Data may change without any notice
* Adjustable with the RCC-02/-03
** These features are valid only when using the cooling module ECF-01.
With -01 at the end of the reference, means 120V/60Hz. Available for all Xtenders except XTH 8000-48
XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH 8000-48
Nominal battery voltage 12 Vdc 24 Vdc 48 Vdc
Input voltage range 9.5 - 17 Vdc 19 - 34 Vdc 38 - 68 Vdc
Continuous power @ 25°C 2500 VA 4500 VA 5000 VA 7000 VA
Power 30 min. @ 25°C 3000 VA 5000 VA 6000 VA 8000 VA
Power 5 sec. @ 25°C 7.5 kVA 12 kVA 15 kVA 21 kVA
Maximum load Up to short-circuit
Asymmetric load Up to Pcont.
* Load detection (stand-by) 2 to 25 W
Maximum efciency 93 % 94 % 96 %
Consumption OFF/Stand-by/ON 1.2 W / 1.4 W / 14 W 1.4 W / 1.8 W / 18 W 1.8 W / 2.2 W / 22 W 1.8 W / 2.4 W / 30 W
* Output voltage Pure sine wave 230 Vac (± 2 %) / 120 Vac
* Output frequency Adjustable 45 - 60 Hz
± 0.05 % (crystal controlled)
Harmonic distortion < 2 %
Overload and short-circuit protection Automatic disconnection with 3 time restart attempt
Overheat protection Warning before shut-off - with automatic restart
6 steps: Bulk, Absorption, Floating, Equalization, reduced oating, periodic absorption
Number of steps, thresholds, end current and times completely adjustable with the RCC-02/-03
* Maximum charging current 160 A 140 A 100 A 120 A
* Temperature compensation With BTS-01 or BSP 500/1200
Power Factor Correction (PFC) EN 61000-3-2
XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH 8000-48
* Input voltage range 150 to 265 Vac / 50 to 140 Vac
Input frequency 45 to 65 Hz
Input current max. (transfer relay) / Output current max.
50 Aac / 56 Aac 50 Aac / 80 Aac
Multifunction contacts 2 independent contacts (potential free 3 points, 16 Aac / 5 Adc)
Weight 34 kg 40 kg 42 kg 46 kg
Dimensions h/w/l [mm] 230 / 300 / 500 230 / 300 / 500 230 / 300 / 500
EU declaration of conformity
Low Voltage Directive (LVD) 2014/35/EU:
Electromagnetic Compliance (EMC) Directive 2014/30/EU:
- EN 62040-2:2006, EN 61000-3-2:2014, EN 61000-3-12:2011
Operating temperature range -20 to 55°C
Relative humidity in operation 95 % without condensation
Ventilation Forced from 55°C
Acoustic level <40 dB / <45 dB (without/with ventilation)
ISO Certication 9001:2008 / 14001:2004
Remote control RCC-02 or RCC-03
Communication sets Xcom-LAN /w Xcom-GSM / Xcom-SMS
Battery Status Processor BSP
Remote Control Module RCM-10 (3 m)
2 aux. contacts module ARM-02
Battery temp. sensor BTS-01 (3 m)
Communication cable for 3ph and // CAB-RJ45-8-2