index: WMGBMRP201
Testing RCD breakers of AC, A, B types
Testing of general, short delay and selective RCDs for the rated
current values 10, 15, 30, 100, 300, 500 mA
Measurement of IA trip current and tripping time tA for currents
0.5IΔn, 1IΔn, 2IΔn, 5IΔn
RE and UB measurement without RCD tripping
Extended AUTO function of RCD measurement
Measurement of IA and tA during one RCD tripping
Specialist in
residual-current devices
Features
Additional functions
Checking the correctness of PE connection using a contact electrode
Measurement of voltage (0 … 500 V) and network frequency
Memory of 990 results
Wireless data transmission to a computer
Backlit keypad
page 2 / 3 sonel.com
"m.v." - measured value
Safety and operating conditions
Measuring category acc. to EN 61010 IV 300V, III 600V
Ingress protection IP67
Type of insulation acc. to EN 61010-1 and IEC 61557 double
Dimensions 220 x 98 x 58 mm
Weight ca. 0.7 kg
Memory and communication
Memory 990 cells, 10 000 records
Data transmission radio
Other data
The product meets the EMC (emission for industrial
environment) requirements according to standards
EN 61326-1
EN 61326-2-2
Specications
Measurement functions Measurement
range
Display
range Resolution Accuracy
±(% m.v. + digits)
Measurements of RCD parameters
RCD tripping test and measurement of tripping time tA
measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
general and short-time delay RCD
0 ms…300 ms 0 ms…300 ms
1 ms ±(2% m.v. + 2 digits)
selective RCD 0 ms…500 ms 0 ms…500 ms 1 ms ±(2% m.v. + 2 digits)
Measurement of RCD tripping current IA
measuring current 0.15 IΔn2.0 IΔn
for sinusoidal residual current (AC type) 3.0 mA…500 mA from 0.1 mA ±5% I3.0 mA…500 mA Δn
for unidirectional residual current and
unidirectional with the 6 mA DC bias (typeA) 1.5 mA…420 mA 1.5 mA…420 mA from 0.1 mA ±10% IΔn
for direct residual current (type B) 2.0 mA…600 mA 2.0 mA…600 mA from 0.1 mA ±10% IΔn
Application areas
The meter enables the user to measure the parameters of residual-current de-
vices (RCDs), such as time or operating current. The device is useful for testing
electrical systems with circuits protected by RCDs of AC, A and B type.
Technical data
Increased resistance to environmental conditions
The meter will cope well in difcult environmental conditions. Protection
against penetration of dust and water is ensured by a unique housing with a
level of protection IP67.
Communication and software
You can easily transfer measurement data to your computer via wireless
communication. In order to generate a report on measurements for electric
shock protection, use Sonel Reports PLUS software. Saving the downloaded
data to the simplest formats and printing is provided by free Sonel Reader
software.