Læs gratis den danske manual til Festo CPX-FB36 (3 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 24 personer og har en gennemsnitlig bedømmelse på 4.5 stjerner ud af 12.5 anmeldelser. Har du et spørgsmål om Festo CPX-FB36, eller vil du spørge andre brugere om produktet?

Side 1/3
Bus node
CPX-FB36
Festo SE & Co. KG
Postfach
73726 Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description 8067482
1611a
[8067484]
Original: de
Bus node CPX-FB36 English. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Use for intended purpose
The module described in this document is intended for use as a participant in net
works with the protocols EtherNet/IP or Modbus TCP in an industrial environment.
The module is intended exclusively for use in CPX terminals from Festo for installa
tion in machines or automated systems and may be used only in the following
ways:
in an excellent technical status
in original status without unauthorised modifications, except for the adapta
tions described in this documentation
within the limits of the product defined through the technical data.
Outside of industrial environments, e.g. in commercial and mixed-residential
areas, actions to suppress interference may have to be taken.
You will find detailed information in the following documentation:
Description on the module (è CPX-FB36-…)
CPX system description (è P.BE-CPX-SYS-…).
EtherNet/IP®, MODBUS®, SPEEDCON® are registered trademarks of the
respective trademark holder in certain countries.
2 Safety
Before assembly or installation work, switch off the power supply, switch off the
compressed air supply, exhaust any pneumatic components.
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1/EN 60204-1.
Observe the handling specifications for electrostatically sensitive devices.
Seal unused connections with cover caps to achieve the required degree of
protection.
Use connection hardware with the required degree of protection.
Observe specifications in the description for the module and the CPX system
description.
Place only a completely mounted and wired CPX terminal into operation.
3 Connection and display components
1
2
3
4
1LED indicators
2Network connections [X1], [X2]1)
3DIL switches
4Service interface
2)
1) 2× socket, M12, D-coded, 4-pin
2) Socket, M12, A-coded, 5-pin; for the operator unit CPX-MMI or Festo Maintenance Tool CPX-FMT
Fig. 1
3.1 Network connections
There are two 4-pin, D-coded M12 sockets on the bus node for the network con
nection. The sockets are compatible with SPEEDCON plugs. Both connections have
Auto-Negotiation and Crossover Detection (factory setting).
When crossover detection is activated, the bus node automatically
exchanges the transmitted and received data.
If Crossover detection is deactivated, assignment of the pins for transmit
ted and received data at the XP2 connection is crossed. As a result, several
bus nodes in a row can each be connected with a patch cable.
Connection1) Pin X12) X22)
Signal Explanation Signal Explanation
1 TD+ Transmitted
data +
RD+ Received data +
2 RD+ TD+ TransmittedReceived data +
data +
3 TD– Transmitted
data
RD– Received data
4 RD– TD– TransmittedReceived data
data
3) Shield ShieldFunctional earth Functional earth
1) Socket, M12, D-coded, 4-pin
2) Pin activation with deactivated crossover detection
3) Housing; equipotential bonding è CPX system description P.BE-CPX-SYS-…
Fig. 2
If the QuickConnect function has been activated, the crossover detection
function is not available.
3.2 LED indicators – normal operating status
Behaviour of the LED indicators in normal operating status:
The green LEDs [PS], [PL], [MS] and [NS] are illuminated.
The green LEDs [TP1] and/or [TP2] light up or flash.
The red LED [SF] is off.
The yellow LED [M] lights up only whenSystem start with saved paramet
erisation and CPX extension” is set.
Network-specific LED indicators1) CPX-specific LED indicators2)
MS (red, green) Module status PS (green) Power system
NS (red, green) Network status PL (green) Power load
TP1 (green) “Link/traffic” X1 SF (red) System Failure
3)
TP2 (green) “Link/traffic” X2 M (yellow) Modify4)
1) Detailed information (è Description on the module CPX-FB36-…)
2) Detailed information (è CPX system description P.BE-CPX-SYS-…)
3) Flashes in case of error, error diagnostics (è CPX system description P.BE-CPX-SYS-…)
4) Parameterisation revised or “Forceactive.
Fig. 3
4 Mounting and removal
Warning
Uncontrolled movements of the actuators and loose tubing, undefined switching
states of the electronic components
Injury caused by moving parts, damage to machine and to system
Before mounting and installation work:
Switch off the power supply.
Switch off the compressed air supply.
Exhaust any pneumatic components.
2
1
3
2
1Bus node CPX-FB36
2Screw
3Interlinking block
Fig. 4
4.1 Installation
Note
Material damage due to incorrect mounting
Select screws that are suitable for the material of the interlinking block:
plastic: thread-cutting tapping screws
Metal: Screws with metric thread.
When ordering a single module, all required screws are supplied.
1. Check seal and sealing surfaces. Replace damaged parts.
2. Push the module carefully and without tilting into the interlinking block up to the
stop.
3. Turn the screws into the existing thread.
4. Tighten the screws in diagonally opposite sequence. Tightening
torque:1 Nm ± 10 %.
4.2 Dismantling
1. Unscrew screws.
2. Pull the module without tilting out of the interlinking block.
5 Power supply
The operating and load voltage supply is fed in via interlinking blocks or end plates
(è CPX system description P.BE-CPX-SYS-…).
Warning
Electric voltage
Injury caused by electric shock, damage to machine and to system
For the electrical power supply, only use PELV circuits in accordance with
IEC 60204-1/EN 60204-1.
Use only voltage sources that ensure a reliable electric separation from the
mains network in accordance with IEC 60204-1/EN 60204-1.
Observe the requirements of IEC 60204-1/EN 60204-1 for PELV circuits.
Always connect all circuits for operating and load voltage supply U
EL/SEN, UVAL
and UOUT.
6 DIL switch elements
1 2
3
1DIL switch 1:
– DIL 1.1: operating mode
– DIL 1.2: network protocol
2DIL switch 2: diagnostic mode and
data field size1)
3DIL switch 3: IP addressing
1) Setting of the data field size is available only in the remote controller operating mode.
Fig. 5
6.1 DIL switch 1 – operating mode and network protocol
Setting DIL switch 1.1 Operating mode
DIL 1.1: OFF
(Factory setting)
Remote I/O
All functions of the CPX terminal are controlled directly by
the higher-order controller. A control block integrated into
the CPX terminal (e.g. CPX-CEC or CPX-FEC) works as a
passive function module without controller.
DIL 1.1: ON Remote controller
A control block integrated into the CPX terminal
(e.g. B. CPX-CEC or CPX-FEC) takes over I/O control. This
operating mode is only useful if a control block is integ
rated into the CPX terminal.
Fig. 6
Setting DIL switch 1.2 Network protocol
DIL 1.2: OFF
(Factory setting)
EtherNet/I P
The CPX terminal uses the EtherNet/IP network protocol.
DIL 1.2: ON Modbus TCP
The CPX terminal uses the Modbus TCP network protocol.
Fig. 7
6.2 DIL switch 2 – diagnostic mode or data field size
The function of DIL switch 2 is dependent on the set operating mode of the
CPX terminal (è Fig. 6).
Setting DIL switch 2 Diagnostics mode
(Remote I/O)1)
Data field size
(Remote controller)2)
DIL 2.1: OFF
DIL 2.2: OFF
(Factory setting)
I/O diagnostics interface and
status bits switched off
8 byte I/8 byte O for
communication of the bus
node with a control block
(e. B. CPX-FEC)
DIL 2.1: ON
DIL 2.2: OFF
I/O diagnostics interface is
switched on
32 byte I/32 byte O for
communication of the bus
node with a control block
(e. B. CPX-FEC)3)
DIL 2.1: OFF
DIL 2.2: ON
Status bits switched on 16 byte I/16 byte O for
communication of the bus
node with a control block
(e. B. CPX-FEC)
DIL 2.1: ON
DIL 2.2: ON
Reserved 64 byte I/64 byte O for
communication of the bus
node with a control block
(e. B. CPX-FEC)4)
1) Setting of the diagnostic mode is available only in the remote I/O operating mode.
2) Setting of the data field size is available only in the remote controller operating mode.
3) Revision 12 and above
4) Revision 13 and above
Fig. 8
6.3 DIL switch 3 – IP addressing
Setting DIL switch 3 IP addressing
1 2 3 4 5 6 7 8
3.8:
3.7:
3.6:
3.5:
3.4:
3.3:
3.2:
3.1:
27 =
26 =
25 =
24 =
23 =
22 =
21 =
20 =
128
64
32
16
8
4
2
1
The type of addressing or the host ID of the IP address of the
bus node is set via DIL switch elements 3.1 ... 3.8.
Possible settings:
0 = Dynamic addressing via DHCP/BOOTP
1 254 = Permissible address range
255 = Reset all IP parameters to factory setting
Factory setting: 0
Example:
21 + 22 + 25 = 2 + 4 + 32 = 38 (host ID)
Set IP address: 192.168.1.038
Fig. 9
7 Ensuring the degree of protection
Note
Short circuit
Malfunction or damage to the electronics
Use connection technology with the required degree of protection e.g. plug
NECU-M-S-D12G4-C2-ET (è www.festo.com/catalogue).
Use cover caps to seal unused connections, e.g. cover cap ISK-M12
(è www.festo.com/catalogue).
Mount the DIL switch cover:
Check seal, place cover and push it down, tighten screws. Tightening torque
maximum 0.4 Nm.
Connection Connecting hardware Cover cap
Network connection (M12) Plug NECU-M-S-D12G4-C2-ET ISK-M12
Service interface (M12) Connecting cable KV-M12-M12-…
1) ISK-M12
1) Connecting cable for operator unit (CPX-MMI)
Fig. 10
8 Parameterisation
The CPX terminal and the module described here can be parameterised with the
operator unit (CPX-MMI), the Festo Maintenance Tool (CPX-FMT) software or the
higher-level system.