Vimar 01703 Manual


Læs gratis den danske manual til Vimar 01703 (84 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 21 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 11 anmeldelser. Har du et spørgsmål om Vimar 01703, eller vil du spørge andre brugere om produktet?

Side 1/84
Installer Manual
By-alarm
01703-01703.120
64 zone control panel
Programming manual
1
By-alarm
Index
Introduction
General information 5 …………………………………………………………………………………………………………………………………………………………………………
Section 1 - Programming the control unit using the keypad 01705
Guidelines for programming the control unit using the keypad 8 …………………………………………………………………………………………………………………………
Primary menus
Primary menu diagram 10 ……………………………………………………………………………………………………………………………………………………………………
Settings
Keypad activation 11 …………………………………………………………………………………………………………………………………………………………………………
Input expansion activation 11 ………………………………………………………………………………………………………………………………………………………………
Output expansion activation 11 ……………………………………………………………………………………………………………………………………………………………
Reader activation 11 …………………………………………………………………………………………………………………………………………………………………………
Digital telephone 12 …………………………………………………………………………………………………………………………………………………………………………
GSM dialler 12 ………………………………………………………………………………………………………………………………………………………………………………
Telephone 01706 12 …………………………………………………………………………………………………………………………………………………………………………
Direct connection to the computer 12 ………………………………………………………………………………………………………………………………………………………
Clock settings
Control unit time and date 13 ………………………………………………………………………………………………………………………………………………………………
Input programming
Zone programming 14 ………………………………………………………………………………………………………………………………………………………………………
Zone type 14 ……………………………………………………………………………………………………………………………………………………………………………
Number of zone unbalancings to cause an alarm………………………………………………………………………………………………………………………………… 15
Duration of switch alarm pulses 15 ……………………………………………………………………………………………………………………………………………………
Zone areas for different installations 15 ……………………………………………………………………………………………………………………………………………………
Area 1 - 8 15 ……………………………………………………………………………………………………………………………………………………………………………
Zones associated to the areas active on arming ON - INT - PAR 16 ……………………………………………………………………………………………………………
Keypads associated to the Areas 16 ………………………………………………………………………………………………………………………………………………
Readers associated to the Areas 17 ………………………………………………………………………………………………………………………………………………
Zone alarm options 17 ………………………………………………………………………………………………………………………………………………………………………
Memo zone alarm in events memory 17 ………………………………………………………………………………………………………………………………………………
Memo zone restore in events memory 18 ……………………………………………………………………………………………………………………………………………
Buzzer activated by zone alarm 18 ……………………………………………………………………………………………………………………………………………………
Double balance (alarm - tamper) 19 ……………………………………………………………………………………………………………………………………………………
Triple balance (alarm - tamper - masking) 19 …………………………………………………………………………………………………………………………………………
Alarm codes for multiple events 19 ……………………………………………………………………………………………………………………………………………………
Zone auxiliary options 19 ……………………………………………………………………………………………………………………………………………………………………
Buzzer sound for entry time………………………………………………………………………………………………………………………………………………………… 19
Buzzer sound for exit time 20 …………………………………………………………………………………………………………………………………………………………
Chime function 20 ………………………………………………………………………………………………………………………………………………………………………
Door Function 20 ………………………………………………………………………………………………………………………………………………………………………
Ding Dong Function 21 …………………………………………………………………………………………………………………………………………………………………
Which zone cannot be bypassed 21 …………………………………………………………………………………………………………………………………………………
Zone as last exit door 22 ………………………………………………………………………………………………………………………………………………………………
Tamper (anti-tamper) function programming 22 ……………………………………………………………………………………………………………………………………………
Control unit tamper 22 …………………………………………………………………………………………………………………………………………………………………
Keypad tamper 23 ………………………………………………………………………………………………………………………………………………………………………
Input expansion tamper 23 ……………………………………………………………………………………………………………………………………………………………
Output expansion tamper 23 …………………………………………………………………………………………………………………………………………………………
Masking function programming 23 …………………………………………………………………………………………………………………………………………………………
Zone test function programming 24 …………………………………………………………………………………………………………………………………………………………
Radio option programming 25 ………………………………………………………………………………………………………………………………………………………………
Transmitter programming 26 …………………………………………………………………………………………………………………………………………………………………
2
By-alarm
Index
Output Programming
Relay 1 programming 29 ……………………………………………………………………………………………………………………………………………………………………
Relay 2 programming 31 ……………………………………………………………………………………………………………………………………………………………………
Output programming 31 ……………………………………………………………………………………………………………………………………………………………………
ID Programming
Installer Code programming and functions 35 ……………………………………………………………………………………………………………………………………………
Codes 35 …………………………………………………………………………………………………………………………………………………………………………………
User Code programming and functions 35 …………………………………………………………………………………………………………………………………………………
Codes 35 …………………………………………………………………………………………………………………………………………………………………………………
If the code is active 36 …………………………………………………………………………………………………………………………………………………………………
Which area it is associated to 36 ………………………………………………………………………………………………………………………………………………………
Arming management 36 ………………………………………………………………………………………………………………………………………………………………
If arming in ON - INT - PAR 36 ……………………………………………………………………………………………………………………………………………………
If switching off 36 ……………………………………………………………………………………………………………………………………………………………………
If blocking the scheduler 36 ………………………………………………………………………………………………………………………………………………………
If enabling overtime 36 ……………………………………………………………………………………………………………………………………………………………
Auxiliary options 37 ……………………………………………………………………………………………………………………………………………………………………
If changing telephone number 37 …………………………………………………………………………………………………………………………………………………
If changing code 37 …………………………………………………………………………………………………………………………………………………………………
If changing date and time 37 ………………………………………………………………………………………………………………………………………………………
If blocking outgoing calls 37 ………………………………………………………………………………………………………………………………………………………
If accessing the control unit events memory 37 …………………………………………………………………………………………………………………………………
If blocking the keypad buzzer 37 …………………………………………………………………………………………………………………………………………………
If enabling user remote connection with voice call 37 …………………………………………………………………………………………………………………………
If enabled for user remote connection via MyWeb 37 ……………………………………………………………………………………………………………………………
If enabled for user remote connection with SMS 37 ……………………………………………………………………………………………………………………………
If excluding zones in the control unit 37 …………………………………………………………………………………………………………………………………………
If enabling macros 37 ………………………………………………………………………………………………………………………………………………………………
Access control system 38 ………………………………………………………………………………………………………………………………………………………………
If blocked by scheduler 38 …………………………………………………………………………………………………………………………………………………………
If sending a telephone call 38 ………………………………………………………………………………………………………………………………………………………
If cancelling a panic alert 38 ………………………………………………………………………………………………………………………………………………………
TAG Settings 38 …………………………………………………………………………………………………………………………………………………………………………
Acquisition - Delete - Check TAG 38 ………………………………………………………………………………………………………………………………………………
If the TAG is enabled 39 ……………………………………………………………………………………………………………………………………………………………
Which reader is associated to the ID 40 …………………………………………………………………………………………………………………………………………
Which output is active 40 ………………………………………………………………………………………………………………………………………………………………
Which output is active with Emergency Code 40 …………………………………………………………………………………………………………………………………
Code duration in days 40 ………………………………………………………………………………………………………………………………………………………………
Time Programming
Entry and exit times of delayed zones 41 …………………………………………………………………………………………………………………………………………………
Buzzer duration in case of alarm 41 …………………………………………………………………………………………………………………………………………………………
Zone unbalancing acquisition time 41 ………………………………………………………………………………………………………………………………………………………
Warning time for arming from scheduler 41 ………………………………………………………………………………………………………………………………………………
Warning cancellation timing 41 ………………………………………………………………………………………………………………………………………………………………
Control Programming
Arming function programming 42 ……………………………………………………………………………………………………………………………………………………………
If the installer ID is active with the control unit on 42 ………………………………………………………………………………………………………………………………
If self-test is active when arming the control unit 42 …………………………………………………………………………………………………………………………………
If forced arming is active 42 ……………………………………………………………………………………………………………………………………………………………
If fast arming is active 42 ………………………………………………………………………………………………………………………………………………………………
If fast disarming is active 43 ……………………………………………………………………………………………………………………………………………………………
If constant area vision is active on the keypad 43 ……………………………………………………………………………………………………………………………………
If the shared zone function is active 43 ………………………………………………………………………………………………………………………………………………
If the tamper exclusion function is active with OFF ZONE 43 ………………………………………………………………………………………………………………………
3
By-alarm
Index
Programming functions on power supplies 43 ……………………………………………………………………………………………………………………………………………
No mains voltage delay 43 ……………………………………………………………………………………………………………………………………………………………
Hour, minute and interval of the self-test call 43 ………………………………………………………………………………………………………………………………………
Day and month of system maintenance indication 43 ………………………………………………………………………………………………………………………………
Text Programming 43 ………………………………………………………………………………………………………………………………………………………………………
Info Text 43 ………………………………………………………………………………………………………………………………………………………………………………
Zone Texts 44 ……………………………………………………………………………………………………………………………………………………………………………
ID Texts 44 ………………………………………………………………………………………………………………………………………………………………………………
Output Texts 43 …………………………………………………………………………………………………………………………………………………………………………
Keypad texts 45 …………………………………………………………………………………………………………………………………………………………………………
Input expansion texts 45 ………………………………………………………………………………………………………………………………………………………………
Reader texts 46 …………………………………………………………………………………………………………………………………………………………………………
Output expansion texts 46 ……………………………………………………………………………………………………………………………………………………………
Area Texts 47 ……………………………………………………………………………………………………………………………………………………………………………
Macro Texts 47 …………………………………………………………………………………………………………………………………………………………………………
Network card address programming 48 ……………………………………………………………………………………………………………………………………………………
TCP IP address 48 ………………………………………………………………………………………………………………………………………………………………………
Netmask……………………………………………………………………………………………………………………………………………………………………………… 49
Gateway 49 ………………………………………………………………………………………………………………………………………………………………………………
TCP port 49 ……………………………………………………………………………………………………………………………………………………………………………
LAN code 49 ……………………………………………………………………………………………………………………………………………………………………………
Macro programming 50 ………………………………………………………………………………………………………………………………………………………………………
Setting the triggering event 50 …………………………………………………………………………………………………………………………………………………………
Setting the type of triggering event 50 …………………………………………………………………………………………………………………………………………………
Setting the stop macro event 50 ………………………………………………………………………………………………………………………………………………………
Setting the stop macro type 50 ………………………………………………………………………………………………………………………………………………………
If the macro is stopped by the scheduler 52 …………………………………………………………………………………………………………………………………………
If the macro must have automatic restart 52 …………………………………………………………………………………………………………………………………………
Settable delay in seconds/minutes 53 …………………………………………………………………………………………………………………………………………………
Memo macro activation in events memory 53 ………………………………………………………………………………………………………………………………………
Macro operation programming 53 ……………………………………………………………………………………………………………………………………………………
Operation 1 - 10 command 53 ……………………………………………………………………………………………………………………………………………………
Operation 1 - 10 Options 53 ………………………………………………………………………………………………………………………………………………………
Events memory view 54 ……………………………………………………………………………………………………………………………………………………………………
Software Version 54 …………………………………………………………………………………………………………………………………………………………………………
Restoring the control unit programming to default values 54 ……………………………………………………………………………………………………………………………
Access control system 54 ……………………………………………………………………………………………………………………………………………………………………
If the reader leds must always be on 55 ………………………………………………………………………………………………………………………………………………
Scheduler
Time band programming 56 …………………………………………………………………………………………………………………………………………………………………
Monday - Sunday 56 ……………………………………………………………………………………………………………………………………………………………………
Operation 1 - 16 56 …………………………………………………………………………………………………………………………………………………………………
Hour - Minute 56 ……………………………………………………………………………………………………………………………………………………………………
Function type 56 ……………………………………………………………………………………………………………………………………………………………………
Auxiliary options 56 …………………………………………………………………………………………………………………………………………………………………
Holiday period programming 57 ……………………………………………………………………………………………………………………………………………………………
Holiday period start and end programming 57 ……………………………………………………………………………………………………………………………………
Telephone
Phone number programming 58 ……………………………………………………………………………………………………………………………………………………………
Numbers 58 ……………………………………………………………………………………………………………………………………………………………………………
Send protocol 58 ………………………………………………………………………………………………………………………………………………………………………
Customer Code 58 ……………………………………………………………………………………………………………………………………………………………………
Zone alarm 59 ……………………………………………………………………………………………………………………………………………………………………………
Zone restoring 59 ………………………………………………………………………………………………………………………………………………………………………
Call not OK attempts 59 ………………………………………………………………………………………………………………………………………………………………
Stop call 59 ………………………………………………………………………………………………………………………………………………………………………………
4
By-alarm
Index
Telephone parameter programming 60 ……………………………………………………………………………………………………………………………………………………
Wait for answer 60 ………………………………………………………………………………………………………………………………………………………………………
Pause between attempts 60 ……………………………………………………………………………………………………………………………………………………………
Vocal message repetition 60 ……………………………………………………………………………………………………………………………………………………………
Number of rings on PSTN for connection in Remote connection 60 ……………………………………………………………………………………………………………
Number of rings on GSM for connection in Remote connection 60 ………………………………………………………………………………………………………………
Skip voice mail settings 60 ……………………………………………………………………………………………………………………………………………………………
If the SIM is rechargeable 61 …………………………………………………………………………………………………………………………………………………………
If the number must be recognised 61 …………………………………………………………………………………………………………………………………………………
Ring Back activation 61 …………………………………………………………………………………………………………………………………………………………………
Events to be associated to telephone numbers 61 ……………………………………………………………………………………………………………………………………
Tamper alarm………………………………………………………………………………………………………………………………………………………………………… 61
Sensor masking alarm 61 ………………………………………………………………………………………………………………………………………………………………
Bypassed zone 61 ………………………………………………………………………………………………………………………………………………………………………
Area Arming - Disarming 61 ……………………………………………………………………………………………………………………………………………………………
No mains voltage 62 ……………………………………………………………………………………………………………………………………………………………………
No battery 62 ……………………………………………………………………………………………………………………………………………………………………………
Low battery 62 …………………………………………………………………………………………………………………………………………………………………………
Self-test 62 ………………………………………………………………………………………………………………………………………………………………………………
D.G Batch Events 62 ……………………………………………………………………………………………………………………………………………………………………
User ID Entry 62 …………………………………………………………………………………………………………………………………………………………………………
Emergency User ID Entry 62 ……………………………………………………………………………………………………………………………………………………………
Medical dispatch call 62 ………………………………………………………………………………………………………………………………………………………………
Panic dispatch call 62 …………………………………………………………………………………………………………………………………………………………………
Fire dispatch call 62 ……………………………………………………………………………………………………………………………………………………………………
SIM not charged 62 ……………………………………………………………………………………………………………………………………………………………………
SIM expiring 62 …………………………………………………………………………………………………………………………………………………………………………
Association to alarm type for each zone 63 ………………………………………………………………………………………………………………………………………………
Vocal message recording………………………………………………………………………………………………………………………………………………………………… 63
Address message recording for each area 63 ………………………………………………………………………………………………………………………………………
Personalised word recording 63 ………………………………………………………………………………………………………………………………………………………
Password programming for interactive connection 65 ……………………………………………………………………………………………………………………………………
Section 2 - Programming the control unit with By-Alarm Manager software
Procedure to enable settings with By-alarm Manager 69 ………………………………………………………………………………………………………………………………
System card 70 ……………………………………………………………………………………………………………………………………………………………………………
5
By-alarm
General information
All control unit functions can be programmed using a computer which has the software installed or using one of the keypads connected to the control unit.By-alarm Manager
The control unit has two RS 485 inputs for connection to the bus on devices such as keypads, input expansion modules, output expansion modules, radio interfaces and read-
ers.
The devices can be connected either to the RS485 bus or in parallel to the same conductors, respecting the codes on the terminals of the control unit and of the devices
themselves, namely:
• + with +
• - with -
• A with A
• B with B
For 12 Vdc power supply 0.50 mm
2 conductors must be used and for the A and B sensors, 0.22 mm2 conductors; the shield must be connected to the negative with regard
to the control unit.
20
A
D
E
B
CN10
1
10
RS 485/1
D
EA B
RS 485/2
The keypads have a special anti-tampering button which is activated when the container is opened and when the keypad is removed from the wall.
• The bridge on the side of the button closing causes the full exclusion of the keypad protection
Changing the keypad address.
1) Press and release the RESET push button (PB1) on the keypad card on the right-hand side near the microprocessor (see photo below).
2) Press the button for approx. 1 s.ENT
3) The display will show the physical address of the keypad.
4) Press the button to enter the menu.ENT
5) Using the and buttons, select the desired address.
6) Press twice to confirm the address and exit the menu.ESC
OTHER RS485 BUS DEVICES
Introduction
6
By-alarm
7
Section 1
Programming the control unit using the keypad 01705
8
By-alarm
Guidelines for programming the control unit using the keypad
Guidelines for programming the control unit using the keypad
1. With the power off, connect all devices (both those connected to the RS485 bus and those connected directly to the control unit).
2. The control unit is supplied pre-set to manage 6 zones as illustrated in chap. 3 of the installation manual.
If settings other than default are required, connect the 3k3 Ω resistors in the inputs for the unused devices in the control unit, and if the siren and relative tamper resistor have
not already been connected, connect the 3k3 Ω resistor directly between the terminals on the control unit.T T
N.B. When powering the system, if the resistors are not connected as described, the keypad will emit a tamper alarm and the procedure described in the control unit instal-
lation sheet must be followed (enter user ID to silence the alarm and enter installer ID to proceed with the settings).
3. Check that the jumpers required to exclude the control unit anti-tamper devices are present.
4. Power up the system.
5. Assign the relative ID address to each device connected to the RS485 bus (the assigning procedure can be done via the user interface or dip switch, as described in the
respective instruction sheets).
As illustrated in the installation manual, the ID assignment must always be sequential, starting with ID=1 for the first device, ID=2 for the second and so on for all devices of the
same category connected to the bus; two devices in the same category must always have different IDs (the radio frequency interfaces 01729 and input expansion modules
01709 and 01704 are devices in the same category and must therefore have a different ID while, for example, an input expansion module 01709, a reader 20478-19478-
14478 and an output expansion module 01710 may all have the same ID). If there is more than one keypad, select the one to be used for the settings, which will be assigned
ID=1; assign to the other keypads respectively ID=2, 3, etc.
6. Run the control unit self-learning procedure. This procedure can be done in two different ways (one alternative to the other):
Method 1 (from the control unit)
• Set dip switch 2 to and press the reset push button for at least 1 s.ON PB1
• Once the control unit relays have completed a rapid switching sequence, place dip switch 2 to and press the push button again.OFF PB1
The LED status of the device will indicate the correct outcome of the procedure (where present); for example, for radio frequency interface 01729:
- LED = BUS connection problem.xed on
- LED = device not programmed.ashing 1 s ON and 1 s OFF
- LED = device programmed.ashing briey every second
If the system has one or more radio frequency interfaces 01729 by default these are defined by the control unit as 8-channel interfaces; if you wish to use more than 8 chan-
nels you must eliminate the interface and associate the respective ID to the menu. RADIO 8 RADIO 16
Mode 2 (from keypad)
Enter the Installer ID in the keypad chosen for the settings (default code ), and call up the menu and for each device (reader, keypad, 123456 SETTINGS PROG. BUS 1 or 2
etc.) specify how many are installed in the system, also indicating the respective ID.
For example, if there is an input expansion module with ID=1 and a radio frequency interface with ID=2 which has to manage 8 channels, proceed as follows:
- in the screen INP. EXP. 1-8 enter 1 and 2 to declare that the expansion modules on the bus (wired or radio) with ID 1 and 2.
- in the screen enter 2 to declare that the module with ID=2 is a radio frequency interface with 8 inputs.RADIO 8 (1-8)
Note: having received its own ID, the input expansion module 01709 automatically occupies 4 zones in the system however many devices will actually be connected and,
in the same way, the radio frequency interface will also occupy 8 or 16 according to what defined in the specific menu. It is very important to remember which zones are
occupied by the associated devices as, in the subsequent settings phases, it must be clear which one belongs to every device connected to the input expansion modules or
remote control interfaces; this must be compared with the maximum number of free zones available on the control unit in order to avoid associating additional devices which
will not trigger any alarm as they are not managed.
7. Following the instructions given in the radio frequency device instruction sheet, set the relative parameters (use of auxiliary inputs, radio range, etc.)
8. As described in the instructions for interface 01729 and other radio frequency devices, enter the settings paying attention to the fact that a device associated to the manage-
ment of auxiliary inputs on separate channels will occupy two or three zones: one for the device and one for each auxiliary input. For tidy programming, note the settings
considering that the first radio frequency device programmed will occupy the first zone associated to the interface 01729 and which, if its auxiliary input is programmed im-
mediately afterwards, it will be associated to the subsequent alarm zone and so on.
Note: In the default settings, all the information on the reed/pyroelectric parameters and auxiliary inputs are managed on a single channel; with this setting, information on the
unbalanced zone will be sent to interface 01729 if one of the inputs on the radio frequency device is "unbalanced".
By appropriately programming detectors 01727 and 01728 it is possible to assign a separate radio channel to each input (programming done on the device); in this
case, it is also necessary to correctly associate the radio channels with separate zones to the interface 01729 (for example three radio channels on the detector 01727
are associated to three different zones).
9. SETTINGS-INPUTS-ZONE.PROG.Define the behaviour of the various zones in the menu ) associating them to the required areas and (value=50 indicates a disabled zone
setting their functions (delays, etc.).
10. Define the Areas.
11. ON INT For each Area, define the associated zones belonging to the entry methods , and PAR.
12. Define the behaviour of Relay 1 to which the sirens are connected and that concerning any use of Relay 2.
13. Creation of user IDs and definition of the Areas and functions which can be associated to each code.
By default, user 1 is active on Area 1 with basic permissions (user ID ); the following procedure is used to create other users:111111
- enable the user;
- set the numerical code (which must be different from the default code);
- enter the user settings (assignment of permissions, etc.);
- associate a transponder key to the user if required.
14. Programme the transponder keys and radio frequency remote controls.
9
By-alarm
Guidelines for programming the control unit using the keypad
15. Associate the Areas and required functions to the transponder key and the remote control push buttons.
Notes:
• Each transponder key can be associated to a single user and therefore the relative permissions correspond to the user permissions. The procedure is as follows:
- acquire the tag (then associated to a specific user);
- indicate the settings for the reader on which the tag is enabled in the specific menu.
• As concerns the remote controls, simply associate the required function and entry area to each button.
16. Associate any keypad alarm signal (buzzer) to the required zones; it is possible to define the zones for which, in the event of an alarm, the keypad gives off an acoustic signal,
also setting the duration.
17. In outdoor sirens, set the acoustic signal duration in the event of an alarm (these are armed/disarmed by Relay 1 but in particular situations like a control unit failure or total
blackout of the system with flat batteries they can in turn ring for a set time).
18. Where present, programme the GSM transmitter/receiver module 01706 and the voice expansion module 01713 (if present). In practice the GSM transmitter/receiver mod-
ule must be armed, the phone numbers entered, the user permissions correctly paired and all programming required to manage the telephone part in the desired manner
completed (SMS or voice).
19. If present, programme the voice synthesis module 01713 and record any vocal messages.
20. Having completed the programming, check the connections on the detectors connected to the control unit inputs, restore the anti-tamper devices via the jumpers, check
the siren connections and finally check the balancing on the sirens and devices with any resistors for double or triple balancing.
21. The new “map” of the bus devices can be downloaded to the PC using the By-alarm Manager software; before importing, enable the connection to the PC via the keypad:
- select the e menu and press .Settings ENT
- scroll through the menu as far as and press .PC <--> Control unit ENT
- press to view .CLR YES
- press to exit the menu.ESC
Finally, from the PC, run Connect -> Receive Programming and the programmed bus devices will be viewed in the specific menus.
Note: When programming with the By-alarm Manager software downloaded to the control unit, from the keypad you can view the features of the whole system (devices on
the bus, zone settings, association to areas, etc.).
10
By-alarm
Primary Menu diagram
Primary Menu diagram
All control unit functions are programmed in 9 primary menus identifying as many function categories.
The first control unit programming is done via the keypad which is assigned ID=1; therefore, if more than one keypad is installed in the system, the code allowing access
to the programming must be entered on the keypad with ID=1.
• The control unit is programmed by entering the Installer code on the keypad; by default this is .123456
Menu navigation
• Use the navigation buttons , , and to surf through the Programming Menus:ESC ON INT PAR
• The button confirms the data, (clear) cancels it and is used to exit the menu.ENT CLR ESC
Installer ID
• The default code is programmed with the value: 123456
Installer ID
 
Settings
• System composition - page 9
 
Clock settings
• Setting the date and time - page 11
 
Inputs
• Input programming - page 12
 
Outputs
• Output programming - page 28
 
Codes
• Activation code programming - page 34
 
Times
• Time programming - page 40
 
Controls
• Additional parameter programming - page 42
 
Scheduler
• Scheduler functions - page 56
 
Telephone
• Telephone connection functions - page 58
 
System test
• System diagnostics function - page 65
12
By-alarm
1.1.9 Output expansion modules 01710 (from 1 to 8) installed.
Press number 1-2-3-4-5-6-7-8 for the installed expansions; the indicator will come on to confirm the correct program-
ming. To deselect the module repeat the same operation.
1.1.10 Output expansion modules 01710 (from 9 to 16) installed.
Press number 1-2-3-4-5-6 for the installed expansions; the indicator will come on to confirm the correct programming.
To deselect the module repeat the same operation.
1.1.11 Readers 20478-19478-14478 installed.
Write the number 1-2-3-4-5-6-7-8for the readers installed; the indicator will come on to confirm the correct program-
ming. To deselect the reader repeat the same operation.
- The reader is identified with the address given (see indications given in the control unit or reader installation manual).
to go back As there are no more parameters to be programmed, press to return to the previous level of the RS 485 BUS ESC|
programming menu.
 
menu press the down arrow From the PAR| to access the programming procedures for the other control unit devices.
1.2 Select if the YES circuit in the control unit for connecting to the PSTN analogue phone line must be enabled.
• Press to edit the settings.CLR
1.3 Select the GSM company interface 01706 to be enabled (set the number of GSM modules present).
• Press to edit the settings.CLR
• Programme the telephone company of the SIM inserted in the GSM module.
• Write the company number directly, consulting the table below:
Prog. Function type Phone company
0 NO GSM No company selected.
1 TIM TIM mobile phone company.
2 VODAFONE VODAFONE mobile phone company.
3 WIND WIND mobile phone company.
1.4 Select if you wish to do the programming from the keypad NO
• Press to change the settings.CLR
Select YES if you want a direct connection between a .
• Press to edit the settings.CLR
- The connection between the PC and the control unit must be done via the interface art. 01725.
- For interactive connection between the control units and the PC install and programme the software.By-alarm Manager
- For the installation and recording procedures, follow the indications given in the By-alarm Manager software manual.
Select NO if you wish to do the programming from the keypad
• Press to edit the settings.CLR
1.5 Select if you do not want the system to comply with the indicated standard.NO
to go back As there are no more parameters to be programmed, press to return to the previous level of the Settings menu.ESC|
 
From the menu use the down arrow PAR| to go to the control unit clock settings menu.
Programming the control unit devices
13
By-alarm
2. Internal clock settings
 
2. In you can programme the time and date of the control unit clock.
• From the menu press to enter the settings.ENT
2.1 Setting the current .
• Enter the time directly.
2.2 Setting the current .
Enter the minutes directly.
2.3 Setting the current .
Enter the day directly.
2.4 Setting the current .
Enter the month directly.
2.5 Setting the current .
Enter the year directly.
to go back As there are no more parameters to be programmed, press to return to the previous level of the Clock Settings menu.ESC|
 
From the menu use the down arrow PAR| to view the control unit inputs programming menu.
Clock settings
14
By-alarm
3. Input programming
 
3. In set all the control unit input parameters.
• From the menu press to enter the first zone programming menu.ENT
 
3.1 From the menu press to enter the programming modes for each zone.ENT
3.1.1 Select the to be programmed.
• Write the number of the zone to be programmed.
3.1.2 Select the associating it to the operating mode.
• Write the number of the required mode by consulting the table below.
Progr. Zone type Description
0Instantaneous With the control unit on, an alarm is generated as soon as the zone is unbalanced.
1Instantaneous with
automatic exclusion
If when entering the group the input is unbalanced, the zone is automatically excluded
and the event is stored in the events log.
It is re-included automatically when the control unit is turned off.
Note: if used the IMQ type-approval expires.
2 - 3 Timed 1 -2
When the control unit is turned on the exit time 1 - 2 is activated.
At the end of this time, a subsequent line unbalancing will enable the re-entry time 1 - 2.
At the end of the re-entry time, if the control unit is not turned off an alarm sequence is
enabled.
4Timed with automatic
exclusion/re-inclusion
The zone becomes active after a programmable “exit” time, allowing you to leave having
inserted the group; if at the end of this time the zone is unbalanced it is automatically
excluded. It will be re-included after the next re-balancing. The zone generates an alarm
after a programmable delay calculated from the time in which the entry is unbalanced;
during this delay it is possible to disconnect the group without generating alarms.
Note: if used the IMQ type-approval expires.
5Timed conditioned
instantaneous
Instantaneous line which is automatically excluded during the exit and re-entry time of a
timed line 1 or 2.
624 hours
Line always active, its unbalancing causes an alarm even if the control unit is turned off.
Note: to maintain IMQ type-approval: if this mode is used with the anti-theft function, the
zones must be associated to all phone numbers.
7Anti-Tampering
Additional anti-tampering line; cannot be excluded with "OFF ZONE" operation from
keypad and when unbalanced it causes an anti-tampering alarm even when the control
unit is turned off.
8 - 9 - 10 On
ON/INT/PAR
Remote ON line in mode ON, INT, PAR. When unbalanced it causes the control unit to
come on in one of the possible modes.
11 - 18 Suspension Area 1-8
19 Panic reset delayed If the zone is unbalanced, it cancels the anti-coercion procedure.
20 - 29 Start macro 1-10 If the zone is unbalanced, the associated macro is activated.
30 - 39 Stop macro 1-10 If the zone is unbalanced, the associated macro is locked.
40 - 49 Reset Macro 1 - 10 If the zone is unbalanced, the associated macro is reset.
50 Not used
51 Sensor fault If the zone is unbalanced a Sensor fault signal is generated (EN-50131).
52 Anti-theft device fault If the zone is unbalanced an Anti-theft device fault signal is generated (EN-50131).
53 Siren fault If the zone is unbalanced a Siren fault signal is generated (EN-50131). To be used in the
input to which the LV output of the siren 01715 is connected.
The area suspension is an operating mode which can be used to interrupt the scheduler cycle arming and disarming. After the
suspension the control unit goes to the state set in the programming for the current time band.
Important: Panic, theft, tampering events must be associated to at least the first phone number.
This guarantees that in the event of more than one event at the same time panic, theft and tampering are transmitted as a priority.
Input programming
15
By-alarm
This is the number of 3.1.3 required to trigger the control unit alarm.
• Write the number or required unbalancings.
Note: the pulse count only applies to the alarm signal and not to tampering and/or masking that are signalled with the
first pulse.
CAUTION: This function cannot be used to connect inert sensors or sensors for roll-up shutters at the inputs
from L1 to L8 of the control unit as these detect unbalancings with a time greater than 120 ms and which can-
not be calibrated.
This is the duration of a single unbalancing for it to be considered valid. 3.1.4
The acquisition times are shown in the following tables:
Prog. Description
01 ms
12 ms
2 5 ms
310 ms
420 ms
Prog. Description
540 ms
680 ms
7 120 ms
8160 ms
9200 ms
Prog. Description
10 600 ms
11 1 s
12 2 s
13 4 s
to go back
As there are no more parameters to be programmed, press to return to the previous level of the Zone Programming ESC|
menu.
 
From the
menu use the down arrow PAR| to go to the Area Settings menu.
 
3.2 In you programme all the settings for the possible control unit partitions.
• From the menu press to enter the first Zone Programming menu.ENT
 
3.2.1 Partition Area refers to the possibility to group zones to obtain different systems with a single control unit.
 
 
 
 
3.2.1.1 In you programme the zones associated to the arming in mode.ON
• Press to enter the settings.ENT
3.2.1.1.1 Select which zone will be when the Area is armed in mode.ON
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to confirm the association.
• To remove the association write the required number.
From the to the menu press to enter the Programming menu for the 8 possible areas.ENT
- The control unit has 8 Areas and for each one must be programmed or associated to the required functions. If you do
not need to use more than one area, simply do not associate any function to the areas from 2 to 8.
- The arming methods are used to customise the safety system operation; the control unit 01703 has 3 arming modes
which are identified with as many push buttons on the keypad: (total arming), (internal arming) and (par-ON INT PAR
tialised arming). Every area can therefore be independently placed in armed state using one of the 3 different modes
at a time.
- If the same zone is associated to 2 or more different areas for the same arming mode, a shared zone is obtained; the
shared zone will be active only when all the associated areas are in the ON state; this automation makes program-
ming easier when there are several systems with a shared entrance. Obviously, there may be more than one shared
zone.
Input programming
16
By-alarm
to go back As there are no more parameters to be programmed, press to return to the menu.ESC|Active in ON
 
From
use the down arrow PAR| INTernal to go to the Zone Activation Menu in .
 
3.2.1.2 In you programme the zones associated to the arming in mode.ON
• Press to enter the settings.ENT
3.2.1.2.1 Select which zone will be when the Area is armed in mode.INT
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to confirm the association.
• To remove the association write the required number.
to go back As there are no more parameters to be programmed, press to return to the menu.ESC|Active in INT
 
From
use the down arrow PAR| to go to the Zone Activation menu in PARtialised
 
3.2.1.3 In you programme the zones associated to arming in mode.PAR
• Press to enter the settings.ENT
3.2.1.3.1 Select which zone will be when the Area will be armed in mode.PAR
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to confirm the association.
• To remove the association write the required number.
As there are no more parameters to be programmed, press to return to the to go back ESC|Active in PAR menu.
 
From
use the down arrow PAR| to go to the Keypad Association menu.
 
3.2.1.4 In programme the association between the chosen Area and the installed keypads.
• Press to enter the settings.ENT
3.2.1.4.1 Select which will be associated to the chosen Area.
• Write the number for the keypads to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to confirm the association.
• To remove the association write the required number.
to go back As there are no more parameters to be programmed, press to return to the Keypads menu.ESC|
Input programming
18
By-alarm
Reset memory
ENT
3.3.2 In
reset memo
make the events memory record the alarm reset.
• Press to enter the settings.ENT
Zones 1 - 8
————————
3.3.2.1 Select which zone must
record the alarm reset
in the control unit events memory.
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
Events Memory: the control unit has a memory used to record all the fault, arming and disarming events with date
and time, the codes entered and alarm and zone reset states, if the function described above is
selected in programming; there are 500 recorded events which are automatically updated, deleting
the oldest ones.
the events in the memory can be consulted directly by the user and will be shown on the control
keypad in the following form:
to go back As there are no more parameters to be programmed, press to return to the Memo Alarm Reset menu.ESC|
Reset memory
 ENT
From
memo reset
use the down arrow PAR| to view the Buzzer Activation menu.
activate buzzer
ENT
3.3.3 In
buzzer active
you programme which of the programmed zones will activate the keypad buzzer in the event of an alarm.
To set the buzzer length see chap. 6 of this manual.
• Press to enter the settings.ENT
Zones 1 - 8
————————
3.3.3.1 Select which zone must
activate the buzzer
on the keypad in the event of an alarm.
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
to go back As there are no more parameters to be programmed, press to return to the Keypad buzzer activation menu.ESC|
activate buzzer
ENT
From
buzzer active
use the down arrow PAR| to view the Double Balancing menu.
double eol
ENT
3.3.4 In
double eol
you programme the zones with double balancing.
• Press to enter the settings.ENT
Zones 1 - 8
————————
3.3.4.1 Select which zone must be programmed for
double balancing
.
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
The zones not associated to double balancing will automatically be programmed for single balancing.
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
As there are no more parameters to be programmed, press to return to the Double Balancing menuto go back ESC|
Input programming
19
By-alarm
double eol
ENT
From
double eol
use the down arrow PAR| to view the Triple Balancing menu.
triple eol
ENT
3.3.5 In
triple eol
you programme the zones with triple balancing.
• Press to enter the settings.ENT
Zones 1 - 8
————————
3.3.5.1 Select which zone must be programmed for
triple balancing
.
• Write the number for the zones to be associated.1-2-3-4-5-6-7-8
To be associated to triple balancing, the zones must also be associated to double balancing.
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
As there are no more parameters to be programmed, press to return to the Triple Balancing menu.to go back ESC|
triple eol
ENT
From
triple eol
use the down arrow PAR| to view the Alarm Coding menu.
Alarm coding
3 (max. 10)
3.3.6 In
alarm coding
with a number greater than zero, you enable the multiple alarm control function.
Write the number of alarms required to activate the Alarm Coding function.
- After the programmed number of alarms in the same zone, the alarm relay will no longer be activated, the events
memory records the zone bypassed and the sum of the events and a single phone call will be made notifying the
zone bypassed.
- The counter reset and re-inclusion of the zone will occur when disarming the control unit or if an alarm is triggered in
another zone.
- All zones programmed with and functions are excluded automatically from the alarm coding.24 hour type tamper
- Enter zero to completely disable the function.
to go back As there are no more parameters to be programmed, press to return to the Alarm Options menu.ESC|
Alarm options
ENT
From
alarm options
use the down arrow PAR| to go to the Auxiliary Options menu.
Auxiliary options
ENT
3.4 In
Auxiliary options
you programme the auxiliary parameters for the zones.
• From the
auxiliary options
menu press to enter the settings.ENT
Buzzer in
ENT
3.4.1 In
buzzer in
you programme which zones programmed with timer must make the keypad buzzer ring.
• From the
buzzer in
press to enter the settings.ENT
Input programming
20
By-alarm
Zones 1 - 8
————————
3.4.1.1 Which zone must activate the
buzzer in
on the keypads to indicate the entry time of a timed zone.
For each zone group, write the number 1-2-3-4-5-6-7-8 for the input lines that must activate the buzzer.
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
- The function can be left active for all zones as only the timed zones will make the keypad buzzer ring.
to go back As there are no more parameters to be programmed, press to return to the Buzzer IN menu.ESC|
Buzzer in
ENT
From the
buzzer in
menu use the down arrow PAR| to view the Buzzer OUT menu.
Buzzer out
ENT
3.4.2 In
buzzer out
you programme which zones programmed with timer must make the keypad buzzer ring.
• From the
buzzer out
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.2.1 Which zone must activate the
buzzer out
on the keypads to indicate the exit time of a timed zone.
For each zone group, write the number for the input lines that must activate the buzzer.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
- The function can be left active for all zones as only the timed zones will make the keypad buzzer ring.
to go back As there are no more parameters to be programmed, press to return to the Buzzer OUT menu.ESC|
Buzzer out
ENT
From the
buzzer out
menu use the down arrow PAR| to go to the Chime menu.
The
chime
is a function that makes the keypad buzzer ring when, with the system disarmed, the zone is unbalanced. The sound is
continuous and you must enter a User ID to silence it.
chime
ENT
3.4.3 In
chime
you programme which zones will activate the Chime function.
• From the
chime
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.3.1 The
chime
is a function that makes the keypad buzzer ring when, with the system disarmed, the zone is
unbalanced.
The sound is continuous and you must enter a User ID to silence it.
For each zone group, write the number for the input lines that must activate the buzzer.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
To remove the association write the required number.
Zones 57 - 64
————————
As there are no more parameters to be programmed, press to return to the Chime menu level. to go back ESC|
chime
ENT
From the
chime
use the down arrow PAR| to go to the Door menu.
door
ENT
3.4.4 In
door
you programme which zones activate the Chime function.
• From the
door
menu press to enter the settings.ENT
Input programming
21
By-alarm
Zones 1 - 8
————————
3.4.4.1 The
door
is a function that makes the keypad buzzer ring when, with the system disarmed, the zone is
unbalanced.
The sound is continuous and you must enter a User ID to silence it.
For each zone group, write the number for the input lines that must activate the buzzer.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
To remove the association write the required number.
Zones 57 - 64
————————
to go back As there are no more parameters to be programmed, press to return to the Door menu level.ESC|
door
ENT
From the
door
use the down arrow PAR| to view the Ding Dong menu.
Ding dong
ENT
3.4.5 In
door
you programme which zones activate the Chime function.
• From the
door
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.5.1 The
Ding Dong
is a function that makes the keypad buzzer ring for two seconds when, with the system
disarmed, the zone is unbalanced.
The sound will be automatically interrupted even if the zone stays unbalanced.
For each zone group, write the number for the input lines that must activate the buzzer.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
To remove the association write the required number.
Zones 57 - 64
————————
As there are no more parameters to be programmed, press to return to the Ding Dong menu. to go back ESC|
Ding dong
ENT
From the
ding dong
use the down arrow PAR| to view the Zone not Bypassable menu.
Zone not bypassable
ENT
3.4.6 In
Zone not Bypassable
you programme the zones that cannot be bypassed.
• From the
Zone not Bypassable
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.6.1 By selecting the
Zone not Bypassable
the zone can never be bypassed, even by the User.
For each zone group, write the number for the input lines which cannot be bypassed.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
- The zones programmed in Tamper mode can in any case never be bypassed.
to go back As there are no more parameters to be programmed, press to return to the Zone not Bypassable level.ESC|
Zone not bypassable
ENT
From the
Zone not Bypassable
use the down arrow PAR| to view the Zones programmed for pre-alarm menu
Input programming
22
By-alarm
pre-alarm
ENT
3.4.7 In
pre-alarm
you programme the zones with Coercion function.
• From the
pre-alarm
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.7.1 The unbalancing of the zone associated to the
PRE-ALARM
function triggers a silent alarm which consequently
sends programmed telephone calls.
For each zone group, write the number for the input lines that must activate the phone calls.1-2-3-4-5-6-7-8
The symbol will come on to conrm the association.
• To remove the association write the required number.
- The coercion zone may be any line in the control unit whatever mode it is programmed in.
Zones 57 - 64
————————
- The Coercion procedure can only be stopped by unbalancing a zone programmed with the Delayed Panic
Reset function.
As there are no more parameters to be programmed, press to return to the Coercion Menu level. to go back ESC|
PRE-ALARM
ENT
From the
PRE-ALARM
use the down arrow PAR| to view the Menu of the Zones programmed as .Final Door
Final Door
ENT
3.4.8 In
final door
you programme the zones to be considered as the last exit. In practice it is a zone that interrupts the
timer (exit time) when it is balanced again (this application is useful for entrance doors, doors onto corridors, etc.).
• From the
final door
menu press to enter the settings.ENT
Zones 1 - 8
————————
3.4.8.1 The zone associated to the
final door
function immediately stops the exist time of a timed line when this is
re-balanced.
For all zones, write the number for the input lines considered “last exit”.1-2-3-4-5-6-7-8
The symbol will come on to conrm the association.
• To remove the association write the required number.
- The function must necessarily be associated to a zone programmed in Timed mode (see page 5).
Zones 57 - 64
————————
- This is a typical function for an entrance door when it is closed after having switched the system on, it im-
mediately stops the exit time.
As there are no more parameters to be programmed, press to return to the Final Door menu level. to go back ESC|
Final Door
ENT
As there are no more parameters to be programmed, press to return to the Auxiliary Options menu level.to go back ESC|
Auxiliary options
ENT
From
auxiliary options
use the down arrow PAR| Anti-tamper settings menu.
Tamper
ENT
3.5 By
Tamper
we refer to all anti-tamper functions of the system of any kind, although they all follow the same programmed
procedure.
• From each
Tamper
menu press to enter the settings.ENT
Control unit tamper
ENT
Tamper control unit
: there are two types, but both are identied in the same way.
Dedicated control unit anti-tamper line; in the terminal block, identied by codes TT.
Buttons protecting the control unit container from being opened or pulled off the wall.
Input programming
23
By-alarm
Keypad tamper
ENT
Keypad Tamper
: this is the anti-tamper function protecting the keypad from being opened or pulled off the wall, or having
the connecting cables cut.
INP. EXP. Tamper
ENT
INPUT EXP. Tamper
: is the anti-tamper device coming from the tamper input and input expansion module 01709 communica-
tion input.
OUT. EXP. Tamper
ENT
Out. Exp. Tamper
: is the anti-tamper device coming from the tamper input and output expansion module 01710 communi-
cation input.
Activate relay 1
YES
3.5.1 A enables theYES
activation of relay 1
general alarm.
Press CLR to change the settings
Activate relay 2
YES
3.5.2 A enables theYES
activation of relay 2
.
Press CLR to change the settings.
- The use of this condition:
Relay 2 active NO
annuls the IMQ type-approval.
Activate buzzer
YES
3.5.3 A enables theYES
activation of the keypad
buzzer.
Press CLR to change the settings.
Alarm memory
YES
3.5.4 A programmes the control unit toYES
record the alarm
in the control unit events memory.
Press CLR to change the settings.
Reset memory
NO
3.5.5 A programmes the control unit toYES
record the alarm reset
in the control unit events memory.
Press CLR to change the settings.
As there are no more parameters to be programmed, press to return to the Tamper menu level.to go back ESC|
Tamper
ENT
From
tamper
use the down arrow PAR| to go to the Masking settings menu.
masking
ENT
3.6 In
masking
the control unit is programmed for detecting a masking state alarm in the sensors (see Triple Balancing).
• From the
masking
menu press to enter the rst associated function.ENT
Activate relay 1
YES
3.6.1 A enables theYES
activation of relay 1
general alarm.
Press CLR to change the settings.
Activate relay 2
YES
3.6.2 A enables theYES
activation of relay 2
.
Press CLR to change the settings.
Activate buzzer
YES
3.6.3 A enables theYES
activation of the
keypad buzzer.
Press CLR to change the settings.
Alarm memory
YES
3.6.4 A programmes the control unit to YES
record the alarm
in the control unit events memory.
Press CLR to change the settings.
Input programming
25
By-alarm
Activate buzzer
YES
3.7.5 Programming a , an alarm state caused by the zone to which the test function is associated will not cause theNO
acti-
vation of the buzzer
.
Press CLR to change the settings.
Telephone com.
YES
3.7.6 Programming a , an alarm state caused by the zone to which the test function was associated will not activate theNO
phone communications
.
Press CLR to change the settings.
Duration of zone test
0 (0÷ 255)
3.7.7 In
zone test duration
you set the test duration in days.
Write the number of days of the zone test period directly.
- The test period starts from the time you exit the programming.
- After the test period, the zones return to programmed operation, ignoring the test settings.
- Important: - The test settings remain programmed in the control unit, even if the test period has expired, and in fact
do not condition the control unit operation in any way.
- If however you enter or exit the programming, even without editing any of the settings, the zone test
period will be represented.
- This is to be able to activate the function from Installer Remote Phone Connection; in this way the
sensors can be controlled from critical calibration and in difcult environmental positions, putting the
device in test mode without having to go directly on site.
- With a value of 0 the zones are constantly being tested and their operation depends on the test
congurations.
to go back As there are no more parameters to be programmed, press to return to the Zone Test menu level.ESC|
Zone test
ENT
From the
zone test
menu use the down arrow PAR| to view the Radio Options menu.
radio options
ENT
3.8 In
radio options
you programme the functions associated to the module 01729.
supervision
ENT
3.8.1 The
supervision
is the control the radio receiver has over the receivers; if it does not read a survival signal the pro-
grammed functions are activated.
Activate relay 1
YES
3.8.1.1 A enables theYES
activation of relay 1
general alarm.
Press CLR to change the settings.
Activate relay 2
YES
3.8.1.2 A enables theYES
activation of relay 2
.
Press CLR to change the settings.
Activate buzzer
YES
3.8.1.3 A enables theYES
activation of the
keypad buzzer.
Press CLR to change the settings.
alarm memory
YES
3.8.1.4 A programmes the control unit to YES
record the alarm
in the control unit events memory.
Press CLR to change the settings.
restore memory
YES
3.8.1.5 A programmes the control unit toYES
record the alarm reset
in the control unit events memory.
Press CLR to change the settings.
to go back As there are no more parameters to be programmed, press to return to the Supervision menu.ESC|
Input programming
26
By-alarm
supervision
ENT
From the
supervision
menu use the down arrow PAR| to go to the Radio Device Battery management menu.
BATT. LOW RF
ENT
3.8.2 I n
BATT. LOW RF
programmes the functions associated to the radio frequency detector 01727 and 01728 at battery
signal.
Activate relay 1
YES
3.8.2.1 A enables theYES
activation of relay 1
general alarm.
Press CLR to change the settings.
Activate relay 2
YES
3.8.2.2 A enables theYES
activation of relay 2
.
Press CLR to change the settings.
Activate buzzer
YES
3.8.2.3 A enables theYES
activation of the
keypad buzzer.
Press CLR to change the settings.
Memo alarm
YES
3.8.2.4 A programmes the control unit to YES
record the alarm
in the control unit events memory. This is used to
view even the detail of the zone the device belongs to.
Press CLR to change the settings.
store reset
YES
3.8.2.5 A programmes the control unit toYES
record the alarm reset
in the control unit events memory.
Press CLR to change the settings.
As there are no more parameters to congure, press to return to the radio device battery managing menu.to go back ESC|
transmitter battery
ENT
From the
transmitter battery
menu use the down arrow PAR| to go to the Transmitters management menu.
transmitters
ENT
3.8.3 In
transmitters
you programme the functions associated to the 4 push buttons on the 8 possible Transmitters.
transmitters 1
(max 8)
3.8.3.1 For the
transmitters 1
you programme the function associated to the 4 push buttons on the 8 possible
Transmitters.
Enter the number of the transmitter for which you wish to associate the various functions to the respective push buttons
(from 1 to 8).
Input programming
27
By-alarm
push button 1
ENT
3.8.3.1.1 For
button 1
,
button 2, button 3
and
button 4
you have to associate the type of func-
tion which must be completed with auxiliary data; having selected the required button (1-4) press
ENT Type Auxiliaries to view the options and which have the following functions:
push button 4
ENT
type
O ( max. 20)
auxiliaries
O ( max. 50)
As there are no more parameters to be programmed, press to return to the Buttons menu level. to go back ESC|
push button 1
ENT
Select the other buttons and repeat the procedure illustrated in 3.8.3.1.1.
to go back As there are no more parameters to be programmed, press to return to the Transmitters Menu level.ESC|
transmitters
ENT
RADIO OPTIONS
ENT
JAMMING GSM
ENT
Activate relay 1
YES
3.8.3.1.2 A enables theYES
activation of relay 1
general alarm.
Press CLR to change the settings.
Input programming
Progr. Options Function description
0 0 No function
1 1 - 8 Area ON mode on [1 - 8]
2 1 - 8 Area INTERNAL mode on [1 - 8]
3 1 - 8 Area PARTIALISED mode on [1 - 8]
4 1 - 8 Area off [1 - 8]
5 1 - 64 Exclude zone [1 - 64]
6 1 - 64 Re-include zone [1 - 64]
7 1 - 64 Activate output [1 - 64]
8 1 - 64 Deactivate output [1 - 64]
9 1 - 20 Start Macro [1 - 20]
10 1 - 20 Stop Macro [1 - 20]
11 1 - 20 Reset Macro [1 - 20]
12 1 - 20 Enable Macro [1 - 20]
13 1 - 20 Disable Macro [1 - 20]
14 1 - 50 Lock User Codes [1 - 50]
15 1 - 50 Release User Codes [1 - 50]
16 1 - 4 Keypad lock [1 - 4]
17 1 - 4 Keypad Release [1 - 4]
18 1-32 By-me command [1-32]
19 0 - 255 Entry of a Delay in minutes or seconds
28
By-alarm
Activate relay 2
YES
3.8.3.1.3 A enables theYES
activation of relay 2
.
Press CLR to change the settings.
Activate buzzer
YES
3.8.3.1.4 A enables theYES
activation of the
keypad buzzer.
Press CLR to change the settings.
Memo alarm
YES
3.8.3.1.5 A programmes the control unit to YES
record the alarm
in the control unit events memory.
Press CLR to change the settings.
store reset
YES
3.8.3.1.6 A programmes the control unit toYES
record the alarm reset
in the control unit events memory.
Press CLR to change the settings.
to go back As there are no more parameters to be programmed, press to return to the Transmitter Battery menu.ESC|
JAMMING GSM
ENT
to go back As there are no more parameters to be programmed, press to return the the Transmitter Battery menu.ESC|
Inputs
ENT
From the
Inputs
menu use the down arrow PAR| to view the Output Programming menu.
Input programming
29
By-alarm
4. Output Programming
Outputs
ENT
4. In
outputs
you programme all the control unit output settings.
• From the
outputs
menu press to enter the rst Output Programming menu.ENT
Relay 1
ENT
4.1
Relay 1
is the positive safety alarm output the sirens must be connected to.
• From the
relay 1
menu press to enter the rst Programming menu.ENT
Output RELAY 1
Positive safety relay, with double exchange, with 1A capacity each. A voltage free exchange is provided at the output where is the C
common, is the normally closed exchange and is the normally open one; the other one is provided already polarized for con-NC NO
necting the self-powered sirens and the optional non-self-powered internal sirens.
- / + : power supply for recharging the batteries of the self-powered sirens; the positive is protected by the 3.15A 250V fuse F3.
+S ext : command positive for the self-powered sirens; it constantly provides a positive which fails in the event of an alarm and is
protected by the 3.15A 250V fuse F4.
+S int : power supply positive for the optional non-self-powered sirens; it provides a positive in the event of an alarm and is protected
by the 3.15A 250V fuse F4.
ACTIVE ZONES
ENT
4.1.1 In
ACTIVE zones
you programme the zone to activate relay 1.
• From
ACTIVE zones
press to enter the rst Programming menu.ENT
Zones 1 - 8
————————
4.1.1.1 Select which
zone from 1 to 64
must activate the relay in the event of an alarm.
For each zone group, write the number 1-2-3-4-5-6-7-8 for the zones to be associated
- The default setting associates all the zones to relay 1
• The symbol will come on to conrm the association.
Zones 57 - 64
————————
• To remove the association write the required number.
to go back As there are no more parameters to be programmed, press to return to the Activated from Zone menu.ESC|
ACTIVE ZONES
ENT
From the
ACTIVE Zones
menu use the down arrow PAR| to go to the other Relay 1 settings.
Activation time
3 (0 - 255)
4.1.2
Dene what the
activation time
of relay 1 must be.
Write the required time in gures.
- The time base may be in minutes or seconds (see next step).
Time
minutes
4.1.3 The time selected can be in
minutes
or seconds.
Press CLR to change the settings.
Arming delay
0 (0 - 255)
4.1.4 Set an
activation delay
if required.
• Write the required time in gures.
- To maintain IMQ-ALARM certication the delay on activating the main relay must be programmed to zero
Disarming delay
0 (0 - 255)
4.1.5 Set a
deactivation delay
if required.
• Write the required time in gures.
to go back As there are no more parameters to be programmed, press to return to the Relay 1 Programming menu.ESC|
Output Programming
30
By-alarm
Relay 1
ENT
From the Relay 1 Programming
menu
use the down arrow PAR| to go to the Relay 2 Programming menu.
Relay 2
ENT
4.2
Relay 2
is a supplementary alarm output.
• From the Relay 1 men press to enter the rst Programming menu.ENT
Output RELAY 2
Non-positive safety relay, with exchange with 1A capacity. The voltage-free exchange is provided at the output
where there is the common, is the normally closed exchange and is the normally open one.NC NO
TYPE
0 (0 - 255)
4.2.1 Use
type
to select the Relay 2 output function, associating the activation mode.
Write the number of the required method consulting the output programming table given in point 4.3.2.
- Important: make sure that relay 2 is already associated to the tamper.
ACTIVE ZONES
ENT
4.2.2 In
A zones
the relay must activate in the event of an alarm.
From
ACTIVE zones
press to enter the rst Programming menu.ENT
Zones 1 - 8
————————
4.2.2.1 Select which
zone from 1 to 8
must activate the relay in the event of an alarm.
For each zone group, write the number for the zones to be associated.1-2-3-4-5-6-7-8
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
to go back As there are no more parameters to be programmed, press to return to the Activated from Zone menu.ESC|
ACTIVE ZONES
ENT
From the
ACTIVE ZONES
menu use the down arrow PAR| to go to the other Relay 2 settings.
Activation time
3 (0 - 255)
4.2.3 Dene what the
activation time
of relay 2 must be.
Write the required time in gures.
- The time base may be in minutes or seconds (see next step).
Time
minutes
4.2.4 The time selected can be in
minutes
or seconds.
Press CLR to change the settings.
Arming delay
0 (0 - 255)
4.2.5 Set an
activation delay
, if required.
Write the required time in gures.
Disarming delay
0 (0 - 255)
4.2.6 Set a
deactivation delay
, if required.
Write the required time in gures.
to go back As there are no more parameters to be programmed, press to return to the Relay 2 Programming menu level.ESC|
Output Programming
31
By-alarm
Relay 2
ENT
From the
relay 2 programming
menu use the down arrow PAR| to go to the Output Programming menu.
ACTIVE outputs
ENT
4.3 01710The active outputs are additional outputs available with the output expansion modules .
Output 1
(Max. 64)
4.3.1 Choose the
number of the output
to be programmed.
Write the number of the output to be programmed.
Output function
0 (MAX 108)
4.3.2 Choose the output function associating the mode.
Write the number of the required mode by consulting the table on the following page.
Output Programming
Progr. Type of function Description
0 No function No associated function.
1Zone state
(circuit test)
When one of the associated zones is unbalanced the output is activated,
while if a zone is excluded the exit is activated intermittently; the output does
not follow the programmed times.
2 Zone state
(not ashing)
When one of the associated zones is unbalanced the output is activated; the
output does not follow the programmed times.
3 Timed zone state
The output is activated when one of the associated zones is unbalanced;
the output is deactivated at the end of the programmed time (classic ap-
plication: stair lights).
Note: the programmed time starts from when the zone is re-balanced.
4 Zone alarm The output is activated when one of the associated zones sets off an alarm,
following the programmed time. Time: T1
5 Anti-tampering zone The output is activated when one of the associated zones sets off an anti-
tampering alarm, following the programmed time. Time: T1
6 Masking The output is activated when one of the associated zones sets off a masking
alarm, following the programmed time. Time: T1
7 General anti-tampering The output is activated when any anti-tampering alarm is triggered from any
part, following the programmed time. Time: T1
8Control unit anti-tam-
pering
The output is activated when there is a anti-tampering alarm on the control
unit, following the programmed time. Time: T1
9 Keypad anti-tampering The output is activated when there is a anti-tampering alarm on one or more
keypads, following the programmed time. Time: T1
10 Input expansion Tamper The output is activated when there is a anti-tampering alarm on one or more
input expansion modules 01709, following the programmed time. Time: T1
11 Output expansion
Tamper
The output is activated when there is a anti-tampering alarm on one or more
output expansion modules 01710, following the programmed time. Time:
T1
12 - 19 Area on 1-8
The output is activated when the selected group is inserted in one of the
three modes. If during the last on period there was an alarm and the output
activation duration is not zero, when disconnecting the group the output
ashes until reconnection, or otherwise is deactivated.
20 - 27 Time: T4Area ON on 1-8 It is activated when the selected group is on in ON mode.
28 - 35 Time: T4Area INT on 1-8 As above, when the selected group is on in INT mode.
36 - 43 Area PAR on 1-8 As above, when the selected group is on in PAR mode. Time: T4
44 Activation from keypad
RFA, PO
The outputs programmed in this mode can be activated from a user code,
a remote phone using the RFA function and from a programmable time
switch. If the activation duration is 255 the output function is toggle other-
wise it follows the programmed time.
32
By-alarm
Output Programming
Progr. Type of function Description
45 No mains It is activated when there is no 230 V mains voltage to the control unit.
Time: T2
46 Battery trouble It is activated when the control unit or additional power supply battery level
is low or not available. Time: T2
47 Time: T2Cut telephone line It is activated when the phone line is cut.
48 Time: T2Failed GSM signal It is activated when there is no GSM signal on the module 01706.
49 Time: T2Sim used up It is activated when the SIM CARD inserted has less than 5 EUR. .
50 Time: T2On line PSTN dialler It is activated when the phone communicator occupies the line.
51 On line GSM It is activated when the module 01706 is on line. The output follows the set
times. Time: T2
52 Time: T3Self-test (battery) It is activated when the control unit runs the dynamic battery test.
53 No
PC connection
It is activated when there is no direct connection with the PC.
Time: T3
54 Incorrect code It is activated when an incorrect code is entered three times in a row both
from the keypad and from an RFA telephone connection. Time: T3
55 Chime
It is activated when the lines associated to the chime function are unbal-
anced. This output is reset when a valid user code is entered for the group
the relative zones belong to; the output does not follow the programmed
time.
56 Ding dong It is activated when the lines associated to the Din Don function are unbal-
anced. Time: T3
57 Advanced warning turn-
ing on by Prog. Timer
It is activated during the programmable time switch on notication time.
Time: T3
58 Installer ID It is activated when an installer code is entered and is deactivated when you
exit programming regardless of the programmed time value.
59-66 Area 1-8 The exit is activated when the re-entry time for the corresponding group is
progress and is deactivated after the time or if the group is turned off.
67-74 Area 1-8 The exit is activated when the exit time for the corresponding group is pro-
gress and is deactivated after the time or if the group is turned off.
75 Output AND Zone The output is activated when all the associated entry lines cause an alarm.
Time: T3
78 Remote function access
active
The output is active when an RFA remote function session is in progress.
Time: T1
79 Key (TAG)
recognised
The output is activated when a proximity key is recognised.
Time: T1
80 General output
(RFA-TAST-PO)
The output is activated when commanded from a user code, emergency
code, programmable time switch, macro or RFA. Time: T3
81 Panic message The output is activated when a panic call is made from the keypad (ON + 4).
Time: T3
82 Doctor Message The output is activated when a doctor call is made from the keypad
(ON + 5). Time: T3
83 Fire Message The output is activated when a re call is made from the keypad (ON + 6).
Time: T3
84 Public holiday The output is active when there is a public holiday running on the program-
mable time switch. Time: T2
85 Locked Prog. Timer
(PO)
The output is activated when the programmable time switch is disabled by
the user. Time: T2
86 Non-routine The output is active when overtime is running on the programmable time
switch. Time: T2
87 Time: T2Keypad lock The output is active when the associated keypad is locked.
88 - 95 Suspension Area 1-8 The output is active when the corresponding group is suspended. Time: T2
96 User codes blocked The output is active when one or more associated codes are locked (by the
Programmable time switch or an appropriately programmed input). Time: T2
97 Pre-alarm The output is activated at the end of the pre-alarm time if the coercion
condition is not re-set. Time: T3
98 Phone line ring-tone The output is activated when the telephone connected to the network rings.
Time: T3
33
By-alarm
Times Times
T 1
0 : armed for 3 seconds
1 .. 253 : armed for the programmed seconds or minutes
254 : armed until the area to which the zone is associated is disconnected
255 : follows the zone alarm status (disarmed if the zone returns from the alarm status)
T2 If the activation length is 255 the output follows the signalling status otherwise it follows the
programmed time
T3 The output on duration follows the programmed time
T4
0 : a pulse is given on arming and again on disarming.
1 .. 253 : armed for the programmed seconds or minutes
255 : follows the signalling status
For the usable and therefore programmable time values, comply with what stated in the table below.
Output Programming
Progr. Type of function Description
99 GSM line ring-tone The output is active when the GSM module 01706 is receiving a call. Time:
T3
100 Incoming SMS The output is activated when a text message arrives through the GSM
module 01706. Time: T3
101 AND Outputs The output is activated when all the associated outputs cause an alarm.
Time: T3
102 OR Outputs The output is activated when one of the associated outputs causes an
alarm. Time: T3
103 Gate The output is activated when one of the associated entrances is activated
from a transponder key. Time: T1
104 Caller
recognition (via GSM)
The output is activated when the associated numbers are recognised on
arrival by the GSM module 01706. Time: T1
105 SIM expiring The output is activated when there are 30 days left until the SIM expires.
Time: T1.
106 Fail supervision
107 Radio battery trouble
108 Jamming
34
By-alarm
Activation time
0 (0 - 255)
4.3.3 Dene the
activation time
of the active output selected.
• Write the required time in gures.
- The time base may be in minutes or seconds (see next step).
Time
seconds
4.3.4 The selected time can be in
seconds
or minutes.
Press CLR to change the settings.
Arming delay
0 (0 - 255)
4.3.5 Set an
activation delay
if required.
Write the required time in gures.
Disarming delay
0 (0 - 255)
4.3.6 Set a
deactivation delay
if required.
Write the required time in gures.
Out. mode
NORM.Disarmed
4.3.7 In
Output mode
you programme the output state:
Write the required time in gures.
Not active: normally does not supply any voltage; a negative is supplied when the programmed condition occurs.
Active: constantly supplies a negative which is stopped when the programmed condition occurs.
Memo arming
NO
4.3.8 In
memo activation
with a you programme any active output state change is recorded in the control unit events YES
memory.
Press CLR to change the settings.
ACTIVE ZONES
ENT
4.3.9 In
ACTIVE zones
you programme the zone which must activate the output.
From
ACTIVE Zones
press to enter the rst Programming menu.ENT
Zones 1 - 8
————————
4.3.9.1 Select which
zone from 1 to 8
must be activated in the event of unbalancing of the active output selected.
For each zone group, write the number 1-2-3-4-5-6 for the zones to be associated.
• The symbol will come on to conrm the association.
• To remove the association write the required number.
Zones 57 - 64
————————
As there are no more parameters to be programmed, press to return to the zone activation menu level. to go back ESC|
ACTIVE zones
ENT
As there are no more parameters to be programmed, press to return to the Output Programming menu level. to go back ESC|
ACTIVE outputs
ENT
As there are no more parameters to be programmed, press to return to the Output Programming menu level. to go back ESC|
Outputs
ENT
From the
Outputs
menu use the down arrow PAR| to return to the Code Programming menu level.
Output Programming
35
By-alarm
5. ID Programming
 
5. The Codes are used to manage all the control unit functions and are authentic access keys.
The first 15 default codes are given in the following table and by default programming only the Installer ID and the User 1 ID are
enabled; all other User IDs must be activated via the programming.
Installer User 1 User 2 User 3 User 4 User 5
1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4 5 5 5 5 5 5
User 6 User 7 User 8 User 9 User 10
1 2 3 4 5 6 6 6 6 6 6 6 7 7 7 7 7 7 8 8 8 8 8 8 9 9 9 9 9 9 0 0 0 0 0 0
User 11 User 12 User 13 User 14 User 15
1 0 0 0 0 0 1 0 0 1 0 0 1 0 0 2 0 0 1 0 0 3 0 0 1 0 0 4 0 0
Press ENT to enter the settings.
 
5.1 In you programme the figures comprising the code.
• From the menu press to enter the settings.ENT
5.1.1 The Installer ID is the only code allowing access to the programming and is programmed by default as .123456
• Press to delete the current code.CLR
• Write the .new code
• Press to confirm the new code.ENT
As there are no more parameters to be programmed, press to return to the Installer ID Programming menu level. to go back ESC|
 
From the Installer ID use the down arrow PAR| to go to the User ID Programming menu.
 
5.2 In you enter the figures comprising the ID.
• Press to enter the programming. ENT
5.2.1 Select the you wish to programme.
• Write the number of the code you wish to programme.
• With the down arrow PAR| go to the User ID parameter settings.
 
5.2.2 In you programme the digits comprising the code.
From the menu press
ENT to enter the settings.
5.2.2.1 You enter the value of the chosen code.
Press CLR to delete the current code.
• Write the new code.
• Press to confirm the new code.ENT
to go back As there are no more parameters to be programmed, press to return to the Code Digits Programming ESC|
menu level.
ID Programming
36
By-alarm
 
From the Code Digits Programming use the down arrow PAR| to go to the Code properties programming menu.
5.2.3 A programmes the YES .
Press CLR to change the settings.
 
5.2.4 In you associate the code to the control unit area.
From the menu press to enter the settings.ENT
5.2.4.1 Select an to associate the Code to.
Write the number 1-2-3-4-5-6-7-8 for the areas it is associated to.
• The symbol will come on to confirm the association.
• To remove the association write the required number.
As there are no more parameters to be programmed, press to return to the Active Areas menu level. to go back ESC|
 
From use the down arrow PAR| to go to the Arming and Scheduler Settings menu.
 
5.2.5 In the menu you programme all the functions for the arming states.
Press ENT to enter the settings.
5.2.5.1 A enables the Code onYES .
Press CLR to change the settings.
5.2.5.2 A enablesYES .
Press CLR to change the settings.
5.2.5.3 A enablesYES .
Press CLR to change the settings.
5.2.5.4 A enables the Code toYES the control unit.
Press CLR to change the settings.
5.2.5.5 A enables the Code to YES .
Press CLR to change the settings.
5.2.5.6 A enables the Code to YES .
Press CLR to change the settings.
As there are no more parameters to be programmed, press to return to the Arming Programming menu. to go back ESC|
ID Programming
37
By-alarm
 
From the programming menu use the down arrow PAR| to go to the Auxiliary Options programming menu.
 
5.2.6 In the you can programme additional User ID properties.
Press ENT to enter the settings.
5.2.6.1 A enables the User ID to be able toYES .
Press CLR to change the settings.
5.2.6.2 A enables the User ID to be able toYES .
Press CLR to change the settings.
5.2.6.3 A enables the User ID to be able toYES .
Press CLR to change the settings.
5.2.6.4 A enables the User ID to be able toYES .
Press CLR to change the settings.
5.2.6.5 A enables the User ID to be able to YES in the event of an alarm.
Press CLR to change the settings.
5.2.6.6 A enables the User ID toYES of the control unit.
Press CLR to change the settings
5.2.6.7 A enables the User ID toYES on the keypad.
Press CLR to change the settings.
5.2.6.8 With enables the User ID to remotely connect the voice user.YES
Press CLR to change the settings.
5.2.6.9 With enables the User ID for remote connection via SMS.YES
Press CLR to change the settings.
5.2.6.10 With enables the User ID to bypass zones.YES
Press CLR to change the settings.
5.2.6.11 With , the User ID is enabled to activate the macro-instructions.YES
Press CLR to change the settings.
As there are no more parameters to be programmed, press to return to the Auxiliary Options menu level. to go back ESC|
ID Programming
38
By-alarm
 
From the programming menu use the down arrow PAR| to go to the Access Control Settings menu
 
5.2.7 In you programme some special functions of the Code.
Press ENT to enter the settings.
5.2.7.1 A allows the code toYES .
Press CLR to change the settings.
5.2.7.2 A allows the code to trigger aYES send.
Press CLR to change the settings.
5.2.7.3 With in , the code can block a silent alarm phone call.YES
Press CLR to change the settings.
As there are no more parameters to be programmed, press to return to the Access Control menu level. to go back ESC|
 
From use the down arrow PAR| to go to the proximity key (TAG) Settings menu, associating it to the User ID.
 
5.2.8 In you programme the proximity key for the User ID.
From the menu press to enter the settings.ENT
 
5.2.8.1 In
you associate a proximity key to the User ID.
Press ENT to enter the settings.
 
5.2.8.1.1 In you associate a proximity key to the system arming and disarming function.
Press ENT to enter the settings.
5.2.8.1.1.1 key near the reader with address 0 and the acquisition will be confirmed on
the display.
Press ESC| to exit the acquisition and return to the previous menu.
to go back
 
In
you associate a proximity key to the User ID.
Press ENT to enter the settings.
 
From use the down arrow PAR| to go to the menu associating the key to the entry function.
ID Programming


Produkt Specifikationer

Mærke: Vimar
Kategori: Ikke kategoriseret
Model: 01703

Har du brug for hjælp?

Hvis du har brug for hjælp til Vimar 01703 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Vimar Manualer

Vimar

Vimar EZS10.GA Manual

2 April 2025
Vimar

Vimar ELVOX 1358 Manual

12 Januar 2025
Vimar

Vimar 01585 Manual

12 Januar 2025
Vimar

Vimar 20136.120.B Manual

11 Januar 2025
Vimar

Vimar 20457.TR.B Manual

29 December 2024
Vimar

Vimar 20457.TR.N Manual

29 December 2024
Vimar

Vimar 19457.TR.B Manual

29 December 2024
Vimar

Vimar 20537 Manual

15 December 2024
Vimar

Vimar 19593.M Manual

15 December 2024
Vimar

Vimar 20537.B Manual

15 December 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer