DSC PG9933 Manual

DSC Røgdetektor PG9933

Læs gratis den danske manual til DSC PG9933 (40 sider) i kategorien Røgdetektor. Denne vejledning er vurderet som hjælpsom af 45 personer og har en gennemsnitlig bedømmelse på 4.8 stjerner ud af 23 anmeldelser. Har du et spørgsmål om DSC PG9933, eller vil du spørge andre brugere om produktet?

Side 1/40
The PG9933 is designed to monitor the CO gas level in residential dwellings and give
early warning before dangerous levels are detected. This device is intended to be used
with a compatible wireless alarm system. The detector consists of an electrochemical
carbon monoxide sensor assembly coupled to a wireless transmitter.
The Wireless Carbon Monoxide Alarm communicates with the control panel and can
send alarm, tamper and battery condition messages to the system receiver.
CAUTION: The detector expiry date is stamped on the detector. After the
expiry date, the detector should not be used - do not wait for end- of-life indic-
ation!
CAUTION: Unauthorized removal of the unit from the mounting bracket will
initiate a tamper alert.
Warnings:
The PG9933 wireless Carbon Monoxide detector shall be installed and used within an
environment that provides the pollution degree max 2 and overvoltages category II in
NON HAZARDOUS LOCATIONS, indoor only. The equipment is designed to be
installed by SERVICE PERSONS only; (SERVICE PERSON is defined as a person
having the appropriate technical training and experience necessary to be aware of haz-
ards to which that person may be exposed in performing a task and of measures to min-
imize the risks to that person or other persons.)
Failure to properly install, test and maintain a CO detector may cause it to fail, res-
ulting in loss of life. Installation of the CO detector should not be used as a substitute
for proper installation, use and maintenance of fuel burning appliances, including
appropriate ventilation and exhaust systems.
This carbon monoxide detector is designed for indoor use only. Do not expose it to
rain or moisture. Do not knock or drop the detector. Do not open or tamper with the
detector as this could cause malfunction. The detector will not protect against the risk
of carbon monoxide poisoning if not properly installed.
CAUTION: This device will only indicate the presence of carbon monoxide gas at the
sensor. Carbon monoxide gas may be present in other areas. This carbon monoxide
alarming device is designed to detect carbon monoxide gas from ANY source of
combustion. It is NOT designed to detect smoke, fire or other gases unless the product
has been investigated and determined to comply with applicable requirements.
WARNING! To comply with FCC and ISED Canada RF exposure compliance
requirements, the device should be located at a distance of at least 20 cm from all per-
sons during normal operation. The antennas used for this product must not be co- loc-
ated or operated in conjunction with any other antenna or transmitter.
Figure 1: Wireless CO Detector
C
D
AB
Legend
A. Alarm LED (see Table 1 for LED indications)
B. Tamper release opening
C. Test/Hush button
D. Battery compartment
E. Breakaway tab (see Figure 3)
PG9933 (915MHz) Wireless Carbon Monoxide Detector
Installation and Operating Instructions
ATTENTION: Read these instructions thoroughly before installation and use of the PG9933. Keep the instructions for future reference.
D-307065
Installation Instructions
Battery Installation
To replace the battery:
1. Remove the detector from its mounting base by twisting it counterclockwise.
Remove and dispose of the battery according to your local regulations.
2. To ensure proper power-down sequence, wait a minimum of 20 seconds before
installing the new battery.
3. Install a new, 3-volt CR123A Panasonic lithium battery in the battery com-
partment observing correct polarity. If the battery is incorrectly inserted, remove
gently with a flathead screwdriver and correctly reinsert.
4. Reinstall the detector onto the mounting bracket by turning it clockwise.
5. After the power-up sequence, the green LED blinks once every 12 seconds to
indicate normal operation. If the battery is not installed correctly, the detector
will not operate and the battery may be damaged.
Enrollment
The 7- digit serial number located on the back of the CO detector housing must be
enrolled on the alarm systems control panel. See the Receiver Installation Manual and
follow the enrollment procedure. For placement tests remove the detector from its
backplate for one second (tamper) and then reattach. Wait at least 30 seconds for the
test result before activating again.
A general description of the procedure is provided in the following flow chart:
Step Procedure
1 See the Installation Manual for the alarm system that the device is being
enrolled on to ensure that the proper steps are used.
2 Enter the Device Enrollment option through the specified method and select the
appropriate option to add the new device.
3 Enroll the device by inserting the batteries to power up the device and enter the
Device ID. For example, ID No. 222-XXXX.
4 Select the desired Zone Number.
5 Configure any device parameters that are required. Enter the DEV
SETTINGS menu and select the required options to configure the detector.
6 Mount and test the detector. See Testing the CO detector for information on
testing the device. In addition, see the alarm systems Installation Manual that
the device is enrolled on for other test procedures that are required.
Selecting a Location
Selecting a suitable location is critical for the CO detector. The Consumer Product
Safety Commission (CPSC) recommends to use at least one CO detector per house-
hold, located as near as possible to sleeping areas of the home, because the human
body is most vulnerable to the effects of CO gas during sleeping hours.
NOTE: Alarm shall be heard from all sleeping areas.
Figure 2: CO Detector Placement
Legend
A: Bedroom
B: Living Room
C: Kitchen
D: Basement
E: Garage
For added protection, install additional CO detectors in every bedroom and on every
level of your home. If your bedroom hallway is longer than 14 meters (40 feet), install
a CO detector at BOTH ends of the hallway. Install an additional detector 6 meters
(20 feet) away from the furnace or fuel burning heat source. For maximum protection,
the detector should also be located outside primary sleeping areas or at each level of
your home. Mount the detector on a firm wall or ceiling.
DO NOT install CO detectors:
lIn locations where the normal ambient temperature is below 40 ºF (4.4 ºC) or
exceeds 100 ºF (37.8 ºC), unless the device has been found acceptable for install-
ation at a higher or lower ambient temperature..
lIn locations where humidity is below 10% or above 93% RH non-condensing.
lNear paint thinner fumes.
lNear air conditioners, furnaces, stoves, fireplaces and any other ventilation source
that may interfere with CO gas entering the detector.
lIn locations where furniture or draperies may obstruct the air flow.
lIn exhaust streams from gas engines, vents, flues or chimneys.


Produkt Specifikationer

Mærke: DSC
Kategori: Røgdetektor
Model: PG9933

Har du brug for hjælp?

Hvis du har brug for hjælp til DSC PG9933 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Røgdetektor DSC Manualer

DSC

DSC PG9933 Manual

2 September 2024

Røgdetektor Manualer

Nyeste Røgdetektor Manualer

Hochiki

Hochiki HCA-4 Manual

26 Februar 2025
Hochiki

Hochiki SOC-24V Manual

25 Februar 2025
Hochiki

Hochiki ALN-V Manual

25 Februar 2025
Hochiki

Hochiki ACC-V Manual

25 Februar 2025
First Alert

First Alert SMICO110 Manual

23 Februar 2025
Drayton

Drayton CCT599002 Manual

20 Februar 2025
LogiLink

LogiLink SC0016 Manual

29 Januar 2025
FirstAlert

FirstAlert SA700CE Manual

12 Januar 2025