Air King AKHV160 Manual


Læs gratis den danske manual til Air King AKHV160 (8 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 13 personer og har en gennemsnitlig bedømmelse på 4.8 stjerner ud af 7 anmeldelser. Har du et spørgsmål om Air King AKHV160, eller vil du spørge andre brugere om produktet?

Side 1/8
IMPORTANT INSTRUCTIONS - OPERATING MANUAL
SAVE THESE INSTRUCTIONS
www.airkinglimited.com
6728104 Rev. B 5-20 1 of 8
Exhaust Recovery Ventilator
Heat Recovery Ventilator
AKEV, AKHV Series
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT
DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY
WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should always be followed to reduce
the risk of fire, electric shock and injury to person, including the following:
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK AND INJURY TO PERSON, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have questions,
contact the manufacturer.
b) Before servicing or cleaning the unit, disconnect the power cord from the electrical outlet.
c) ONLY qualified persons should attempt repair or service of any electrical/internal
component of this product.
WARNING: TO REDUCE THE RISK OF FIRE, REMOVE ANY SHIPPING
MATERIAL THAT MAY BE PRESENT INSIDE THE UNIT.
c) The cover to this unit is removable to ensure ease of access to internal components during
cleaning and servicing. USE CAUTION when opening or removing the cover of the unit to
avoid risk of personal injury or damage to the cover.
d) Installation work and electrical wiring must be done by qualified person(s) in accordance
with all applicable codes and standards, including fire-related construction.
e) Sufficient air is needed for proper combustion and exhausting of gases through the flue
(chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those published by the National Fire
Protection Association (NFPA) and the American Society for Heating, Refrigeration, and Air
Conditioning Engineers (ASHRAE), and the local code authorities.
f) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other
hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY. DO NOT USE
TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS.
g) Ducted fans must always be vented to the outdoors. Do not intake/exhaust into or from
between walls, ceilings, attics, crawl spaces or garages.
h) Do not run any air ducts directly above or closer than 2 ft to any furnace or its supply plenum,
boiler, or other heat producing appliance. If a duct has to be connected to the furnace return
plenum, it must be connected not closer than 9' 10" from this plenum connection to the
furnace (applies only in regions where the outside temperature falls below 32° F).
i) This unit must be grounded. The power cord is equipped with a three-prong grounded
plug that must be inserted into a matching receptacle. Under no circumstances should the
ground prong be cut off the plug. Where a two-prong wall receptacle is encountered, it
must be replaced with a properly grounded three-prong receptacle installed in accordance
with the National Electrical Code (NEC) and all applicable local codes and ordinances. This
work must be done by a qualified electrician, using copper wires only.
j) To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray,
construction dust, etc. off power unit. Turn unit OFF during construction or renovations.
k) Read all instructions before installing or using exhaust fan.
l) For residential installations only.
m) Must use suitable weather hood with insect screen to protect air intake.
n) DO NOT install this product in an unconditioned space—61º F ambient temperature is
recommended—or in a space/manner where maintenance and service might pose a risk of
personal injury or damage to this product.
o) If ductwork passes through unconditioned spaces, it must be insulated.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, DO
NOT USE THIS FAN WITH ANY SOLID-STATE SPEED CONTROL DEVICE.
p) This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
q) Due to the weight of the unit, two installers are recommended to perform installation.
WARNING: DO NOT USE IN KITCHENS.
WARNING: FOR INDOOR INSTALLATIONS ONLY.
WARNING: THE DUCTING FROM THIS FAN TO THE OUTSIDE OF THE
BUILDING HAS A STRONG EFFECT ON THE AIR FLOW, NOISE AND ENERGY USE OF THE
FAN. USE THE SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR BEST PERFORMANCE,
AND AVOID INSTALLING THE FAN WITH SMALLER DUCTS THAN RECOMMENDED. INSULATION
AROUND THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD GROWTH. FANS
INSTALLED WITH EXISTING DUCTS MAY NOT ACHIEVE THEIR RATED AIRFLOW.
INSTALLATION CONSIDERATIONS:
Prior to integrating this ERV/HRV with any other piece of mechanical equipment, i.e. furnace, air handler, combustion heating appliance, careful consideration must be given to system design and
integration to ensure compatibility and proper operation of both appliances. Do not connect the duct system of your ERV/HRV to any clothes dryer or kitchen exhaust fan duct system.
Whether installing this ERV/HRV as part of an independent system or to integrate it with a central heating/cooling system, use the procedure in this manual to ensure that the air flows of the ERV/HRV are
balanced. Only a properly balanced ERV/HRV will deliver maximum performance and energy efficiency.
Although this document contains guidelines for proper ERV/HRV sizing and installation, your ventilation system should be installed in conformance to the appropriate local or state building
regulations or National Building Code and/or ASHRAE “Good Engineering Practices”.
www.airkinglimited.com
6728104 Rev. B 5-20 2 of 8
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE UNIT IS UNPLUGGED BEFORE STARTING
INSTALLATION.
WARNING: TO REDUCE THE RISK OF FIRE, REMOVE ANY
SHIPPING MATERIAL THAT MAY BE PRESENT INSIDE THE UNIT.
SECTION 1
Preparing the Installation Area
CAUTION: INSTALLERS ARE RESPONSIBLE FOR THE PERFORMANCE
OF THE VENTILATION SYSTEM AND FOR ENSURING THAT ALL CODES AND
STANDARDS ARE MET.
1. Ensure that all the following conditions are met:
a) Do not mount the fresh air supply near a source of contaminated air such as
automotive exhaust, gas or propane exhaust, garbage containers or oil tanks.
b) Do not connect a dryer exhaust to an ERV/HRV.
c) Combustion appliances such as furnaces and water heaters must not draw
combustion air directly from an ERV/HRV.
d) Do not connect a kitchen range hood to any part of this system.
e) Do not install in attics or other unconditioned spaces (min. 61º F).
f) Do not install in enclosed garages.
g) Maintain straight duct runs as much as possible, using as few jointttings as possible.
h) Keep use of flexible ducting to a minimum.
i) Be sure to observe local codes regarding running and insulating ducts in
unconditioned spaces.
j) Poorly insulated ducts run in unconditioned spaces will hamper the efficiency of the unit.
SECTION 2
Installation Options
CAUTION: INTERCONNECTION WITH A FORCED AIR FURNACE DUCT
SYSTEM IS PERMISSIBLE; HOWEVER, YOUR ERV/HRV IS NOT INTENDED TO BE
CONNECTED TO ANY OTHER EQUIPMENT OR APPLIANCES.
NOTE: When selecting an installation option, consideration should be given to the increased
electrical consumption of the furnace fan. The way your ERV/HRV is installed may make a
significant difference to the electrical energy used. To minimize the electricity use of the
ERV/HRV, a stand-alone fully ducted installation is recommended. If you choose a simplified
installation that operates your furnace air handler for room-to-room ventilation, an electrically
efficient furnace that has an electronically commutated (EC) variable speed blower motor will
minimize your electrical energy consumption and operating cost. Installing a user-accessible
control with your product will improve comfort and may significantly reduce the products
energy use. Most building codes require a centrally located control with an on/off switch.
Fully Ducted System
1. This system uses an
independent duct system for
supply and exhaust air. The ERV/
HRV is controlled independently
of all other equipment. The best
results are achieved when:
• Each room of the space
is serviced with a vent
mounted in the ceiling or
high on an interior wall
(within 12" of the ceiling).
Vents are located deep
within a room, where they
will not short circuit or
create an uncomfortable draft.
Extended Exhaust System
1. This system uses the ERV/HRV in conjunction with a forced air furnace distribution
system. In this system the ERV/HRV supply air to the house is introduced into the return
duct of the forced air furnace. Separate
ductwork (not included) is used to transfer
stale air from the wet rooms to the ERV/HRV.
2. Extended System, Continuous Ventilation: The furnace fan may not need to run
continuously with this system. Check local code requirements. For improved supply air
distribution during continuous ventilation mode, the furnace may be interlocked to the ERV/
HRV. See Section 7 for interlock wiring and settings and Section 10 Control Wiring and Options.
3. Extended System, Intermittent Ventilation: If the ERV/HRV is operated intermittently,
the furnace fan should be interlocked with the ERV/HRV for good distribution of supply air
during high-speed ventilation conditions.
Simplified System
1. This system uses the furnace’s return plenum for both supply air distribution and exhaust
air collection. The exhaust air connection must be a minimum of 40 inches upstream of
the supply air connection to avoid short circuiting of the fresh air.
2. Simplified System, Continuous Ventilation & Intermittent Operation: For proper
supply air distribution with this system, and to prevent short circuiting in the return air
duct, the furnace fan must run during ventilation mode. Interlock the furnace and unit in
accordance with Section 7.
SECTION 3
Preparing the Unit
1. Unpack unit from the carton and confirm that all pieces are present. In addition to the unit
you should have:
Standard Filters Anti-Vibration Straps Removable Terminal Block
8 - Washers 4 - ½ Screws Drain Hose Assembly (HRV ONLY)
Core RVC8 Control Switch Instruction/Safety Sheet
2. Choose the location for your unit. To ensure the best air and sound performance, it is
recommended that the length of ducting and the number of elbows be kept to a minimum,
the radius of each elbow be as large as possible for the installation, and that insulated hard
ducting be used. The unit is designed to mount from the ceiling using the included anti-
vibration mounting straps. Avoid mounting the unit under bedrooms or other quiet areas.
NOTE: The unit must be installed into a location that can be easily accessed once installed.
3. No additional vibration deadening materials are needed for this fan.
SECTION 4
Mounting the Fan
1. Using appropiate sized mounting screws at
least #8 x 1.5" (not included) insert through
the included washers and hanging strap
grommets, then fasten to the mounting
surface. If mounting to a material other than
a wood joist use an appropriate mounting
method as determined by a professional.
2. Insert the included screws through the washers
and bottom grommets of the straps, then
fasten to the unit.
3. Pull down vertically on each strap while lifting
the bottom of the unit. Level the unit from right
to left and front to back.
4. To loosen strap, lift up on the buckle.
NOTE: Support unit and gently lift as you tighten each strap.
Fresh Air
Exhaust Air
Kitchen Living Room Bedroom
Laundry Bathroom
ERV
1
2
3
1 2 3
Grommet
Washer
Mounting Screw
(not included)
WasherStrap
Screw
Strap
Stale Air
Exhaust
Fresh Air
Furnace
Supply Air
From Outside
To Outside
Extended Exhaust System
Port configuration of ERV/HRV
may vary from unit to unit
Return Duct
Exhaust Air
Fresh Air
Furnace
From
Outside
To
Outside
Simplified System
Port configuration of ERV/HRV
may vary from unit to unit
40"
Min


Produkt Specifikationer

Mærke: Air King
Kategori: Ikke kategoriseret
Model: AKHV160

Har du brug for hjælp?

Hvis du har brug for hjælp til Air King AKHV160 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Air King Manualer

Air King

Air King EVD Manual

22 September 2024
Air King

Air King FAS Manual

26 August 2024
Air King

Air King F130D Manual

14 August 2024
Air King

Air King QMDB Manual

6 August 2024
Air King

Air King EVLDGH Manual

6 August 2024
Air King

Air King DL4D Manual

2 August 2024
Air King

Air King MD624 Manual

1 August 2024
Air King

Air King R120 Manual

1 August 2024
Air King

Air King EVLD Manual

31 Juli 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer