System Sensor CO1224TR Manual


Læs gratis den danske manual til System Sensor CO1224TR (4 sider) i kategorien Gasdetektor. Denne vejledning er vurderet som hjælpsom af 18 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 9.5 anmeldelser. Har du et spørgsmål om System Sensor CO1224TR, eller vil du spørge andre brugere om produktet?

Side 1/4
CO1224T/CO1224TR
Carbon Monoxide Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
SPECIFICATIONS
Electrical Specifications
System Voltage Nominal: 12/24 VDC
Min: 10 VDC
Max: 33 VDC
Avg. Standby Current: 20 mA
Max Alarm Current: 40 mA (75 mA test)
Alarm Contact Ratings: 30 VDC @ 0.5 A
Trouble Contact Ratings: 30 VDC @ 0.5 A
Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft)
Max. Start-up Capacitance: 20 uF
Physical Specifications
Operating Temperature Range: 0° to 40°C (32° to 104°F)
Operating Humidity Range: 22 – 90% %RH
Diameter: 6.0˝
Height: 1.2
Weight: 7 oz
Wire Gauge Acceptance: 14-22 AWG
NOTICE: This manual shall be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
Listed to standard 2075
Round shape allows for mounting in aesthetically demanding areas
Six-wire, system monitored
Optional CO detector replacement plate for previously installed detectors
Local sounder
Low current draw
Alarm relay, Form C
Trouble relay, Form A
Dual LED’s
Test/Hush button
SEMS wiring terminals
Mount to single gang electrical box or surface mount to wall or ceiling
Optional drywall anchors included
TABLE 1. DETECTOR OPERATION MODES:
OPERATION
MODE GREEN LED RED LED SOUNDER
Normal
(standby)
Blink 1
per minute OFF OFF
Alarm OFF Temp 4*pattern Temp 4* pattern
Alarm Test OFF Temp 4 pattern Temp 4 pattern
RealTest®
Mode
Blink 1
per second OFF Temp 4 pattern
(after CO is sprayed)
End of Life OFF OFF OFF
CO Trouble OFF Blink 1
per minute OFF
Power Loss/
Cell Fault OFF OFF OFF
Alarm Test: Will send alarm signal to panel.
Hush feature/Alarm Silence: If required, the audible alarm can be silenced
for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light
will continue to flash in temp-4 pattern. If carbon monoxide is still present
after the 5 minute hush period, the audible alarm will sound. The hush facility
will not operate at levels above 350 ppm (parts per million) carbon monoxide.
RealTest® Alarm Silence: Alarm will automatically silence after about 20 sec-
onds of alarm from spraying canned CO into the detector. Alarm Reset: Alarm
automatically resets after CO has cleared from the sensor.
Trouble feature: When the sensor supervision is in a trouble condition (e.g.
such as a sensor that has been tampered with, or the cell itself has prema-
turely dried out due to environmental conditions, etc.), the detector will send
a trouble signal to the panel. The detector must then be replaced. The green
LED turns off and the red LED blinks every minute when the detector is in
trouble.
End of Life Timer feature: When the detector has reached the end of its life,
the trouble contact will open. This indicates that the CO sensor inside the
detector has passed the end of its life and must be replaced. This detector’s
lifespan is approximately ten years from the date of manufacture. The green
LED turns off when the detector is in trouble. Periodically check the “Replace
by” sticker located under the detector cover. The detector must be replaced by
this date. Refer to Detector Replacement on page 3.
Per UL 2075, it is mandatory that a trouble signal be sent to the panel
upon CO cell trouble or cell end of life. Refer to Figure 4 for wiring of the
trouble relay.
I56-3111-012
LIVING
ROOM
BEDROOM BEDROOM
BEDROOM
KITCHEN
TO
BR
CLOSED
DOOR
BASEMENT
GARAGE
CARBON MONOXIDE/SMOKE ALARM
LOCATION FOR MULTI-LEVEL RESIDENCE
S0295-01
FIGURE 1. ALARM LOCATION DIAGRAM:
1 I56-3111-012
10-28
INSTALLATION GUIDELINES
Ceiling: Detector should be at least 12 inches from any wall.
Wall: Detector should be at least as high as a light switch, and at least six
inches from the ceiling.
Do not install in any environment that does not comply with the detec-
tor’s environmental specifications
Install in accordance with NFPA 720–the Standard for the Installation of
Carbon Monoxide (CO) Detection and Warning Equipment
As of 2009, NFPA 720 defines standards for both commercial and resi-
dential installations of CO detectors. If the installation can be interpreted
as a commercial application, consult the section of NFPA 720 that out-
lines commercial applications.
For example, Chapter 5.5.5.3.1 states that carbon monoxide detectors
shall be installed in accordance with manufacturers published instruc-
tions in the following locations:
(1) On the ceiling in the same room as permanently installed fuel burn-
ing appliances
(2) Centrally located on every habitable level and in every HVAC zone of
the building
If the installation can be interpreted as residential, consult the section of
NFPA 720 that outlines residential applications.
For example, chapter 9.4.1.1 states that carbon monoxide alarms or
detectors shall be installed as follows:
(1) Outside each separate dwelling unit sleeping area in the immediate
vicinity of the bedrooms
(2) On every level of a dwelling unit, including basements
(3) Other locations where required by applicable laws, codes or standards
MOUNTING
The CO1224T/CO1224TR can be ceiling-mounted or wall-mounted:
1. To a single gang box.
2. Direct mount to ceiling or to wall using drywall fasteners.
INSTALLATION
WIRING INSTALLATION GUIDELINES
All wiring must be installed in compliance with the NFPA 70, National Electrical
Code, applicable state and local codes, and any special requirements of the local
Authority Having Jurisdiction (AHJ).
Proper wire gauges should be used. The conductors used to connect carbon
monoxide detectors to the alarm control panel and accessory devices should
be color-coded to reduce the likelihood of wiring errors. Improper connections
can prevent a system from responding properly in the event of a CO.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire
connections are made by stripping approximately
14
˝ of insulation from the
end of the feed wire, inserting it into the proper base terminal, and tightening
the screw to secure the wire in place. Do not put wires more than 2 gauge
apart under the same clamping plate.
WARNING: This product does not have a local audible trouble signal, and
may fail without supervision if trouble loop remains unconnected.
WARNING: Gas detectors on a zone that is bypassed may not signal a trouble
condition. Do not bypass zones used for gas detectors.
Wiring diagrams located on page 4, Figure 4.
WARNING
Remove power from alarm control unit or initiating device circuits before in-
stalling detectors.
1. Using a small, flat head screw driver, push in the small tab located on the
underside of the detector. Once the snap is loosened, lift the bottom end
of the cover up and unhinge the top to remove the cover.
2. Wire the detector base screw terminals per Figure 5.
3. Screw the base of the detector onto a single gang electrical box, or to the
surface of the wall or ceiling. Use the hardware included in the packaging.
4. If mounting with the System Sensor replacement plate model CO-PLATE*:
* Hold replacement plate over desired mounting area.
* Use hook feature to hold CO1224T onto the replacement plate.
* Mount detector and plate together using hardware provided with the
CO1224T.
5. Hinge the top portion of the cover onto the base; with the cover at a 45
degree angle, fit the hinges into the slots of the base.
6. Push the unhinged bottom portion of the cover down until it snaps into place.
7. After all detectors have been installed, apply power to the alarm control unit.
8. Test each detector as described in Testing.
9. Notify the proper authorities that the system is in operation.
CAUTION
Airborne dust particles can enter the detector. System Sensor recommends the
installation of detectors after construction or any other dust producing activ-
ity. Carbon monoxide detectors are not to be used with detector guards unless
the combination has been evaluated and found suitable for that purpose.
TESTING
Detector must be tested after installation.
NOTE: Before testing, notify the proper authorities to avoid any nuisance
alarms.
Ensure proper wiring and power is applied. After power up, allow 80 seconds
for the detector to stabilize before testing.
Test the CO1224T/CO1224TR detector as follows:
1. A test button is located on the detector housing (See Figure 4).
2. Use the tip of your finger to press and hold the test button for 1-4
seconds.
3. If the sounder beeps twice in the Temporal 4 tone and the LED’s light up,
the detector is operational.
4. The detector now enters Realtest speed up test mode indicated by a
quickly blinking green LED. See Functional Gas Test section for instruc-
tions on testing with canned CO.
If a detector fails the above test method, its wiring should be checked. If the
detector still fails after rewiring, it should be replaced.
S0320-00
FIGURE 2. MOUNTING OF DETECTOR:
CO1224T CO1224TR
S0296-01
2 I56-3111-012
10-28


Produkt Specifikationer

Mærke: System Sensor
Kategori: Gasdetektor
Model: CO1224TR

Har du brug for hjælp?

Hvis du har brug for hjælp til System Sensor CO1224TR stil et spørgsmål nedenfor, og andre brugere vil svare dig




Gasdetektor System Sensor Manualer

Gasdetektor Manualer

Nyeste Gasdetektor Manualer

ORNO

ORNO OR-DC-636 Manual

15 Juni 2025
Alecto

Alecto GA11 Manual

9 Juni 2025
Carel

Carel GLD Mini Manual

4 Marts 2025
Kidde

Kidde C3010D-CA Manual

10 Januar 2025
Joy-It

Joy-It SEN-MQ7 Manual

27 December 2024
Vimar

Vimar 16592 Manual

15 December 2024
Aeroqual

Aeroqual AQ-500 Manual

13 December 2024
Protector

Protector C11-L Manual

11 December 2024
Pentatech

Pentatech GA60 Manual

24 November 2024