Eltako DSZ15WDM-3x5A Manual

Eltako Måling DSZ15WDM-3x5A

Læs gratis den danske manual til Eltako DSZ15WDM-3x5A (5 sider) i kategorien Måling. Denne vejledning er vurderet som hjælpsom af 44 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 22.5 anmeldelser. Har du et spørgsmål om Eltako DSZ15WDM-3x5A, eller vil du spørge andre brugere om produktet?

Side 1/5
CT operated energy meter with settable CT ratio and MID.
Maximum current 3x5A. Standby loss 0.5 watt per path only.
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With M-bus interface.
This three-phase meter measures active energy by means of the currents
flowing between inputs and outputs. The internal power consumption of
0.5 watt active power per path is neither metered nor indicated.
1, 2 or 3 converters with secondary currents of up to 5 A can be connected.
The inrush current is1OmA. The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply.
Power consumption is indicated by an LED flashing at a rate of 10 times per KWh.
On the right next to the display are the MODE and SELECT buttons to browse
through the menu. First the background lighting switches on. Then the total
active energy, the active energy of the resettable memory and the instantaneous
values of power, voltage and current are displayed for each outer conductor.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a
bridge over the terminals which are marked with 'JUMPER'. To adjust the CT
ratio to the installed transformer remove the bridge and reset the energy
meter according to the operation manual.
Then block it again with the bridge.
Adjustable current transformer ratios: 5:5, 50:5, 100:5,
150:5, 200:5,
250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
If there is no outer conductor of the current direction is incorrect, 'false' and
the related outer conductor are indicated in the display.
M-bus data transfer
On read-out all values are transferred in a telegram.
The following telegrams are supported:
- Initialisation: SND_NKE Reply: ACK
- Read out meter: REQ_UD2 Reply: RSP_UD
- Change primary address: SND_UD Reply: ACK
- Reset RS1: SND_UD Reply: ACK
- Slave selection for the secondary address Reply: ACK
The device does not reply to unknown requests
The transfer rate is detected automatically
The device has a voltage monitor. In case of voltage loss,
all registers are saved in the EEPROM.
Changing the M-bus primary address:
To change the M-bus primary address, hold down SELECT for 3 s. In the menu
that appears, press MODE to increment the address by 10. Press SELECT to
increment by 1. When the required primary address is set, wait until the main
menu reappears.
Secondary address:
It is possible to communicate with the energy meter according to the
standard EN13757 with help of the secondary address.
The use of wildcards is possible.
Detailed information are available in the operating manuals at www.eltako.com
Important! Before working on the current transformers disconnect the voltage
paths of the energy meters.
M-bus three-phase meter for use with CT
DSZ15WDM-3x5A with display and MID approval
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
28 305 515 - 1
GB Typical connection:
4-wire-connection 3x230/400 V
The secondary current converter terminals on the mains side must be
connected to the outer conductors measured. These connections for the
meter power supply must be protected according to local installation
regulations.
Terminal cover sealable Terminal cover claps
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section1) N and L terminals 16mm2,
M-Bus terminals and jumper terminals 6mm
2
Recommended torque2) L- and N terminals 1,5 Nm (max. 2,0 Nm)
M-Bus terminals and jumper terminals 0,8Nm (max. 1,2Nm)
EC type examination certificate 0120/SGS0314
The energy meter is used indoors.
Mechanical environmental conditions class M1
Electromagnetic environmental conditions class E2
1) The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2) The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal
must not be exceeded!
Technical data
Rated voltage, extended range 3x230/400V, 50Hz,
-2O%/+15%
Reference current Iref (Limiting current Imax) 3x0.05 - 5(6)A
Internal consumption active power 0.5 W per path
Display LC display 7 digits,
therefrom 1 digit after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 1O mA
Operating temperature -25/+55°C
Bus system M-Bus
Bus length According to M-bus specifications
Transfer rates 300, 2400, 9600 baud.
Response time Write up to 60ms
(system response time) Read up to 60ms


Produkt Specifikationer

Mærke: Eltako
Kategori: Måling
Model: DSZ15WDM-3x5A

Har du brug for hjælp?

Hvis du har brug for hjælp til Eltako DSZ15WDM-3x5A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Måling Eltako Manualer

Eltako

Eltako DSZ15WDM-3x5A Manual

12 November 2023
Eltako

Eltako EVA12-32A Manual

17 December 2022

Måling Manualer

Nyeste Måling Manualer

Steinberg

Steinberg SBS-DT-74 Manual

2 November 2025
Steinberg

Steinberg SBS-DT-72 Manual

2 November 2025
Dasqua

Dasqua 5111-0000 Manual

1 November 2025
Dasqua

Dasqua 1804-3611 Manual

31 Oktober 2025
LogiLink

LogiLink WZ0028 Manual

31 Oktober 2025
Dasqua

Dasqua 2015-1005 Manual

31 Oktober 2025
ANCEL

ANCEL AD310 Manual

31 Oktober 2025
Dasqua

Dasqua 3004-0010 Manual

31 Oktober 2025
Testboy

Testboy TV 475 Manual

30 Oktober 2025