Læs gratis den danske manual til Sauermann COST-S (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 4.9 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Sauermann COST-S, eller vil du spørge andre brugere om produktet?

Side 1/4
COST-S
CO Stats
CO detector
DATA SHEET
Parameter Accuracy Measuring range Resolution*
CO ±3 ppm or 3% of the reading value From 0 to 500 ppm 0.1 ppm
Technical features
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.
RCR relay output,
3 A / 240 Vac (NC),
power supply 24 Vac/Vdc
ABS V0 IP20 housing
“¼ turn” system mounting
with wall-mount plate
Housing with simplied
mounting system
Visual and audible alarm,
red led in front
Measuring range
from 0 to 500 ppm
CO
CO
Output 1 RCR relay. NO (normally opened): 5A / NC (normally closed): 3A / 240 Vac.Common mode voltage <30 Vac
Power supply 24 VAC/VDC ±10%
Consumption 3 VA
Relay and alarm status Red led in front and internal buzzer (70 dB at 10 cm)
European directives 2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Electrical connection Terminal block for cables Ø0.05 to 2.5 mm
2
. Carried out according to the code of good practice
PC communication USB-mini Din cable
Environment Air and neutral gas
Measured parameter
Unit of measurement ppm
Type of sensor Electrochemical sensor
Life-time of the sensor 5 years
Response time T
63
= 35 s
Type of uid Air et gaz neutre
Conditions of use
(°C/%RH/m)
From 0 to +50°C. In non-condensing condition.
From 0 to 2000 m.
Storage temperature From -10 to +70°C
General features
Material ABS V0 as per UL94
Protection IP20
Display
LCD 10 digits. Size: 50 x 17 mm
Height of digits:
Values: 10 mm; Units: 5 mm
Weight 138 g
Features of the housing
Connections
Inside the front housing
Removable front face
Fixed back housing
1
2 3
4
5
6
7
8
Electrical connections as per NFC15-100 standard
NO COM NC
1 2 3 4 5 6 7
-
+
Power supply
24 Vdc
or
N L
N L
~ ~
~ ~
6 7
Power supply
24 Vac
Class II
This connection must be made by a
qualied and trained technician. To make
the connection, the transmitter must not
be energized.
Settings and use of the transmitter
Thresholds conguration
The button allows to activate or not an alarm (threshold), to set the action of the alarm (edge), to set the threshold(s) value, to
set the time-delay and to acknowledge the alarm.
Working principle:
- By pressing on the button more than 3 seconds, you can validate the setting and go to the next setting.
- By pressing quickly on the button, you can increment a value and scroll down the different option or values.
NO: normally opened
COM: common
NC: normally closed
1. Electrochemical sensor
2. Inactive switch
3. Active switch
4. LCC-S software connection
5. Alarm led
6. Button for settings
7. Relay terminal block
8. Power supply terminal block


Produkt Specifikationer

Mærke: Sauermann
Kategori: Ikke kategoriseret
Model: COST-S

Har du brug for hjælp?

Hvis du har brug for hjælp til Sauermann COST-S stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Sauermann Manualer

Sauermann

Sauermann COST-S Manual

19 August 2025
Sauermann

Sauermann TH 210-R Manual

19 August 2025
Sauermann

Sauermann HST Manual

19 August 2025
Sauermann

Sauermann CP 110 Manual

19 August 2025
Sauermann

Sauermann HM 110 Manual

15 August 2025
Sauermann

Sauermann Si-60 Manual

15 August 2025
Sauermann

Sauermann SI-1801 Manual

14 August 2025
Sauermann

Sauermann CTV 210 Manual

14 August 2025
Sauermann

Sauermann Si-C320 Manual

14 August 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer