Carrier 06N Manual


Læs gratis den danske manual til Carrier 06N (6 sider) i kategorien Kompressor. Denne vejledning er vurderet som hjælpsom af 13 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 7 anmeldelser. Har du et spørgsmål om Carrier 06N, eller vil du spørge andre brugere om produktet?

Side 1/6
Installation Instructions
06N Screw Compressors
Part No. 1TB1047 1 CREV
SAFETY
Failure to follow these instructions could result in
equipment damage, serious personal injury or death, .
WARNING: ELECTRIC SHOCK HAZARD! Do not operate
compressor or provide electric power to it unless the
cover is in place and secured.
WARNING: Do not provide power to unit or turn-on compressor
unless suction and discharge service valves are open.
WARNING: ELECTRIC SHOCK HAZARD! Do not remove the
compressor terminal box cover until all electrical sources
have been disconnected.
WARNING: CONTENTS UNDER PRESSURE! Compressor
contains oil and refrigerant under pressure. Pressure
must be relieved before installation, servicing or opening
any connections.
WARNING: RISK OF PERSONAL INJURY! HOT and COLD
surface temperatures can occur during operation and can
result in severe burns or frostbite.
WARNING: RISK OF PERSONAL INJURY! Only approved
refrigerants and refrigeration oils m be used. ay
WARNING: Use nitrogen or inert gas for tightness/pressure testing.
DO NOT USE oxygen or other industrial gases.
System strength/tightness test pressure may not exceed WARNING:
the compressor est pressure on the maximum Proof T
tag. Close shuto valves to isolate compressor if
necessary.
WARNING: Charge only with refrigerant that conforms to AHRI
Standard 700.
Only qualified, authorized, and appropriately trained HVAC or
refrigeration personnel, should install, commission, and maintain
this equipment.
Use appropriate personal safety equipment where required.
Safety goggles, gloves, protective clothing, safety boots, and
hard hats should be worn where necessary .
Safety Decals
Install label 2TB0713 on inside of terminal box cover. Install label
06DA502503 on outside of terminal box cover. Install one label
06DA508142 on outside of terminal box and the other label 06DA508142
on inside of terminal box.
Operating Limits
Maximum Proof : 450 psig Test Pressure
Refer to Figures 1 and 2
Figure 1 Operating Envelope for Air Cooled Condensing
Figure 2 Operating Envelope for Water Cooled Condensing
Application Drawings
Refer to Application Drawing 0TB0410
Approved Refrigerants
The 06N screw compressor is specically designed for use in R-134a
systems.
Approved Lubricants
The are following lubricants approved for use with 06N Series screw
compressors:
-13, PP47-14, -32, - , Carrier Material Spec PP47 PP47 or PP47 34
Viscosity Grade 220 ISO
Note that all POE oils are very hygroscopic (will readily pick up and retain
moisture from the air). Damaging acids can form if moisture is present. Oil
should only be used from a properly sealed container.
Electrical Connections
Compressor user must provide properly sized motor over-current
protection. Use the electrical data on drawing 0TB0659 or the
compressor nameplate to size the contactor and overload relay or circuit
breaker.
When circuit breakers are used for motor protection, they must be
permanently marked "Special Purpose - Not For General Use" and
should indicate must trip current not exceeding 140% of compressor
rated load current.
Motor protection system must protect against primary single-phase
failure.
Motor over- rrent protection system must protect all three phases. cu
An appropriate terminal box must be installed.
, with its cover installed, WARNING: Terminal box must be in place
before power can be applied.
Connect the compressor in accordance with the Application Drawing
and the wiring diagram located on the terminal box lid.
Power wires are to be connected to the terminal pins using ring
terminals and jam nuts.
The compressor terminals are copper feed through pins. Torque nuts in
accordance with the Application Drawing
WARNING: Disturbing the factory installed nut will jeopardize the
seal integrity of the terminal pin.
The motor temperature thermistors and a separate grounding lug
connection are located in the terminal pin area.
The T-series compressors are approved for use with Across the Line
and Open or Closed Transition Wye-Delta starting methods.
There are two critical timing parameters associated with the open
transition Wye-Delta starting method.
Duration of the Wye connection shall be 5 to 10 seconds.
WARNING: Overheating of the motor can occur if duration is
too long.
10
20
30
40
50
60
70
80
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Saturated Discharge Temperature (
°C)
Saturated Suction Temperature (°C)
Air Cooled Condensing Discharge Temp. Limit for Full Load
Discharge Temp. Limit for 2/3 Load Discharge Temp. Limit for 1/3 Load
10
20
30
40
50
60
70
80
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Saturated Discharge Temperature (°C)
Saturated Suction Temperature (°C)
Water Cooled Condensing Discharge Temp. Limit for Full Load
Discharge Temp. Limit for 2/3 Load Discharge Temp. Limit for 1/3 Load


Produkt Specifikationer

Mærke: Carrier
Kategori: Kompressor
Model: 06N

Har du brug for hjælp?

Hvis du har brug for hjælp til Carrier 06N stil et spørgsmål nedenfor, og andre brugere vil svare dig




Kompressor Carrier Manualer

Carrier

Carrier 06N Manual

10 August 2025
Carrier

Carrier 06E Manual

8 Juli 2025
Carrier

Carrier 05K Manual

8 Juli 2025
Carrier

Carrier 06D Manual

7 Juli 2025

Kompressor Manualer

Nyeste Kompressor Manualer

Vevor

Vevor FB1500D0-20C80 Manual

22 November 2025
Vevor

Vevor JR550GJ4L Manual

22 November 2025
Vevor

Vevor FB-2065/8 Manual

22 November 2025
Vevor

Vevor KYJ-6554 Manual

22 November 2025
Vevor

Vevor JR880-2GAL Manual

21 November 2025
Vevor

Vevor SS-PAC03B Manual

20 November 2025
Vevor

Vevor FB-2090/12.5 Manual

20 November 2025