Aritech SHATTERPRO 3 Manual

Aritech Sikkerhed SHATTERPRO 3

Læs gratis den danske manual til Aritech SHATTERPRO 3 (16 sider) i kategorien Sikkerhed. Denne vejledning er vurderet som hjælpsom af 16 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 8.5 anmeldelser. Har du et spørgsmål om Aritech SHATTERPRO 3, eller vil du spørge andre brugere om produktet?

Side 1/16
SHATTERPRO 3 GLASSBREAK DETECTOR
INSTALLATION I NSTRUCTIONS
- 1 -
Figure 1 - Mounting Locations
Figure 2 - Multiple Window Coverage
Microphone
LED
Figure 3 - Attaching the Cover
7. Connect the system wires to the appropriate screw terminals on the base
and tighten the screws.
8. Replace the cover as follows:
- Round housing: Line up the tabs on the base with the correspond-
ing tabs on the cover, press together and turn clockwise until the
cover snaps firmly into place. See Figure 3.
- Rectangle housing: Press the cover back down over the detector
until the cover snaps firmly into place.
9. Apply power. The red LED should flash once.
10. Test the detector. See Testing the Detector.
F
NL
D
I
S
DK
DESCRIPTION
The ShatterPro 3 is an acoustic glassbreak detector designed to detect
breaking glass from framed windows in the perimeter of a building. The
detector is mounted in the building interior and uses a power supply from a
12 VDC control panel. The detector is available in either a low-profile round
housing or a rectangular housing that connects easily to a single-gang box.
SELECTING A L OCATION FOR THE D ETECTOR
Mount the detector on ceilings or on walls opposite or adjacent the window
to be protected. See Figure 1. Use the following guidelines to determine the
best location to install the detector.
wMount at least 1m from the glass windows being protected.
wWindows must be at least 30 x 60 cm square.
wAvoid locations where lined, insulating or sound deadening curtains are
used.
wMount 30cm away from wall corners.
wAvoid locations where interior closed wooden shutters are used.
wLocate in a suitable environment as follows:
- Temperature between and 50°C
- Humidity between 10 and 90% non-condensing
wMount the detector on a stable surface up to 7.6 m from the farthest point
on the glass surface. See Figure 1.
wAvoid locations that expose the detector to possible false alarm sources
such as: Glass airlocks and vestibule areas, kitchens, residential car
garages, small utility rooms, stairwells, bathrooms, small acoustically live
rooms, air vents.
SELECTING THE B EST L OCATION FOR M ULTIPLE W INDOW
COVERAGE
The detector has a 360° coverage pattern that can cover several windows
in a single room as follows (See Figure 2):
wDraw an imaginary line from the center of each window to be covered
in towards the center of the room.
wMount the detector as close to where the lines intersect as possible.
wDo not mount the detector at more than a 60° angle from the center of any
window to be protected.
INSTALLING THE D ETECTOR
All wiring must conform to national approvals.
Important ! If you are unsure about a location, connect a 9 V battery to the
detector and test it before permanently mounting. See Testing the Detector.
To install the detector:
1. Run the security system wiring to the detector location.
2. Remove the front cover as follows:
- Round housing: Press the release tab on the lip of the base, twist
the cover counterclockwise, and lift off.
- Rectangle housing: Gently pry up the slot on the bottom of the
cover to unlock the cover. Lift up the cover until it latches in the open
position.
3. Set the range with J3 on the circuit board. See Setting the Range.
4. Remove the appropriate wiring and mounting knockout holes from the
base. See Figure 4.
5. Pull the wires through the knockout holes and use two screws to attach
the base to the surface. Use wall anchors if necessary.
6. Strip 1 cm of insulation from each wire.
GB
Ceiling
mount
Detector
60° max.
60° max.
7.6 m
max.
7.6 m
max.
Ceiling
mount
Wall
mount
- 2 -
SPECIFICATIONS
Input voltage ........................................................................... 9.5 to 16 VDC
Current
Typical ..................................................................................... 15 mA
Maximum ................................................................................. 25 mA
Electrical configuration ....................................................................... Form C
Relay rating ....................................................................... 16 V, 50 mA max.
Tamper switch rating ....................................................... 12 V, 50 mA max.
Detection range ............................................................ 0.9 m - 7.6 m x 360°
Alarm response ................................................................................... 4 sec.
Minimum glass size ............................................................. 30.5 cm x 61 cm
Recommended glass thickness:
Plate ........................................................................ 2.5 mm - 6.5 mm
Tempered .................................................................. 3 mm 6.5 mm
Wired ...................................................................................... 6.5 mm
Laminated .............................................................................. 6.5 mm
Operating temperature ....................................................................0° - 50°C
Relative humidity .................................................. 10 - 90% non-condensing
Round housing dimensions: ............................................. 2 x 10 cm (D x Æ)
Rectangle housing dimensions: ....................... 11.5 x 7 x 2 cm (H x W x D)
Color ................................................................................................. White
Field wiring size ......................................................................... 18-24 AWG
SETTING THE R ANGE
The detector has a spring clip (J3) to set room size. See Figure 4. Use the
following table to determine what setting to use for an application.
Setting Description
Open Sets the range for 1.5 m to 7.6 m. Use for rooms
30 m² and larger. Default
Closed Sets the range 1 m to 3 m. Use for rooms smaller
than 30 m².
TESTING THE D ETECTOR
Use a Sentrol 5709C hand-held tester to verify detector range and operation.
To test the detector:
1. Set the tester to the appropriate glass-type setting. Use the tempered
setting if you are unsure about the glass type.
2. Put the detector in test mode as follows:
- Hold the tester close to the detector. See Figure 5.
- Activate the tester.
The LED on the detector lights for 4 seconds and then starts flashing to
indicate the detector is in test mode. The relay opens for 4 seconds, then
returns to standby.
3. Hold the tester near the surface of the glass to be protected and aim the
speaker at the detector. Be sure the tester is at the point on the glass
farthest from the detector. If closed curtains are present, hold the tester
behind them. See Figure 6.
4. Press the test button on the tester. The LED on the detector should stay
on for 4 seconds to indicate the glass is within detection range of the
detector. If the LED does not stay on for 4 seconds, move the detector
and retest.
UNDERSTANDING THE LED
The red LED located on the front of the detector indicates the status of the
unit as follows:
Status LED indication
Power on Flashes when power is applied.
Clap test/Alarm
memory In response to the clap test:
Flashes twice to indicate the detector has power
and is functioning properly.
Or
On for 4 seconds to indicate the detector has
alarmed.
Alarm On for 4 seconds with relay when breaking glass
is detected.
Test mode On for 4 seconds with relay, then flashes for 60
seconds. Each test trigger resets the test mode
clock and the LED restarts flashing for 60
seconds.
USING THE H AND-CLAP T EST AND A LARM M EMORY
Check the alarm memory and detector operation with the hand-clap test as
follows:
1. Standing under the detector, clap your hands together.
2. Observe the LED on the detector.
If the detector has power and is functioning properly, the LED quickly
flashes twice.
If the detector has alarmed, the LED will light for 4 seconds. Cycle the
power to clear the alarm memory.
The hand-clap test is intended as a functional test and is not an accurate
indication of detector range.
J3 Spring clip
Figure 4 - Detector Knockout Locations
Figure 5 Using the Tester Figure 6 - Testing the Range
• Single
• Continuous Plate •
Tempered •
Laminated •
Battery LED
Battery is OK if LED
stays on during test
5709C
Shatter Series Tester
Use for testing:
ShatterPro
Shatterbox
Shatterbox II
ShatterSwitch
SENTROL
2.5 cm
Knockouts
Knockouts
Slot
J3


Produkt Specifikationer

Mærke: Aritech
Kategori: Sikkerhed
Model: SHATTERPRO 3

Har du brug for hjælp?

Hvis du har brug for hjælp til Aritech SHATTERPRO 3 stil et spørgsmål nedenfor, og andre brugere vil svare dig