Apricus | All-In-One Air Sourced Water Heat Pump
A Select installation location
a. This unit is designed for outdoor installation only.
b. Avoid installation in areas where falling debris, such as leaves, is
prevalent.
c. Avoid placing the system in locations with multiple walls or structures.
B Prepare the Base
a. The unit should be installed on a concrete plinth or stable structure
capable of sustaining weights in excess of 450kg.
b. A minimum dimension of 600mm x 600mm is required. Please ensure
that all four feet are supported by the base being used otherwise
warranties may be voided.
c. The system is to be installed level.
C Plumbing and wiring
This product MUST be wired on a dedicated circuit protected by a 20A
circuit breaker. The system supplied with a 3-pin plug but 20A isolator
switch hard wired to the system is highly recommended when electrician
is available on site.
D Air bleed
Ensure at least one hot water tap is open inside the property. While the
system begins filling with water, you will hear air being expelled from the
open hot water tap. This ensures that no air pockets remain. Once water
begins running out of the hot water tap, the system is completely bled and
you can then turn the tap off. Please bleed air out of PTRV as well.
E Turning the system on
a. Remove the controller cover by simply loosening hand screws.
b. Unlock the screen by pressing the POWER button once.
c. Press and hold the POWER button for 3 seconds until the SUN symbol
flashes.
d. Change the operational mode if required. The system has 4 operational
modes, and the default mode is “ECO”.
d. Connect the controller to wifi and mobile app on the end user app.
f. Return screen cover back onto unit after setting clock.
600mm
600mm
CONCRETE BASE
To Drain
1. Cold water supply outlet
(G3/4” f themale read)
2. Hot water outlet
(G3/4” f themale read)
3. Condensing drainage elbow*
4. P&T relief valve*
(G1/2” female)(850kPa)
5. mTe pering valve
(high performance
rec )ommended
6. Expansion Control Valve
(ECV) (if required by council
700kPa)
7. Pressure Valve (500kPa)
8. eNon-return/isolation valv
9. eEl ctrical Cabel
10. Electrical Access
11. Electrical Access
*supplied with the system
1
6
5
2
3
4
9
10 11
78
To Drain
To Drain
To House