SDM630-Modbus V2 User Manual V1.4
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Address: No.52 Dongjin Road, Nanhu, Jiaxing, Zhejiang, China. Web: www.eastron.com.cn email: sales@eastrongroup.com
SDM630-Modbus V2
DIN Rail Smart Meter for Single and Three Phase Electrical Systems
Measures kWh Kvarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
USER MANUAL
2023 V1.5
SDM630-Modbus V2 User Manual V1.4
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Address: No.52 Dongjin Road, Nanhu, Jiaxing, Zhejiang, China. Web: www.eastron.com.cn email: sales@eastrongroup.com
Introduction
The SDM630-Modbus V2 measures and displays the characteristics of single phase two wires (1p2w), three
phase three wires (3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current,
power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure
energy, the unit requires voltage and current inputs in addition to the supply required to power the
product.
SDM630-Modbus V2 supports Max. 100A direct connection, saves the cost and avoid the trouble to connect
external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces provides pulse and RS485
Modbus RTU outputs. Configuration is password protected.
Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Supply system selection 1p2w, 3p3w,3p4w
Demand Interval Time(DIT)
Reset for demand measurements
Pulse output duration
Two pulse outputs indicates real-time energy measurement. An RS485 output allows remote monitoring
from another display or a computer.
RS485 SerialModbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and
controlling the Unit.
Set-up screens are provided for setting up the RS485 port.
Pulse Output
This provides two pulse outputs that clock up measured active and reactive energy. The constant of pulse
output 2 for active energy is 400imp/kWh (unconfigurable), its width is fixed at 100ms.
The default constant of configurable pulse output 1 is 400imp/kWh, default pulse width is
100ms.The configurable pulse output 1 can be set from the set-up menu.