Vemer HT NTC-2P7A Manual


Læs gratis den danske manual til Vemer HT NTC-2P7A (33 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 14 personer og har en gennemsnitlig bedømmelse på 4.8 stjerner ud af 7.5 anmeldelser. Har du et spørgsmål om Vemer HT NTC-2P7A, eller vil du spørge andre brugere om produktet?

Side 1/33
4ERMOREGOLATORI
$IGITALI
(4 
-ANUALED5SO
5SER-ANUAL$IGITAL(EAT2EGULATORS
- 31 -
User Manual Digital Heat Regulators
Contents
Safety warnings Page 32
Technical specifications Page 32
Description of instrument Page 35
Electrical connections Page 35
Glossary Page 36
Operation Page 41
Setting the regulation parameters Page 41
Parameter menu Page 43
Error messages Page 50
Reference standards Page 51
Dimensions and connection diagrams, 33x75 mm Page 52-55
Dimensions and connection diagrams, 72x72 mm Page 56-57
Dimensions and connection diagrams, 4-DIN Page 58-59
English
- 32 -
User Manual Digital Heat Regulators
During the installation and operation of the instrument, the following
safety instructions should be followed:
Series
Series of digital thermoregulator for regulating the temperature that execute 1B type
actions (EN 60730-1).
of digital temperature regulators satisfying the simplest requirements in
the field of heat regulation. They can be used as heating or refrigeration regulators
and as maximum/minimum alarms.
Three dedicated base models for probe input:
- PTC thermal resistances ( os. emp.P T Coeff.) - Ni100, Pt100 HT NiPt
- NTC thermal resistances ( egative emperature N T Coefficient) HT NTC
- TC thermocouples - J, K, L, R, S, T, E, N HT JK
; or each single model, the probe input can be configured from the keyboard.
; wo probe inputs for the HT NTC models, for the measurement of two temperatures
that can be displayed alternatively by the closure or opening of an outer consensus
to be connected to the instrument, or directly from the keyboard for the 72x72 mm
rear panel version (this version has no digital input).
;Relay capacity: 8A / 250VAC
;Available in versions with 1 or 2 relay outputs with exchange contact.
;Heat re
g
ulators with 3 di
g
it, seven se
g
ment and decimal point display.
TECHNICAL SPECIFICATIONS
SAFETY WARNINGS
1) The instrument should be installed by qualified personnel
2) Read the instructions in this manual carefully
3) Carefully follow the instruction diagrams to install the device
4) Before gaining access to the connector terminals, make sure the conductors
to be connected to the instrument or already connected are not powered
5) Make sure the electric panel in which the device is inserted will prevent
access to the terminals after installation
6) Do not supply power to the device if any part of it is damaged
The instrument must be installed and activated in compliance with current
electric systems standards.
7)
The connection cables should be able to resist the maximum operating
temperature in the form of the maximum ambient temperature + 20 °C
8)
The instruments guarantee main insulation between the low voltage parts
(250 V) and the extremely low voltage parts
10)
9)
Any outside switches connected to the control panel should guarantee
a minimum insulation of 250 V AC at operating temperature, or should be
protected by equivalent insulation
IMPORTANT: In order to avoid malfunctions, the differential of intervention
(DF1 or DF2 parameter) should not be set above 30 °C.
English
- 33 -
User Manual Digital Heat Regulators
>Digital
>Relay capacity: 8A / 250VAC
parameter setting:
- Set point
- Differential
- Neutral zone
- Output drive times
- Digital input function and delay time
- Alarm delay / buzzer enable time
- Probe calibration offset
- Resolution displayed
- Temperature measurement unit
- Measurement display filter (update speed)
- Probe input type
- Password
- Operating modes (regulation):
ON/OFF direct and/or reverse action with or without neutral zone
PWM direct and reverse action and neutral zone
— ALARM
Refrigeration mode
Special mode
> independent set points
>Digital input: 1 (not versions HT NiPt NTC JK-..P7A, HT -P7A, HT -..P7A) for outside
consensus for configurable function: outside alarm, regulation ON/OFF, selection
of probe to be displayed, set point switching, direct/reverse switching, etc
>Acoustic and visual alarm signals for: outside alarm (from digital input),
probe alarm (malfunction), minimum or maximum alarm
>Infrared receiver with RC-5 protocol (not versions HT NTC NTC-1DA, HT -2DA) for
remote control (accessory available separately for remote programming)
>Available in the following fixing versions: rear panel 33x75 mm,
rear panel 72x72 mm and modular 4 DIN
> ower supply: see table on the following page
> !ated power output: 4.5 VA
>Max absorption: 100 mA at 12 V 50 mA at 24 V (1 channel)
>Operating temperature: 0 ÷ +50 °C
>Operating humidity: <80%
>Storage temperature: -10 ÷ +70 °C (<80% RH)
>Protection level: front panel IP54 (IP40 for the 4 DIN module version)
terminals IP20
>Display range: -99 ÷ +999 °C
>Display resolution: 0.1 °C (-9,9 ÷ +99.9 °C) and 1 °C (< -9.9 °C and > +99.9 °C)
>Precision: ±0.5 % of the end of scale value ±1 digit
(at an ambient temperature of 23 °C)
>Sampling time: 0.5s
> #emperature T2 signalling lamp (only models HT NTC-..P7.. and HT NTC-..D..)
>Relay intervention signalling lamp.
English
- 35 -
User Manual Digital Heat Regulators
Display
. 3 digit led display with decimal point is used.
For all the models, the display range is:
- minimum display: -99 °C or -9.9 °C
- maximum display: 999 °C or 99.9 °C
Relay intervention signalling lamp:
.Out 1:
LED off if relay one is OFF, on if relay one is ON, flashing if relay one in OFF
is waiting to become ON due to an active timing.
.Out 2:
LED off if relay two is OFF, on if relay two is ON, flashing if relay two in OFF
is waiting to become ON due to an active timing.
Keys
.Three parameter setting keys are used:
Confirm and parameter programming/display key.
Key used to increase the parameter or go to the next parameter.
Key used to decrease the parameter or leave the menu.
. &strictly to the instructions in the safety warnings and the
“connection diagram section.
ELECTRICAL CONNECTIONS
OK
DESCRIPTION OF INSTRUMENT
English
- 37 -
User Manual Digital Heat Regulators
PWM operation (in proportion to time)
,This is a neutral zone type of operation in which the relays are activated
periodically in impulse mode
(the interval can be set, see the
output menu).
The PWM procedure modulates
the power in accordance with the
position occupied by the
measurement within the
differential (the further we move
away from the set point, the more
the power increases).
Important: we advise against using this method to drive compressors,
due to the very close distance between start-up and shutdown.
Direct operating mode [PRO=0]
,In this mode, all the outputs
operate in direct. The values
of set point 1 [ST1] and
differential 1 [DF1] have
to be set. Hysteresis is to the
right of the set point. If both
outputs are used, the
hysteresis for each output is
equivalent to half the
differential. In this case,
output 1 will be activated when the measurement controlled reaches the value
[ST1]+[DF1]/2 [SP], and remains active until the temperature drops below the value of ,
while output 2 is activated by temperature values of and remains active [SP]+[DF1]
until the temperature drops below the value of .[SP]+[DF1]/2
Reverse operating mode [PRO=1]
,In this mode, all the outputs operate in reverse.
The set point 1 [ST1] and differential 1 [DF1] values have to be set.
Hysteresis is to the left of the
set point. If both outputs are
used, the hysteresis for each
output is equivalent to half the
differential. In this case,
output 1 will be activated
when the measurement
controlled reaches the value
[ST1]-[DF1]/2, and remains
active until the temperature
exceeds the value of [SP], while output 2 will be activated when the temperature
reaches the values of [SP]-[DF1] and remains active until the temperature
exceeds the value of [SP]-[DF1]/2.
Set - Diff (R) - ZN
R
ON
OFF
Set
Temperature
D
Set + Diff (D) + ZN
PWM Mode
ZN ZN
Set 1
D
ON
OFF
Diff. 1
PRO=0 mode
OUT 1
Set 1
D
ON
OFF
Diff. 1
OUT 1
D
OUT 2
1 output 2 outputs
Set 1
R
ON
OFF
Diff. 1
OUT 2
R
OUT 1
2 outputs
Set 1
R
ON
OFF
Diff. 1
OUT 1
1 output
PRO=1 mode
English
- 40 -
User Manual Digital Heat Regulators
Reverse operating mode with set point and differential switching
from digital input. [PRO=8]
*In this mode, both outputs operate in reverse, with set point 1/differential 1 or set
point 2/differential 2, depending on the status of the digital input.
More precisely, with set point 1/differential 1 if the digital input is open and set
point 2/differential 2 if closed. The operating modes are the same as mode 1.
It is necessary to set both values of the set points [ST1] [ST2]and and
differentials and .[DF1] [DF2]
Operating mode with channels 1 and 2 in reverse with set point 1
and differential. 1 and direct with set point 2 and differential 2
[PRO=9] respectively.
*In this mode, output 1 operates in reverse and output 2 in direct. It is necessary
to set the values of set point 1 [ST1] and differential 1 [DF1] for output 1,
and set point 2 [ST2] and differential 2 for output 2.[DF2]
The operating modes are the same as modes 0 and 1.
If there is a single output, this will operate in reverse.
Alarm operating mode [PRO=10]
*In this mode, output 1 operates in reverse (with neutral zone), and output 2 is
dedicated to the alarm. It is necessary to set the values of set point 1 [ST1],
PRO=8 mode
Set 2
R
ON
OFF
Diff. 2
OUT 2
R
OUT 1
2 outputs
Set 2
R
ON
OFF
Diff. 2
OUT 1
1 output
Set 1
R
ON
OFF
Diff. 1
OUT 2
R
OUT 1
Set 1
R
ON
OFF
Diff. 1
OUT 1
Digital
input
open
Digital
input
closed
PRO=9 mode
Set 1
R
ON
OFF
Diff. 1
OUT 1
1 output
Set 1
R
ON
OFF
Diff. 1
OUT 1
2 outputs
D
Diff. 2
OUT 2
ON
OFF
Set 2
English
- 42 -
User Manual Digital Heat Regulators
operation (this also happens if no key is pressed for at least 40 seconds).
Press “OK” to switch between the display of the parameter label and its numerical
value. To modify a parameter:
- from the display of its label or value, press “OK” and hold down for at least
three seconds
- the display will start to flash and will show the parameter value
- use the “up” ( ) “down” ( )and keys to increase or reduce the value
- press “OK” to confirm the parameter and leave the modification (the display
will stop flashing)
Note: if no key is pressed for at least 40 seconds, the instrument leaves
the parameter modification without memorising the changes made.
During the display and modification of the parameters, the instrument
will continue to operate with the previously set parameters.
If “password 1” is enabled (access password to protect the settings entered-see
system menu), when the “OK” key is pressed from normal status the message
“- - - will appear. To set the parameters, enter the previously set password
(a number from 0 to 255) with the “up” ( ) “down” ( )and keys and press
“OK” to confirm. If the password is entered correctly, the label of the first menu
will appear. Otherwise, the system will return to normal status.
Advanced programming
Access is gained to advanced programming from normal status by pressing and
holding down the p and q keys for at least 3 seconds.
Note: to reset the default values set in the factory, switch on the instru-
ment while holding down the “OK” key.
These parameters are grouped into eight menus, by type:
1) Regulation [REG](indicated with ): set point, differential, neutral zone
2) Output (indicated with [OUT]): output drive times, PWM cycle time
3) Digital input (indicated with [ING]): function, delay time
4) Alarm (indicated with [ALR]): output status in probe alarm, minimum/maximum
shift, differential, delay time, buzzer enable
5) Display (indicated with [DSP]): set point limits, probe offset, resolution,
measurement unit, measurement filter
6) Sensor [SNS](indicated with ): type of sensor, sensor parameters
7) System [SYS](indicated with ): password, modification enable, operating mode
8) Advanced [ADD](indicated with ): dependence, type, entry, differential/logic
All the parameters inside the menus and their values are listed in the section
that follows.
- Use the “up” ( )to scroll through the eight menus in sequence
- To enter the menu required, press “OK”
Press the “down” ( )key at any time to leave the menu and return to normal
English
- 43 -
User Manual Digital Heat Regulators
that can be modified by pressing “up” ( ). To display the value of the parameter,
press (pressOK” “OK” a second time to return to the display of the parameter
label).
- To modify the parameter value, hold down “OK” for at least 3 seconds.
- The parameter value will start to flash and it will be possible to increase or
decrease it with the “up” ( ) “down” ( )and keys.
- To confirm the value set, press “OK”.
The parameter will stop flashing and the new value will be displayed.
- It is possible to return to normal operation at any time by pressing “down” ( )
(or if no key is pressed for at least 40 seconds).
Note: if no key is pressed for at least 40 seconds, the instrument leaves
the parameter modification without memorising the changes made.
Note: During the display and modification of the parameters, the
instrument will continue to operate with the previously set parameters.
If “password 2” is enabled (access password for the protection of the settings-see
system menu), when the “up” ( ) “down” ( )and keys are held down
for three seconds from normal status, the message “- - - will appear.
To set the parameters, enter the previously set password (a number from 0 to 255)
with the “up” ( ) “down” ( ) “OK”and keys and press to confirm.
If the password is entered correctly, the label of the first menu will appear.
Otherwise, the system will return to normal status.
To simplify the programming of the instruments, the parameters are grouped into
various menus, in the following order:
— [REG] regulation menu
[OUT] output menu
[ING] outside input menu
[ALR] alarm menu
[DSP] display menu
— [SNS] sensor menu
[SYS] system menu
— [ADD] special parameter menu (for special operating mode only)
PARAMETER MENU
- Inside each menu, it is possible to scroll through the labels of the parameters
English
- 44 -
User Manual Digital Heat Regulators
Description of parameters
7Inside the tables, the labels are presented in the same order as they appear in the
various menus of the instrument.
[REG] regulation menu
Notes:
(1) For values LO1/LO2 and HI1/HI2, see the display menu [DSP]
(2) Parameter active only if the operating mode permits
[OUT] output menu
Notes:
(3) This parameter enables the handling of the times defined by DON, TOF and TON for
each output channel, in the following ways:
0timing not enabled for either relay output
1timing enabled for relay 1 output only
2timing enabled for relay 2 output only
3timing enabled for relay 1 and 2 outputs
(4) this parameter limits the number of start-ups per hour for the driver connected to
the instrument (this parameter is frequently used for compressors, for example)
(5) the minimum time for which the output should remain ON
(6) timing enabled for relay 1 output only OFF
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
ST1 set-point 1 degrees LO1 HI1 20.0 (1)
DF1 Differential for set-point 1 degrees 0.1 100 2.0
ST2 set-point 2 degrees LO2 HI2 30.0 (2)
DF2 Differential for set-point 2 degrees 0.1 100 2.0 (2)
DBN Neutral zone (dead band) degrees 0 100 2.0 (2)
min max
unit
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
ETR Handling time on
relays enabled - 0 3 3 (3)
DON Minimum time between
2 start-ups of the same relay min 0 200 0 (4)
TON Minimum relay ON time min 0 200 0 (5)
TOF Minimum relay OFF time min 0 200 0 (6)
INI Initial delay from start-up
of instrument min 0 200 0 (7)
TCL PWM cycle time sec 1 200 200 (8)
min max
unit
English
- 45 -
User Manual Digital Heat Regulators
(7) the delay time for the driving of the outputs from the instant of instrument reset
(8) the period that can be set for PWM regulation. This item is displayed only if the
operating mode selected is PRO=5 (see system menu).
[ING] outside input menu
Notes:
(9) The values that can be set are:
0Not active
1Outside alarm (with contact open) with delay time “DID” and automatic
reset at the end of the alarm. The output status becomes “SUI”
2Outside alarm (with contact open) with manual reset
3The input operates as a switch: instrument on with contact closed and off
with contact open
4The input operates as a switch for the display of the two probes S0 and S1
(contact open-probe S0, contact closed-probe S1)
The digital input function is excluded when one of the following
operating modes is selected inside the system menu [SYS]:
mode=6, mode=7 and mode=8
(10) This is the delay after which the instrument responds to a signal from the digital
input
(11) When the digital input is active and a time period “DID” has lapsed,
the outputs take on the following states:
0Both relays OFF
1Relay 1 ON and relay 2 OFF
2Relay 1 OFF and relay 2 ON
3Both relays ON
(12) This is the variation of the “Set in degrees when the instrument switches
to night operation
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
TID Digital input function - 0 4 0 (9)
DID Digital input delay min 0 200 0 (10)
SUI Output status with digital
input active (open) - 0 3 0 (11)
DEL Variation in night-time
temperature degrees -50.0 +50.0 5.0 (12)
min max
unit
English
- 46 -
User Manual Digital Heat Regulators
[ALR] alarm menu
Notes:
(13) This is the status taken on by the outputs in probe alarm condition (see note 11)
(14) This value is added to or subtracted from the set point defined for the maximum
or minimum alarm respectively
(15) If “yes”, the acoustic signal of the key and the buzzer are enabled in alarm
condition. If “no”, the buzzer is enable in alarm condition only.
(16) If “yes”, the type of alarm is also displayed during its timing.
If “no”, the type of alarm is displayed only at the end of the timing
[DSP] display menu
Notes:
(17) Parameter active only if the operating mode permits
(18) This value is added to the measurement to compensate for imprecision
(19) This is the resolution at which the measurement is displayed:
0.1 if “HI” or 1.0 if “LO”
(20) Important: if the measurement unit is modified, the parameters set are not con
verted automatically, but have to be re-calibrated.
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
SUA Output status in probe
alarm condition - 0 3 0 (13)
LOA Minimum alarm shift degrees 0.1 100 50 (14)
HIA Maximum alarm shift degrees 0.1 100 50 (14)
DFA Alarm differential degrees 0.1 100 2
TRA Alarm activation delay time min 0 200 0
SOU Buzzer enable - no yes yes (15)
EAC Alarm message in timing enable - no yes no (16)
min max
unit
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
LO1 Lower limit of set-point 1 degrees -99 HI1 -99
HI1 Upper limit of set-point 1 degrees LO1 999 999
LO2 Lower limit of set-point 2 degrees -99 HI2 -99 (17)
HI2 Upper limit of set-point 2 degrees LO2 999 999 (17)
SOF Probe calibration offset degrees -50 +50 0.0 (18)
RIS Resolution displayed - HI LO HI (19)
UNI Temperature measurement - C F C (20)
FIL Measurement filter - no yes yes (21)
min max
unit
English
- 47 -
User Manual Digital Heat Regulators
(21) If the parameter is set to “yes”, a mobile average is taken of 8 measurement
values (4 seconds approx.). If “no”, this average is not calculated
[SNS] sensor menu
Notes:
(22) the range of sensors and the default sensor depend on the model.
All the sensors used are listed below:
NiPt thermal resistance
Type of sensor Display message
Pt100 (*) PtE (*)
Ni100 nI
* The instrument is set to this parameter by default.
NTC thermal resistances
Type of sensor Display message
(**) nt0
(**) nt1
type 4 nt2 (*)
(**) CSt
* The instrument is set to this parameter by default.
It corresponds to the use of temperature sensor NTC code VN870200
** For the use of sensors other than “type 4” listed above (see note *), it is possible
to select one of the three items “nt0, nt1, CSt”, corresponding to probes
with different temperature/resistance ratios.
To identify the type of sensor to be selected in these cases, we recommend
contacting our Technical Assistance Service directly
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
TY0 Sensor type 0 - 0 16 (22)
TY1 Sensor type 1 - 12 16 (23)
GFA Cold joint correction enable - no yes yes (24)
S01 Display of sensor 0 or 1 - S0 S1 S0 (23)
min max
unit
English
- 48 -
User Manual Digital Heat Regulators
JK Thermocouples
Type of sensor Display message
J J
K (*) C (*)
L L
T t
E E
N n
R r
S S
* The instrument is set to this parameter by default.
(23) this parameter is visible in NTC models only
(24) this parameter is visible in TC models only
[SYS] system menu
Notes:
(25) the password is enabled if the parameter is different from 000
(26) if set to "yes", it is not possible to modify all the other parameters,
only to display hem
(27) the following operating modes are available:
0 channels 1 and 2 in direct mode with set-point 1 and 1
(hysteresis to the right of the set point)
1 channels 1 and 2 in reverse with set-point 1 and differential 1
(hysteresis to the left of the set point)
2 neutral zone with channel 1 in reverse and channel 2 in direct with
set-point 1 and differential 1
3as mode 0 but with differential centred on the set-point
4as mode 1 but with differential centred on the set-point
5 PWM regulation with channel 1 in reverse and channel 2 in direct
with set-point 1 and differential 1, and neutral zone where applicable
6switching between outputs in direct (with set-point 1 and differential 1)
and outputs in reverse (with set-point 2 and differential 2) from digital input
7outputs in direct with switching between set-point 1/differential 1 and
set-point 2/differential 2 from digital input
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
PS1 password 1 - to set the temperature 0 255 0 (25)
PS2 password 2 - to advanced settings 0 255 0 (25)
NEN Parameter modification enable yes no no (26)
PRO Operating mode 12 0 (27)
min max
English
- 49 -
User Manual Digital Heat Regulators
8 outputs in reverse with switching between set-point 1/differential 1 and
set-point 2/differential 2 from digital input
9 channel 1 in reverse with set-point 1 and differential 1 and channel
2 in direct with set-point 2 and differential 2
10 if one channel: alarm operation;
if two channels: channel 1 in reverse (with set-point 1, differential 1 and
neutral zone) and channel 2 in alarm operation
11 refrigeration mode
12 special mode
[ADD] special parameter menu
Notes:
(28) the parameter defines in what mode an output depends on a set-point or an
alarm mode. The values take on the following meanings:
0 output not active
1 output relates to set-point 1
2 output relates to set-point 2
3 switching between output in direct (with set-point 1 and differential 1) and
output in reverse (with set-point 2 and differential 2) through digital input
(open-direct, closed-reverse)
4 switching between set-point 1/differential 1 and set-point 2/differential
2 through digital input (open-set 1, closed-set 2)
5 output associated with maximum alarm for set-point 2
6 output associated with minimum alarm for al set-point 2
7 output associated with maximum alarm for set-point 1
8 output associated with minimum alarm for al set-point 1
9 output associated with maximum/minimum alarm for set-point 1
10 output associated with maximum/minimum alarm for set-point 2
(29) defines whether the type of regulation is ON/OFF (value 0) or PWM (value 1)
(30) indicates whether the neutral zone is present (value 1) or not (value 0)
(31) indicates the ON switching point of the relay with respect to the set-point
Labels of
parameters that
can be modified
Description
Parameter
values default
notes
DP0 Dependent on output 1 - 0 10 (28)
TI0 on/off or PWM 1 type - 0 1 (29)
DB0 Neutral zone 1 - 0 1 (30)
IN0 Entry 1 % -100 +100 (31)
DF0 Logic 1 differential % -100 +100 (32)
DP1 Dependent on output 2 - 0 10 (28)
TI1 on/off or PWM 2 type - 0 1 (29)
DB1 Neutral zone 2 - 0 1 (30)
IN1 Entry 2 % -100 +100 (31)
DF1 Logic 2 differential % -100 +100 (32)
min max
unit
English
- 50 -
User Manual Digital Heat Regulators
defined by the “dependence” parameter: the switching point is calculated by
adding a percentage “IN0” (from -100% to +100%) to the set-point of the
differential
(32) indicates the OFF switching point of the relay with respect to the point where the
ON switching took place. The OFF switching point is calculated by adding to the
ON point a percentage “DF0” (from -100% to +100%) of the differential.
Note: the default values of these parameters depend on the operating
mode and number of channels, as set out in the table below:
1 Channel Operating mode
Parameter 0 1 2 3 4 5 6 7 8 9 10
IN0 100 -100 -100 50 -50 -100 * 100 -100 -100 0
DF0 -100 100 100 -100 100 100 * -100 100 100 100
IN1 100 -100 100 50 -50 100 * 100 -100 100 0
DF1 -50 50 -100 -50 50 -100 * -50 50 -100 100
2 Channels Operating mode
Parameter 0 1 2 3 4 5 6 7 8 9 10
IN0 50 -50 -100 0 0 -100 * 50 -50 -100 -100
DF0 -50 50 100 -50 50 100 * -50 50 100 100
IN1 100 -100 100 50 -50 100 * 100 -100 100 0
DF1 -50 50 -100 -50 50 -100 * -50 50 -100 100
* The default values for mode 6 are the same as those of modes 0 or 1, depending
on whether the outputs are operating in direct or reverse.
6Due to alarms or malfunctions, the display of the measurement may alternate
with the display of messages describing the type of alarm.
The table below describes the alarm/error messages used.
Message Type of error Output status
ER0 Sensor 1 disconnected or in short circuit As parameter [SUA]
ER1 Sensor 2 disconnected or in short circuit As parameter [SUA]
ALL Minimum alarm Depends on operating mode
ALH Maximum alarm Depends on operating mode
ALE Outside input alarm As parameter [SUA]
OFF Regulation
ERR Error parameter storage
inhibited by outside input As parameter [SUA]
Note:
the “OFF” message is not alternated with the measurement, but remains fixed
on the display
If the message Err is shown, do a CLr reset.
ERROR MESSAGES
English
- 51 -
User Manual Digital Heat Regulators
Compliance to the Community Directives:
2006/95/EC (Low Voltage - LVD)
2004/108/EC (Electromagnetic compatibility- EMC)
is declared with reference to the follow Harmonised Standard:
EN 60730-2-9
REFERENCE ST AND ARDS
English
- 53 -
User Manual Digital Heat Regulators
33x75 mm REAR PANEL DIAGRAMS
HT -2P3ANiPt
P
o
w
e
r
s
u
p
p
ly
~
Digit al
input Probe
input
PTC
2 wires
Digit al
input
Probe
input
PTC
3 wires
52 3 4 61 7 8 9 6 7 8 9
1411 12 13 1510 16 17 18
HT -1P3ANiPt
P
o
w
e
r
s
u
p
p
ly
~
Digit al
input
Probe
input
PTC
2 wires
Digit al
input
Probe
input
PTC
3 wires
Relay out put
8(1) A/250 V~
52 3 4 61 7 8 9 6 7 8 9
1411 12 13 1510 16 17 18
HT -2P3DNiPt
P
o
w
e
r
s
u
p
p
l
y
~
Relay out put 2
8(1) A/250 V~
Probe
input
PTC
3 wires
Probe
input
PTC
2 wires
Digit al
input
Relay out put 1
8(1) A/250 V~
Relay out put 1
8(1) A/250 V~
Relay out put 2
8(1) A/250 V~
Relay out put 2
8(1) A/250 V~
Digit al
input
1411 12 13 1510 16 17 18
52 3 4 61 789
16 17 18
6 7 8 9
Connection diagramModel
HT -1P3DNiPt
P
o
w
e
r
s
u
p
p
l
y
~
Relay out put
8(1) A/250 V~
Digit al
input
Probe
input
PTC
3 wires
Probe
input
PTC
2 wires
Digit al
input
6 7 8 952 3 41 6 7 8 9
English


Produkt Specifikationer

Mærke: Vemer
Kategori: Ikke kategoriseret
Model: HT NTC-2P7A

Har du brug for hjælp?

Hvis du har brug for hjælp til Vemer HT NTC-2P7A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Vemer Manualer

Vemer

Vemer Mini Time Manual

20 Juni 2025
Vemer

Vemer TCR Manual

2 Oktober 2024
Vemer

Vemer Set PC RF8 Manual

1 Oktober 2024
Vemer

Vemer ADR-D Vision Manual

22 September 2024
Vemer

Vemer ES Manual

10 September 2024
Vemer

Vemer Thalos RF Manual

3 September 2024
Vemer

Vemer VE 502E Manual

1 September 2024
Vemer

Vemer VE LAN Manual

10 August 2024
Vemer

Vemer LCR048 Manual

10 August 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

LG

LG LPC-M155X Manual

4 August 2025
LG

LG LX-U150 Manual

4 August 2025
LG

LG LM-U555X Manual

4 August 2025
LG

LG LM-M1030G Manual

4 August 2025
LG

LG DK7711N Manual

4 August 2025
Dual

Dual C 824 Manual

4 August 2025
LG

LG FFH-515A Manual

4 August 2025
LG

LG DKE574XB Manual

4 August 2025
Hikoki

Hikoki H70SD Manual

4 August 2025