Broan QTXE110S Manual

Broan Ventilator QTXE110S

Læs gratis den danske manual til Broan QTXE110S (12 sider) i kategorien Ventilator. Denne vejledning er vurderet som hjælpsom af 26 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 13.5 anmeldelser. Har du et spørgsmål om Broan QTXE110S, eller vil du spørge andre brugere om produktet?

Side 1/12
Page 1
MODELS QTXE110S • QTXE110S2
WARNING
TO REDUCE THE RISK OF FIRE, ELEC-
TRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended
by the manufacturer. If you have questions,
contact the manufacturer at the address or
telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch
power off at service panel and lock the ser-
vice disconnecting means to prevent power
from being switched on accidentally. When
the service disconnecting means cannot be
locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be
done by a qualified person(s) in accordance
with all applicable codes and standards,
including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combus-
tion and exhausting of gases through the
flue (chimney) of fuel burning equipment to
prevent backdrafting. Follow the heating equip-
ment manufacturer’s guideline and safety
standards such as those published by the
National Fire Protection Association (NFPA),
and the American Society for Heating, Re-
frigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden
utilities.
6. Ducted fans must always be vented to the
outdoors.
7. Acceptable for use over a tub or shower when
connected to a GFCI (Ground Fault Circuit
Interrupter) - protected branch circuit.
8. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use
to exhaust hazardous or explosive materials
and vapors.
2. This product is designed for installation in flat
ceilings only. DO NOT MOUNT THIS PROD-
UCT IN A WALL.
3. To avoid motor bearing damage and noisy
and/or unbalanced impellers, keep drywall
spray, construction dust, etc. off power unit.
4. Please read specification label on product for
further information and requirements.
HUMIDITY SENSING FAN
READ AND SAVE THESE INSTRUCTIONS
CLEANING &
MAINTENANCE
Installer: Leave this manual
with the homeowner.
For quiet and efficient operation, long life,
and attractive appearance - lower or remove
grille and vacuum interior of unit with the
dusting brush attachment.
The motor is permanently lubricated and
never needs oiling. If the motor bearings
are making excessive or unusual noises,
replace the motor/blower wheel assembly.
SENSOR CLEANING
The humidity sensor is mounted in the grille.
The sensor will operate most reliably when
cleaned occasionally as follows:
1. Disconnect power at service entrance.
2. Remove the grille. Use a dry dustcloth,
clean toothbrush, or lightly vacuum to
clean sensor and grille. DO NOT USE
ABRASIVE CLOTH, STEEL WOOL
PADS, OR SCOURING POWDERS.
3. DO NOT USE cleaning sprays, solvents,
or water on or near the sensor!
OPERATION
The humidity control and fan can be op-
erated separately. Use a 1 or 2-function
wall control. Do not use a dimmer switch
to operate the humidity control or light.
See “Connect Wiring for details.
SENSOR OPERATION
This humidity-sensing fan responds to: (a)
rapid to moderate humidity increases and
(b) humidity above a 50%-80% relative
humidity (RH) set-point. (a) and (b) are
set with “HUMIDITY” adjustment. Fan may
occasionally turn on when environmental
conditions change. If the fan continuously
responds to changing environmental con-
ditions, “HUMIDITY” adjustment may be
required (see section below).
STATUS INDICATOR
This indicator can only be seen by looking
directly at it. Normal mode is 5-seconds on
and off. If it blinks rapidly for 5-seconds and
then off, check sensor connections on grille
and fan housing.
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be
energized by cycling its wall-mounted switch
if one is installed. Once the fan has been
turned on in this manner, it will remain on
for the set “MINUTES” period.
To manually energize the fan:
1. Go to Step 2 if switch is already on;
otherwise, turn switch on for more than
1 second.
2. Switch off for less than 1 second.
3. Switch back on and fan will turn on.
HUMIDITY ADJUSTMENT
“HUMIDITY” has been factory set for most
shower applications. If the fan is in a tub
area or is used for dampness control, the
“HUMIDITY” may need to be decreased
toward 50% RH. If the control is responding
too often to changing environmental condi-
tions, adjustment toward 80% RH may be
required. To adjust the “HUMIDITY”:
1. Turn power off at electrical service
panel.
2. Through the grille, locate the “HUMIDITY
screwdriver slot.
3. Using a small, flat-blade screwdriver,
carefully rotate “HUMIDITY” adjustment
toward 50 or 80.
4. Turn power on and check operation by
turning on shower or other humidity
source until fan turns on.
5. Repeat above steps if necessary.
TIMER ADJUSTMENT
This humidity-sensing fan has a timer. It is
user-adjustable from 5 to 60 minutes and is
factory-set at 20 minutes. The timer controls
how long the fan remains on (a) after rise
in humidity and (b) humidity level are both
below the user-adjustable HUMIDITY
setting or after being energized by cycling
power switch.
To adjust the timer:
1. Disconnect power at electrical service
panel.
2. Through the grille, locate the MINUTES”
screwdriver slot.
3. Using a small, flat-blade screwdriver,
carefully rotate “MINUTES” adjustment
to desired setting (5 to 60 minutes).
4. Check operation by cycling power switch
as instructed under “MANUAL ON WITH
TIMED OFF” or by turning on a humidity
source until fan turns on.
5. Check timer setting with watch or clock
after turning humidity source off if it was
turned on it Step 4.
6. Repeat above steps if necessary.
To register this product visit:
www.broan.com
Page 2
MODELS QTXE110S • QTXE110S2
TYPICAL INSTALLATIONS
Housing mounted to
I-joists.
Housing mounted anywhere
between trusses using hanger
bars.
PLAN THE INSTALLATION
1. Choose the
installation
location.
The location of
your humidity
sensing fan is
very important.
Use the follow-
ing guidelines
for best opera-
tion:
Housing mounted anywhere be-
tween I-joists using hanger bars.
Housing mounted to joists.
Housing mounted anywhere be-
tween joists using hanger bars.
Housing mounted anywhere be-
tween trusses using hanger bars.
INSTALL HOUSING &
DUCT
1a. Mount
housing
to joist
or I-joist.
Use a pliers to
bend housing
TABS out to
900. Hold hous-
ing in place so
that the hous-
ing tabs con-
tact the bottom
of the j ois t.
The housing
mounts wit h
four (4) screws
or nails. Screw
or nail housing
to joist through
lowest holes in
each mount-
i n g f l a n g e ,
then through
highest holes.
SPACER
(use for mounting to I-Joist)
TABS
I-JOIST
NOTE: Mounting to (shown) requires use of I-JOIST
SPACERS (included) between the highest hole of each
mounting flange and the I-joist.
OR
• Locateunitabove(GFCIprotectedcircuitrequired)or
within 5 feet of shower head.
• Locateunitawayfromheatingorcoolingsources
which can affect humidity levels.
• Donotlocatenearwindow.Unitmayrespondtothe
outdoor humidity level.
• Unitmustbeinstalledinceilingtoproperlysense
moisture.
• Locateunitonlyonflatceilingsupto12feethighfor
proper sensing.
• Theductingfromthisfantotheoutsideofthebuilding
has a strong effect on the air flow, noise and energy
use of the fan. Use the shortest, straightest duct rout-
ing possible for best performance, and avoid installing
the fan with smaller ducts than recommended. Insula-
tion around the ducts can reduce energy loss and
inhibit mold growth. Fans installed with existing ducts
may not achieve their rated airflow.
2. Plan the wiring.
• Plantosupplytheunitwithproperlinevoltageand
appropriate power cable. Power cable should be
routed to the switch box first and then to the unit
(See “CONNECT WIRING” on page 3).
• Donotoperatethisunitwithaspeedcontrol.
Damage to the sensor unit will result.
*Purchase
separately.
INSULATION*
(Place around and
over Fan Housing.)
ROOF CAP*
(with built-in
damper)
FAN
HOUSING
POWER
CABLE*
6-IN. ROUND
DUCT*
6-IN.
ROUND
ELBOWS*
Seal gaps
around
Housing.
Seal duct
joints with
tape.
OR
Keep duct
runs short.
WALL CAP*
(with built-in
damper)


Produkt Specifikationer

Mærke: Broan
Kategori: Ventilator
Model: QTXE110S

Har du brug for hjælp?

Hvis du har brug for hjælp til Broan QTXE110S stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ventilator Broan Manualer

Broan

Broan 688ESF Manual

16 Juni 2025
Broan

Broan 688ES Manual

16 Juni 2025
Broan

Broan QTXE150 Manual

31 Marts 2025
Broan

Broan 744RL Manual

31 Marts 2025
Broan

Broan QTXE110S Manual

31 Marts 2025
Broan

Broan A110C Manual

20 August 2024
Broan

Broan AR70LC Manual

20 August 2024
Broan

Broan E0F70 Manual

19 August 2024
Broan

Broan E070 Manual

19 August 2024
Broan

Broan E0F50 Manual

19 August 2024

Ventilator Manualer

Nyeste Ventilator Manualer