Læs gratis den danske manual til Danfoss VLT MCD 202 (12 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 27 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 14 anmeldelser. Har du et spørgsmål om Danfoss VLT MCD 202, eller vil du spørge andre brugere om produktet?

Side 1/12
MCD Modbus Module Instructions Important User Information
MG17F702 - VLT® is a registered Danfoss trademark 1
INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE
Order Code: 175G9000
1. Important User Information
Observe all necessary safety precautions when controlling the soft starter remotely. Alert
personnel that machinery may start without warning.
It is the installer's responsibility to follow all instructions in this manual and to follow correct
electrical practice.
Use all internationally recognised standard practice for RS-485 communications when installing
and using this equipment.
2. Installation
CAUTION
Remove mains and control voltage from the soft starter before attaching or removing
accessories. Failure to do so may damage the equipment.
2.1. Installation Procedure
1. Remove control power and mains supply from the soft starter.
2. Attach the Modbus Module to the starter as shown.
3. Apply control power to the soft starter.
2.2. Physical installation
1. Fully pull out the top and bottom retaining clips on the module.
2. Line up the module with the comms port slot.
3. Push in the top and bottom retaining clips to secure the module to the starter.
177HA528.11
Remove the MCD Modbus Module using the following
procedure:
1. Take the module off-line.
2. Remove control power and mains supply from the
soft starter.
3. Disconnect all field wiring from the module.
4. Fully pull out the top and bottom retaining clips on
the module.
5. Pull the module away from the soft starter.
177HA378.11
Installation MCD Modbus Module Instructions
MG17F702 – VLT® is a registered Danfoss trademark 2
2.3. Adjustment
Network communication parameters must be set on the Modbus Module. DIP switch settings take
effect on the power-up of the Modbus Module via the soft starter.
A
B
177HA262.12
Protocol
Address
Baud rate
Parity
Timeout (seconds)
DIP switch
Example: Address = 24
2.4. Master Configuration
For standard Modbus 11-bit transmission, the Master must be configured for 2 stop bits with No
Parity and 1 stop bit for odd or even parity.
For 10-bit transmission, the Master must be configured for 1 stop bit.
In all cases, the Master baud rate and slave address must match those set on the Modbus Module
DIP switches.