Finder 22.34.0.024.4320 Manual

Finder Ikke kategoriseret 22.34.0.024.4320

Læs nedenfor 📖 manual på dansk for Finder 22.34.0.024.4320 (1 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 38 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/1
22.34
022.33 022.35
022.33 2 NO (DPST-NO)
022.35 1 NO (SPST-NO) + 1NC (SPST-NC)
AC1 6 A
AC15(230 V AC) 700 VA
22.34 + (022.33 / 022.35)
• Open Type Device - Pollution degree 2 Installation Environment
• Maximum Surrounding Air Temperature 50°C
• Minimum distance among modular contactors 9 mm
• Field Wiring Terminals:
Use 60/75°C copper conductor only and wire ranges
No. 10-12-18-24AWG, Solid only
Terminal tightening torque 7.0 lb.in. (0.8 Nm)
• Suitable for use on a circuit capable of delivering not more than
5000 ARMS Symmetrical, 240 V AC, when protected by Listed
Cartridge Fuses, rated K5 Class (No Current Limiting, Non-Time
Delay, max 600 V AC, 30 A, 50 kA A.I.C.) or RK5 Class (Current
Limiting, Time Delay, max 600 Vac, 15 A, 50 kA A.I.C.) or equivalent.
• For use in a circuit protected by Type1 or Type2 Surge Protective
Devices with “Max Voltage Protection” rating of 3.7 kVpk and
“Minimum Nominal Discharge Current” of 5 kA (at 6 kV).
A
B C
1 2
3
4
22.34.0. .xxx0XXX
UN (12 - 24 - 48 - 60 - 120 - 230)V AC (50/60 Hz) / DC
Umin - Umax: (0.8...1.1)UN
P 2 VA (50 Hz) / 2.2 W
22.34...x x0 22.34...x x0 22.34...x x03 7 6
25 A 440 V AC (EN 61095)
AC1 / AC-7a (250 V AC)
AC3 / AC-7b
AC15 (230 V AC)
3~
M
(400 - 440 V AC)
6250 VA
10 A
1800 VA
4 kW
AC -7c 10 A ( )22.34... xx04
(230 V AC) 800 W
2000 W (22.34... xx0)4
(230 V AC) 300 W
800 W (22.34... xx0)4
CFL - LED 100 W
200 W (22.34... xx0)4
(–20…+50)°C
IP20
Utility Model - IB2234001 - 05/19 - Finder S.p.A. con unico socio - 10040 ALMESE (TO) - ITALY
22.34 MODULAR CONTACTOR 25 A
Contact gap ≥ 3 mm for NO contacts only. NC contacts ≥ 1.5 mm.
Compliant with EN 61095: 2009.
AC/DC silent coil (with varistor protection).
CONNECTION DIAGRAM
OUTLINE DRAWINGS
FRONT VIEW
A 4 = Selector (22.34.0.xxx.xx 0)
The three-position manual selector has the following functions:
ON position
The contacts are latched in the operated state (NO contacts - closed
and NC contacts - open), the mechanical indicator is visible in its
window, the LED is not illuminated.
AUTO position
The state of contacts, mechanical indicator and LED follow the coil
supply voltage.
OFF position
Even if terminals A1 - A2 are supplied with rated voltage, the coil is
not energized, and so the contacts remain in the non-operated state,
the mechanical indicator is not visible and the LED is not illuminated.
B = LED
C = Mechanical indicator
ACCESSORIES
Auxiliary contact module available, “Quick assembly” with the main
contactor 022.33/022.35.
OTHER DATA
It is suggested an air gap of 9 mm between adjacent relays for
installations and working conditions close to the limit (that is,
ambient temperature > 40 °C, coil operated for a prolonged
period of time, all contacts loaded with current > 20 A).
1
2
3
4
ENGLISH


Produkt Specifikationer

Mærke: Finder
Kategori: Ikke kategoriseret
Model: 22.34.0.024.4320
Produktfarve: Hvid
Certificering: CE, EAC
LED-indikatorer: Strøm
Bæredygtighedscertifikater: RoHS
Antal poler: 4
Uddgående frekvens: 50/60 Hz
Spolespænding: 24 V
Kontakt, strømkapacitet: 25 A