Læs gratis den danske manual til Samsung AM250TNBFGB (18 sider) i kategorien Aircondition. Denne vejledning er vurderet som hjælpsom af 44 personer og har en gennemsnitlig bedømmelse på 4.9 stjerner ud af 22.5 anmeldelser. Har du et spørgsmål om Samsung AM250TNBFGB, eller vil du spørge andre brugere om produktet?

Side 1/18
Air conditioner
Installation manual
ADN***BDE** / AM***FNBD** / AM***FNBF** / AM***TNBF**
Thank you for purchasing this Samsung Product.
Before operating this unit, please read this manual carefully and retain it for future reference.
6
Safety precautions
CAUTION SIGNS
After completing the installation, run the trial operation. If no error occurs, explain to the customer how to use and clean the
air conditioner according to the users manual. In addition give the installation manual and the users manual to the customer.
Before the installation, check if the product is in good shape.
f Do not install the product with the damage which occurred during shipment.
All of the materials used to manufacture product and packages are eco-friendly and they are recyclable.
Refrigerant used in this product must be added or disposed in an appropriate way by qualied personnel.
f At the end of the life cycle, take it to a proper recycling or disposal center or return it to the dealer so that it can be
disposed correctly.
Combination rate
f This product should be connected with outdoor unit of the DVM S
f The combinations of the installation.
- This product should be combined among 50~130% of outdoor unit's capacity.
- When this product would be combined with heat pump outdoor units for 130~180% combination rate, it need to meet
the conditions below.
1) The combination rate for indoor units : Under the 100% of the A2A indoor units + Under the 80% of the DVM Hydro
unit/ Hydro unit HT.
2) A2A indoor units should be operated for cooling mode only, and DVM Hydro unit/ Hydro unit HT should be operated
for heating mode(including oor heating) only.
3) It is not possible to operate A2A indoor units and DVM Hydro unit/ Hydro unit HT at the same time.
- When combining an outdoor unit with an indoor unit, refer to the tables below for the capacity of DVM Hydro HT.
Capacity correction
AM160FNBF✴✴
AM160TNBF14.0kW
AM250FNBF✴✴
AM250TNBF22.4kW