Side 1/2
CT-326-C Current Tracer
Probe Range Switch
1. Range switch determines the probes gain.
2. If the probe displays 10 LEDs, gain is too sensitive. Turn switch to lower setting.
Identify Circuit Breaker (Fig. 2)
1. Connect the transmitter to a source of power.
2. Set the probes range switch to BREAKERS-3.
3. Push ON and wait for it to calibrate.
4. Hold the probe’s tip to each circuit breaker as shown. The correct breaker
produces the strongest signal. Adjust gain as necessary.
5. In critical areas, remove panel trim and turn the probes range switch to
WIRES-1. Hold the tip to each wire. The wire with the strongest signal may
be visually traced to the breaker.
Locating Wires In Walls (Fig. 3)
1. Attach pigtail connector to transmitter.
2. Clip one lead to a seperate earth ground such as a water pipe.
3. Clip the other lead to the hot conductor.
4. Set the probes range switch to SCAN position.
5. Push ON and wait for it to calibrate.
6. Hold the probe’s tip close to the wall or floor where you suspect the
conductor is located.
7. Sweep the probe across large areas until the probes signal locates the
conductor. Adjust range switch as necessary.
NOTE: The same procedure may be used for tracing individual wires in
bundles.
Following Conduit (Fig. 4)
1. Attach transmitter and follow signal as explained in
“Locating Wires in Walls”.
2. Adjust the probe’s range switch as necessary.
HINT: Since the feeder panel may radiate a magnetic signal to
nearby conduit, make sure the probe is always more than 5’
(1.5 m) away from the circuit breaker box.
Fig. 4
Fig. 3
Fig. 1
Fig. 2
Test Position (Fig. 1)
1. Connect the transmitter to source of power.
2. Set the probes range switch to BREAKERS-5.
3. Push ON and wait for it to calibrate.
4. Hold the probe next to the transmitter, observe blinking LEDs and
“chirping” sound.
Probe Battery Test
1. Push the probes BATTERY TEST and ON buttons at the same time.
2. If the probes LEDs do not light in BATTERY OK range, change the battery.


Produkt Specifikationer

Mærke: Amprobe
Kategori: Ikke kategoriseret
Model: CT-326-C

Har du brug for hjælp?

Hvis du har brug for hjælp til Amprobe CT-326-C stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Amprobe Manualer

Amprobe

Amprobe MAN30 Manual

16 Maj 2024
Amprobe

Amprobe AT-4004-A Manual

28 April 2024
Amprobe

Amprobe AF-600 Manual

28 April 2024
Amprobe

Amprobe LH41A Manual

19 April 2024
Amprobe

Amprobe AMP-220 Manual

5 April 2024
Amprobe

Amprobe TP254A Manual

22 Marts 2024
Amprobe

Amprobe RC-120S Manual

25 Februar 2024
Amprobe

Amprobe AM-270 Manual

6 Februar 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer