22.32
22.3 (022.33/022.35)2 +
• Open Type Device - Pollution degree 2 Installation Environment
• Maximum Surrounding Air Temperature 50°C
• Minimum distance among modular contactors 9 mm
• Field Wiring Terminals:
Use 60/75°C copper conductor only and wire ranges 
No. 10-12-18-24 AWG, Solid only
Terminal tightening torque 7.0 lb.in. (0.8 Nm)
• Suitable for use on a circuit capable of delivering not more than 
5000 ARMS Symmetrical, 240 V ac, when protected by Listed 
Cartridge Fuses, rated K5 Class (No Current Limiting, Non-Time 
Delay, max 600 Vac, 30 A, 50 kA A.I.C.) or RK5 Class (Current
Limiting, Time Delay, max 600 Vac, 15 A, 50 kA A.I.C.) or equivalent
• For use in a circuit protected by Type1 or Type2 Surge Protective 
Devices with “Max Voltage Protection” rating of 3.7 kVpk and 
“Minimum Nominal Discharge Current” of 5 kA (at 6 kV)
022.33 022.35
022.33 2 NO (DPST- NO)
022.35 1 NO (SPST- NO) + 1 NC (SPST- NC)
      Ith            6 A 
   AC15     700 VA
(230 V AC)
22.32.0. .x x0xxx x
UN ( - - - - - )V AC (50/60 Hz) / DC12 24 48 60 120 230
Umin- Umax (0.8-1.1)UN
P 2 VA / 2.2 W
22.32...x x0 22.32...x x0 22.32...x x03 5 4
25 A 440 V AC (EN 61095)
AC AC-7a (250 V)  6250 VA1/
AC AC-7b  10 A3/
AC5a (250 V)  15 A
AC15 (230 V AC)  1800 VA
  (230 V AC)  1 kW
DC1 (30/11 220 /1)A0/ )V  (25/5
AC-7c     -        (10 A -  ... )22.32 4xx0
    800 W (2000 W -  )22.32... xx04
    300 W (800 W -  )22.32... xx04
CFL–LED  100 W (200 W -  )22.32... xx04
(–20...+50)°C
IP20
M
1 2
A
B
C
3
4
Utility Model - IB2232001 - 06/19 - Finder S.p.A. con unico socio - 10040 ALMESE (TO) - ITALY
22.32 MODULAR CONTACTORS 25 A
Contact gap ≥ 3 mm for NO contacts only; NC contacts ≥ 1.5 mm.
Compliant with EN 61095: 2009.
AC/DC silent coil (with varistor protection).
CONNECTION DIAGRAM 
OUTLINE DRAWINGS
 
FRONT VIEW
A = Selector (22.32.0.xxx.xx40)
    The three-position manual selector has the following functions:
    ON position 
    The contacts are latched in the operated state (NO contacts -
    closed and NC contacts - open), the mechanical indicator is visible
    in its window, the LED is not illuminated.
    AUTO position
    The state of contacts, mechanical indicator and LED follow the coil
    supply voltage.
    OFF position
    Even if terminals A1 - A2 are supplied with rated voltage, the coil
    is not energized, and so the contacts remain in the non-operated
    state, the mechanical indicator is not visible and the LED is not
    illuminated.
B = LED
C = Mechanical indicator
ACCESSORIES
- Auxiliary contact module available, “Quick assembly” with the main
contactor 022.33/022.35
- It is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0
(2 NC versions)
OTHER DATA
It is suggested an air gap of 9 mm between adjacent relays for installations
and working conditions close to the limit (that is, ambient temperature
> 40°C, coil operated for a prolonged period of time, all contacts loaded
with current > 20 A).
1
2
3
4
ENGLISH