Læs gratis den danske manual til APC Smart-UPS On-Line SRC1KXLI (28 sider) i kategorien UPS. Denne vejledning er vurderet som hjælpsom af 18 personer og har en gennemsnitlig bedømmelse på 5.0 stjerner ud af 9.5 anmeldelser. Har du et spørgsmål om APC Smart-UPS On-Line SRC1KXLI, eller vil du spørge andre brugere om produktet?
Side 1/28

Important Safety Information
Read the instructions carefully to become familiar with the equipment before
trying to install, operate, service or maintain it. The following special
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies
a procedure.
The addition of this symbol to a Danger or Warning safety label
indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical
injury.
User Manual Smart-UPS™ On-Line
SRC1KXLI

Smart-UPS On-Line SRC1KXLI2
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
Read the Safety Guide supplied with this unit before installing the UPS.
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC
could void the warranty.
• This UPS is for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or
where there is excessive dust or high humidity.
• Do not operate the UPS near open windows or doors.
• Be sure the air vents on the UPS are not blocked. Allow adequate space
for proper ventilation.
Note: Allow 20 cm clearance on both front and rear sides of the UPS.
• Use only the mains and communication cables provided along with the
UPS.
• The equipment is heavy. Always practice safe lifting techniques
adequate for the weight of the equipment.
Electrical safety
• Use tools with insulated handles.
• Do not handle any metallic connector before power has been
disconnected.
• For models with a hardwired input, the connection to the branch circuit
(mains) must be performed by a qualified electrician.
• Output cord connected to the UPS must not exceed 10 meters in length.
• The protective earth conductor for the UPS carries the leakage current
from the load devices (computer equipment). An insulated ground
conductor is to be installed as part of the branch circuit that supplies the
UPS. The conductor must have the same size and insulation material as

Smart-UPS On-Line SRC1KXLI 3
the grounded and ungrounded branch circuit supply conductors. The
conductor will typically be green, with or without a yellow stripe.
• Leakage current for a pluggable, Type A UPS may exceed 3.5 mA when
a separate ground terminal is used.
• The UPS input ground conductor must be properly bonded to protective
earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the
ground conductor must be properly bonded at the supply transformer or
motor generator set.
Battery safety
• Replace batteries with the same number and type of batteries as
originally installed in the equipment.
• Schneider Electric uses Sealed Maintenance-Free (SMF) batteries.
Under normal use and handling, there is no contact with the internal
components of the battery. Over charging, over heating or other misuse
of batteries can result in a discharge of battery electrolyte. Released
electrolyte is toxic and may be harmful to the skin and eyes.
• CAUTION: Before installing or replacing the batteries, remove
conductive jewelry such as chains, wrist watches and rings. High energy
through conductive materials could cause severe burns.
• CAUTION: Do not dispose of batteries in a fire. The batteries may
explode.
• CAUTION: Do not open or mutilate batteries. Released material is
harmful to the skin and eyes and may be toxic.
Hardwire safety
• Check that all branch circuit (mains) and low voltage (control) circuits
are deenergized, and locked out before installing cables or making
connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• Strain relief is required for all hardwiring (supplied with select
products).
Snap in type strain reliefs are recommended.
• All openings that allow access to UPS hardwire terminals must be
covered. Failure to do so may result in personal injury or equipment
damage.
• Select wire size and connectors according to national and local codes.

Smart-UPS On-Line SRC1KXLI 5
Package Contents
Read the Safety Guide before installing the UPS.
The packaging is recyclable; save it for reuse or dispose of it properly.
• UPS • Literature kit containing:
– Product documentation
All models
Utility power cable USB cable
Used to connect UPS to
computer/laptop for PCBE
monitoring
Serial communication cable
Used to upgrade the UPS
firmware if and when a new
version is available. Also
used to monitor the UPS
UPS management
software CD
• 1 pair rack-mount bracket
• 8 screws to secure the rack-mount bracket with the USP
1 IEC output cable
2 pairs foot
S
c
h
n
e
i
d
e
r
E
l
e
c
t
r
i
c
I
n
d
u
s
t
r
i
e
s
S
A
S
2
0
1
7
User D ocumenta tion
Softw are
UPS Monit oring

Smart-UPS On-Line SRC1KXLI6
Specifications
Environmental specifications
Physical specifications
NOTICE
RISK OF EQUIPMENT DAMAGE
• UPS must be used indoors only.
• The installation location should be sturdy to withstand the weight of
the UPS.
• Do not operate UPS where there is excessive dust or where the
temperature or humidity are outside specified limits.
Failure to follow these instructions can result in equipment
damage.
Temperature Operating 0° to 40°C at rated load
40° to 50°C linearly derated to
80% of maximum load capacity
This unit is intended for
indoor use only. Select
a location sturdy
enough to handle the
weight.
Do not operate UPS
where there is excessive
dust or where the
temperature or
humidity are outside
specified limits.
Note: Charge the
battery modules every
six months during
storage.
Storage -20° to 50°C
Elevation Operating • 0 - 1,000 m: normal operation
• 1,000 - 3,000 m: The load
reduces @ 1% at an increased
height of every 100 m
• > 3,000 m: UPS will not work
Storage 0 - 15,000 m
Humidity 20 to 90% relative humidity,
non-condensing
The UPS is heavy. Follow lifting guidelines.
Dimensions without packaging
Width x Height x Depth
438 mm (17.24 in) x 88 mm (3.5 in) x 410 mm
(16.14 in)
Weight with packaging 17.8 kg
Weight without packaging 15.4 kg

Smart-UPS On-Line SRC1KXLI8
Battery
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery
replacement is necessary.
• Replace battery at the end of its service life.
• Replace batteries with the same number and type of batteries as
originally installed in the equipment.
• Replace the battery immediately when the UPS indicates a battery
overtemperature condition, or when there is evidence of electrolyte
leakage. Power off the UPS, unplug it from the AC input, and
disconnect the batteries. Do not operate the UPS until the batteries
have been replaced.
• Replace all battery modules (including the modules in External
Battery Packs) which are older than one year, when installing
additional battery packs or replacing the battery module(s).
Failure to follow these instructions could result in equipment
damage and minor or moderate injury.
Configuration Internal battery
Type Sealed maintenance free (SMF) 12 V, 10 Ah
Battery bank voltage 36 V

Smart-UPS On-Line SRC1KXLI 9
Installation
Rack-mount installation
CAUTION
RISK OF FALLING EQUIPMENT
• The equipment is heavy.
• Ensure that the stabilizer brackets are installed when the UPS is
installed in the tower orientation.
Failure to follow these instructions can result in minor or
moderate injury.
x4
x4

Smart-UPS On-Line SRC1KXLI10
Secure UPS to the rack with four screws (not supplied)

Smart-UPS On-Line SRC1KXLI 11
Tower installation
Remove display and rotate. Install display
Produkt Specifikationer
Mærke: | APC |
Kategori: | UPS |
Model: | Smart-UPS On-Line SRC1KXLI |
Har du brug for hjælp?
Hvis du har brug for hjælp til APC Smart-UPS On-Line SRC1KXLI stil et spørgsmål nedenfor, og andre brugere vil svare dig
UPS APC Manualer
14 Januar 2025
14 Januar 2025
14 Januar 2025
14 Januar 2025
14 Januar 2025
1 Januar 2025
29 December 2024
11 December 2024
11 December 2024
12 Oktober 2024
UPS Manualer
- HP
- Ditek
- Eaton
- GYS
- LevelOne
- Murr Elektronik
- Puls Dimension
- Online USV
- FSP
- Atlantis Land
- Middle Atlantic
- PowerWalker
- LC-Power
- Voltcraft
- Gembird
Nyeste UPS Manualer
30 Januar 2025
9 Januar 2025
31 December 2025
31 December 2025
30 December 2025
30 December 2025
28 December 2024
28 December 2024
28 December 2024
14 December 2024