Læs gratis den danske manual til Festo CPX-FB23-24 (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 23 personer og har en gennemsnitlig bedømmelse på 4.2 stjerner ud af 12 anmeldelser. Har du et spørgsmål om Festo CPX-FB23-24, eller vil du spørge andre brugere om produktet?

Side 1/4
Bus node
CPX-FB23, CPX-FB23-24
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description
Translation of the original instructions
8101635
2018-11c
[8101637]
Bus node CPX-FB23, CPX-FB23-24 English. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For all available product documentation è www.festo.com/pk
1 Intended use
The bus node type is intended exclusively for use as a participant on a CC-Link
fieldbus for CPX terminals.
The specified limits for technical data must be adhered to. You can find detailed
information in the bus node description P.BE-CPX-FB23-24 and in the CPX system
description P.BE-CPX-SYS-…
Note
This description refers to the bus nodes
CPX-FB23 from revision R14 (CC-Link Version 1.1) and
CPX-FB23-24 from revision R22 (CC-Link Version 1.1 and 2.0).
The bus node CPX-FB23-24 can be configured as function module F24 (CC-Link
Version 2.0) or as function module F23 (CC-Link Version 1.1).
Generally valid information is described on this page.
Commissioning with configuration as function module F24 or F23 is described
on the reverse side.
The bus node is intended for use in an industrial environment. Outside of indus
trial environments, e.g. in commercial and mixed-residential areas, actions to
suppress interference may have to be taken.
Only commission a CPX terminal which has been completely mounted and
connected.
CC-Link®, LEONI® and TORX® are registered trademarks of the respective
trademark owners in certain countries.
Note
The bus node includes electrostatically sensitive devices.
Do not touch any components.
Observe the handling specifications for electrostatically sensitive
devices.
Warning
Electric shock
Injury to people, damage to the machine and system
Use for the electrical power supply only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).
Observe the general requirements in accordance with IEC 60204-1 for PELV
circuits.
Use only voltage sources that guarantee a reliable electric disconnection of
operating and load voltage in accordance with IEC 60204-1.
Always connect all circuits for operating and load voltage supplies U
EL/SEN,
UVAL and UOUT
.
Connect the earth terminal of the end plates of the CPX terminal with low
resistance and impedance (short cable with the largest possible cross sec
tion) to the earth potential.
2 Mounting/dismounting
When built-in, the bus node is located in an interlinking block of the CPX terminal.
1
2
3
1TORX® T10 screws
2Bus nodes
3Interlinking block with contact rails
Fig. 1
Warning
Electric shock
Injury to people, damage to the machine and system
Switch off the power supply before assembling or disassembling bus nodes
(risk of operative malfunction or damage).
Dismounting:
Unscrew screws and carefully lift off the bus node.
Mounting:
1. Check seal and seal surfaces.
2. Carefully insert manifold block into the interlinking block and press it in.
3. Screws must be set so that the existing threads can be used. Tighten the
screws by hand in diagonally opposite sequence.
Tightening torque: 0.9 1.1 Nm.
Note
Use appropriate screws, dependent on the material of the interlocking block
(metal or plastic):
Plastic interlinking block: thread-cutting tapping screws
Metal interlinking block: screws with metric thread.
3 Connection and display components
1
2
34
5
1Rating plate
2Fieldbus- and CPX-specific LEDs
3Fieldbus connection1)
4Cover for DIL switches
5Service interface for
operator unit (CPX-MMI) or Festo
Maintenance Tool (CPX-FMT)2)
1) Connection: Sub-D socket, 9 pin 2) Connection: M12 socket, 5 pin
Fig. 1
3.1 LED display component - standard operating status
Characteristics of the LED display components in standard operating status:
All green LEDs are illuminated (Run, PS and PL).
The yellow LEDs light up or flash, dependent on the data communication or
configuration (SD, RD and M).
The red LEDs do not light up (error, SF).
CC-Link-specific LEDs CPX-specific LEDs2)
Run (green) Data communication OK1) PS (green) Power system
Error (red) Data communication faulty1) PL (green) Power load
SD (yellow) Send data SF (red) System failure3)
RD (yellow) Receive data M (yellow) Modify4)
1) Detailed information è Bus node description P.BE-CPX-FB23-24
2) Detailed information è CPX system description P.BE-CPX-SYS-…
3) Flashes in case of error, error diagnostics è CPX system description P.BE-CPX-SYS-…
4) Parameterisation revised or “Force” active.
Fig. 2
3.2 Pin allocation and specification of the fieldbus interface
Connection Pin Signal Explanation
Sub-D socket, 9-pin 2
3
7
Housing
DA
DG
DB
SLD/FG
Data A
Data reference potential (data ground)
Data B
Screening/functional earth (shield/functional
earth, here designated as functional ground)
Fig. 3
Connection technology Achievable degree of protection
Festo plug connector FBS-SUB-9-GS-2x4POL-B IP65/IP67
Festo bus connection FBA-1-KL-5POL IP20
Other sub-D plug connectors
Fig. 4
Cable specification
Cable type CC-110, CC-110-5, CS-110, CM-110-5, 20 AWG x 3
1)
FANC-110SBH, 20 AWG x 3
2)
L45467-Y19-C15, 20 AWG x 3
3)
Length of cable between the participants > 0.2 m (for all baud rates)
Maximum cable length
(dependent on the baud rate)
156 kBd
625 kBd
2.5 MBd
5 MBd
10 MBd
1200 m
900 m
400 m
160 m
100 m
Terminating resistor
between pin 2 and pin 7
110 Ω _ 5 %, 0.5 W
1) DYDEN Corporation
2) KURAMO ELECTRIC Co., Ltd.
3) LEONI protec cable systems GmbH
Fig. 5
4 Parameterisation
Note
The CPX terminal and the related bus node can be parameterised by means of
the Festo operator unit (CPX-MMI) or Festo Maintenance Tool (CPX-FMT).
Further information on parameterisation, module replacement and start-
up behaviour of the CPX terminal can be found in the bus node descrip
tion P.BE-CPX-FB23-24
You can find information on the fieldbus CC-Link in the documenta
tion of your CC-Link Master and the related control system or in the
internet (è www.cc-link.org).
5 Start-up behaviour of the CPX terminal
If the Modify LED M lights up or flashes permanently after the system start, “Sys
tem start with saved parametrisation and saved CPX expansion” is set or “Force is
active.
6 Note on module replacement
Caution
For CPX terminals with a continuously illuminated or flashing M LED, the para
meterisation is not automatically created by the higher-level system when the
CPX terminal is replaced during servicing.
Before replacement, note required settings and make them again after re
placement.
7 Power supply of the CPX terminal
The operating and load voltage supply for the CPX terminal is fed in via interlinking
blocks. These conduct the operating and load voltages to the neighbouring mod
ules (è CPX system description P.BE-CPX-SYS-…).
8 Technical data
Bus node CPX-FB23, CPX-FB23-24
Function module F24 F23
General technical data è CPX system description P.BE-CPX-SYS-...
Degree of protection through housing1)
completely mounted in accordance with IEC
60529, plug connector inserted or provided
with cover cap2)
With plug connector FBS-SUB-9-GS-2X4POL-B
With bus connection FBA-1-KL-5POL or other
plug connectors for the bus connection
IP65/IP67
IP20
Protection against electric shock
Protection against direct and indirect contact in
accordance with IEC 60204-1
through the use of PELV circuits
Intrinsic current consumption bus node
from operating voltage supply for
electronics/sensors (UEL/SEN)
typ. 70 mA at 24 V (internal electronics)
Separation
Fieldbus connection at UEL/SEN Galvanically separated
Mains buffering time 10 ms
Module code (CPX-specific)
Remote I/O
Remote controller
Module identifiers (CPX-MMI, CPX-FMT)
Remote I/O
Remote controller
206
FB24-RIO CC-Link V2
remote I/O
206
157
FB23-RIO CC-Link
remote I/O
FB23-RC
Fieldbus-specific characteristics
Protocol
Version
Vendor code
Machine type
CC-Link
Version 1.1 and 2.0
0x0177
0x3C
CC-Link
Version 1.1
0x0177
0x3C
Data transmission rate (baud rate) 156 kBd
625 kBd
2.5 MBd
5 MBd
10 MBd
1) Observe that connected devices may only satisfy a lower degree of protection or a smaller temperature
range, etc.
2) Cover cap from Festo, type ISK-M12, included in the scope of delivery
Fig. 6