Læs gratis den danske manual til Crestron CLXI-4HSW4 (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 4.9 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Crestron CLXI-4HSW4, eller vil du spørge andre brugere om produktet?

Side 1/4
CLTI- & CLXI-4HSW4
Terminal Block & Module Locations (Single-wide Enclosure)
Functional Summary
MODULETERMINAL
BLOCK
GROUNDING
TERMINAL
BLOCK
The Crestron
4-Feed, 4-High-Inrush Switch Terminal
Block and Module (CLTI-4HSW4 and CLXI-4HSW4,
respectively), are considered a single entity and must be
used together. They ship separately to permit termination
of the field wiring to the CLTI-4HSW4 prior to
installation of the CLXI-4HSW4, as described in this
guide. They can be mounted in any Crestron Automation
Enclosure (CAEN-Series Enclosures). The terminal block
is designed to terminate four circuit feeds (HOT and
NEUTRAL) and distribute the controlled circuits (LOAD)
to the fixtures. The module connects to the terminal block
and performs switching (non-dim) control of four
incandescent, low voltage, neon, cold cathode,
fluorescent, or HID lighting loads, or motor loads. The
maximum load is 8 amps (1 HP) for each controlled
circuit (32 amps total per module). The unit requires
230VAC 50 Hz input voltage. An oversize heat sink
dissipates heat efficiently. There are LEDs on the module
to indicate communication to a Cresnet
network, input
power to the module, and output power to the load.
NOTE: When connecting to an Arc Fault Breaker,
the load should not exceed 1000 watts.
Terminal Block & Module Locations (Double-wide Enclosure)
Installation
GROUNDING TERMINAL BLOCKS
MODULETERMINAL BLOCK
(LEFT)
TERMINAL BLOCK
(RIGHT)
Terminal block and module must be mounted into a
Crestron Automation Enclosure by a licensed electrician,
in accordance with all national and local codes.
CAUTION: This equipment is for indoor use only
and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be
0°C to 40°C (32°F to 104°F). The relative humidity
must be 0% to 90% (non-condensing).
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are
installed along the right side of single-wide enclosures
and side-by-side in the center of double-wide enclosures.
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so
that they can be properly wired. Refer to the illustrations
shown in the next column when considering the location
of terminal blocks and modules within an enclosure.
NOTE: Modules and terminal blocks must be
installed into the lowest available spaces and
continue toward the top of the enclosure.
Crestron Electronics, Inc. Installation Guide – DOC. 6412
15 Volvo Drive Rockleigh, NJ 07647 (2013808)
Tel: 888.CRESTRON 11.05
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Terminal Block & Module Crestron CLTI- & CLXI-4HSW4
Terminal Block Installation and Field
Wiring
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Single-wide and Left Side Double-wide Enclosures)
TO
LOAD
4
TO
LOAD
3
TO
LOAD
2
TO
LOAD
1
HOT 1 (*)
HOT 2 (*)
HOT 3 (*)
HOT 4 (*)
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
GROUNDING
TERMINAL
BLOCK
GND
TERMINAL
BLOCK
LEFT
SIDE
WIRING
LABEL
AREA FOR
MODULE
LOCATION
LABEL
BYPASS
JUMPERS
(*) FROM 10 OR 16 AMP
CIRCUIT BREAKER
1. Use the two supplied self-tapping pan Phillips
screws (8B x ¼-inch (6 mm) length) to secure
the terminal block and the appropriate (left or
right) wiring label to the Crestron Automation
Enclosure. The wiring label lies beneath the
terminal block as shown in the two wiring
diagrams on this page.
NOTE: Both left and right wiring labels are
provided. The left-side labels are common for both
single and double-wide enclosures. The right-side
labels are only used in double-wide enclosures since
the modules and terminal blocks along the right side
must be inverted when mounting.
CAUTION: On this terminal block there are four
distinct circuits. Bypass jumpers are installed on the
on the brown and red sections of each circuit on the
terminal block to allow testing of the circuits and to
protect the module during installation. When properly
secured by two screws, each bypass jumper on a
circuit shorts the hot to switch so that the circuit is
receiving power. Do not remove any bypass jumpers
until all feed and load wiring has been completed, the
circuit has been tested for electrical faults, and the
module has been installed. Refer to “Module
Installation” on the next page. Jumpers are also
installed on the blue sections of the terminal block
and tie the neutrals together. These jumpers should
never be removed.
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Right Side Double-wide Enclosures)
TO
LOAD
1
TO
LOAD
2
TO
LOAD
3
TO
LOAD
4
HOT 1 (*)
HOT 2 (*)
HOT 3 (*)
HOT 4 (*)
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
GROUNDING
TERMINAL
BLOCK
GND
TERMINAL
BLOCK
RIGHT
SIDE
WIRING
LABEL
AREA FOR
MODULE
LOCATION
LABEL
BYPASS
JUMPERS
(*) FROM 10 OR 16 AMP
CIRCUIT BREAKER
NOTE: Use copper conductors only – rated 75°C
2. With the circuit breaker turned off, connect the
circuit feed (HOT and NEUTRAL) and
controlled circuit (LOAD) wires to the terminal
block per the markings provided on the wiring
label (as shown in the diagrams on this page).
Terminal blocks accept one 2.5 - 6.0 mm
2
wire.
Wires should be stripped to 12 mm. Tighten
terminal blocks to 1 Nm. Do not over tighten.
3. Grounding terminal blocks are available in the
cabinet for termination of ground wires. Tighten
to 4 Nm (2.5 - 6.0 mm
2
), 4.5 Nm (10.0 mm
2
), or
5.1 Nm (16 - 25 mm
2
).
4. Test the circuit for electrical faults by turning on
the circuit breaker and checking that the breaker
does not trip and that power is delivered to the
loads.
2 Terminal Block & Module: CLTI- & CLXI-4HSW4 Installation Guide – DOC. 6412


Produkt Specifikationer

Mærke: Crestron
Kategori: Ikke kategoriseret
Model: CLXI-4HSW4
Bredde: 176 mm
Dybde: 87 mm
Højde: 193 mm
Antal pr. pakke: 1 stk

Har du brug for hjælp?

Hvis du har brug for hjælp til Crestron CLXI-4HSW4 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Crestron Manualer

Crestron

Crestron CLXI-4HSW4 Manual

24 September 2025
Crestron

Crestron GLD-LED-50W Manual

24 September 2025
Crestron

Crestron TPS-4LW Manual

23 September 2025
Crestron

Crestron Zūm Manual

23 September 2025
Crestron

Crestron SIMPL Manual

23 September 2025
Crestron

Crestron UC-FCM-T Manual

23 September 2025
Crestron

Crestron CBLR-HD Manual

23 September 2025
Crestron

Crestron CBLR-AUDIO Manual

23 September 2025
Crestron

Crestron AM-3200-WF Manual

23 September 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Celly

Celly TCSCREEN2C1A45W Manual

24 September 2025
T'nB

T'nB CHCARW1V2 Manual

24 September 2025
Prebena

Prebena 1GP-ALK35 Manual

24 September 2025
Konig & Meyer

Konig & Meyer 260/1 Manual

24 September 2025
Midea

Midea H1-(5-20)-E0 Manual

24 September 2025
T'nB

T'nB CHNBTC65W Manual

24 September 2025
Zen Living

Zen Living 350010 Manual

24 September 2025