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well DIN series, ’s
they can be mounted on a TS35 Standard DIN rail.
Installaon
( )1 Always allow good venlaon clearances, 5mm le and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheang. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
( )2 The appropriate mounng orientaon for the unit is vercal, the input terminals the bottom and output on at
the top. Mounng orientaons other than that, such as upside down, horizontal, or table-top mounng, is not
allowed.
( )3 Use copper wire only, and recommended wires are shown as below.
Make sure that all strands of each stranded wire enter the terminal connecon and the screw terminals are
securely xed to prevent poor contact. If the power supply possesses mul-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
( )4 Use wires that can withstand temperatures of at least 80°C, such as UL1007.
( )5 Recommended wire strapping length m (0.197 . is 5m ”)
( )6 Recommended screwdriver is 3 , sloed type.mm