Læs gratis den danske manual til A.O. Smith HPS10-66H45DV (1 sider) i kategorien Vandvarmer & kedel. Denne vejledning er vurderet som hjælpsom af 20 personer og har en gennemsnitlig bedømmelse på 3.7 stjerner ud af 10.5 anmeldelser. Har du et spørgsmål om A.O. Smith HPS10-66H45DV, eller vil du spørge andre brugere om produktet?

Side 1/1
HPS10 models
4065452, 4842214 &
5207971
HPA10 models
5374506, 5374507,
5374512 & 5374513
HPV10 models
5374508 & 5374510
Conguraon Enclosed Room Fully Louvered Door
Upper and Lower Louvers in Door
Upper Louver and Undercut Door
(Note 1,3,4)
Inlet or
Outlet Ducng and a Single
Louver or Undercut Door (Note
1,3,4,5)
Inlet and Outlet Ducng
(Note 5)
Minimum Space (FT
3
)
450 84 84 84
Space Example
L x W x H (FT)
6 x 7.5 x 10 3 x 2.8 x 10 3 x 2.8 x 10 3 x 2.8 x 10
450
3
enclosed room size is 35% smaller than other manufacturers require
Note 1: Minimum louver size is 130 in
2
free area
each.
Note 2: When two louvers are installed, install one louver at the top of the heater and the other close to the oor.
Note 3: Undercut door should have a minimum of 0.75" clearance. (minimum 18 in
2
air gap)
Note 4: When one louver is installed, install the louver in a locaon close to the top of the heater.
Note 5: This heater supports mulple duct diameters as well as rigid and ex ducng opons. See manual for more informaon.
HP10 models
Lowe's Items:
816193 & 816194
Conguraon Enclosed Room Fully Louvered Door
Upper and Lower Louvers in Door
Upper Louver and Undercut Door
(Note 1,3,4)
Inlet or
Outlet Ducng and a Single
Louver or Undercut Door (Note
1,3,4,5)
Inlet and Outlet Ducng
(Note 5)
Minimum Space (FT
3
)
450 84 84 84
Space Example
L x W x H (FT)
6 x 7.5 x 10 3 x 2.8 x 10 3 x 2.8 x 10 3 x 2.8 x 10
450
3
enclosed room size is 35% smaller than other manufacturers require
Note 1: Minimum louver size is 130 in
2
free area
each.
Note 2: When two louvers are installed, install one louver at the top of the heater and the other close to the oor.
Note 3: Undercut door should have a minimum of 0.75" clearance. (minimum 18 in
2
air gap)
Note 4: When one louver is installed, install the louver in a locaon close to the top of the heater.
Note 5: Ducng these models requires adapter kit 100234320. Duct with 8" ex duct. Maximum 50 equivalent feet for total of inlet and outlet ducng.
No minimum space requirement No minimum space requirement
No minimum space requirement No minimum space requirement
Venlaon Guidelines for Professional Installers


Produkt Specifikationer

Mærke: A.O. Smith
Kategori: Vandvarmer & kedel
Model: HPS10-66H45DV

Har du brug for hjælp?

Hvis du har brug for hjælp til A.O. Smith HPS10-66H45DV stil et spørgsmål nedenfor, og andre brugere vil svare dig




Vandvarmer & kedel A.O. Smith Manualer

Vandvarmer & kedel Manualer

Nyeste Vandvarmer & kedel Manualer

Vevor

Vevor FJI-POR-40S2 Manual

21 November 2025
Midea

Midea 787300 Manual

15 November 2025
Optimal

Optimal Opti12 Manual

15 November 2025
Optimal

Optimal Opti18 Manual

14 November 2025
Tornado

Tornado GHE-C10BNE-W Manual

11 November 2025
Klarstein

Klarstein Blaze Flow Manual

10 November 2025
Tornado

Tornado GHE-10MP-GS Manual

10 November 2025
Tornado

Tornado GHE-C10BNE Manual

9 November 2025
Tornado

Tornado GHS-6CNE-S Manual

9 November 2025