Generac QT08054AVANA Manual
Læs gratis den danske manual til Generac QT08054AVANA (146 sider) i kategorien Generator. Denne vejledning er vurderet som hjælpsom af 19 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 10 anmeldelser. Har du et spørgsmål om Generac QT08054AVANA, eller vil du spørge andre brugere om produktet?
Side 1/146

STATIONARY EMERGENCY GENERATOR
OWNER'S MANUAL
This manual should remain with the unit.
Serial Number Industrial QT
5.4L
80kW Models
EPA Certified
A new standard of reliability
Cover146 Rev. B 03/09 Part No. 0H0942

Stationary Emergency Generator
Table of Contents
SECTION PAGE
INTRODUCTION .....................................................1-1
Read this Manual Thoroughly ...................................1-1
Operation and Maintenance ......................................1-1
How to Obtain Service ..............................................1-1
SAFETY RULES ......................................................1-2
IDENTIFICATION RECORD .....................................2-1
Data Label ................................................................2-1
EQUIPMENT DESCRIPTION ...................................3-1
Equipment Description ................................................3-1
Engine Oil Recommendations ......................................3-1
Coolant Recommendations...........................................3-1
ENGINE PROTECTIVE DEVICES ............................4-1
Coolant Temperature Sensing ...................................4-1
Low Coolant Level .....................................................4-1
Oil Pressure Sensing .................................................4-1
Overcrank Shutdown ................................................4-1
Overspeed Shutdown ................................................4-1
RPM Sensor Loss Shutdown .....................................4-1
DC Fuse ....................................................................4-1
FUEL SYSTEMS .....................................................5-1
Fuel Requirements ....................................................5-1
Natural Gas Fuel System ..........................................5-1
Propane Vapor Withdrawal Fuel System....................5-1
LP Fuel System .........................................................5-1
SPECIFICATIONS ...................................................6-1
Generator .................................................................6-1
Engine.......................................................................6-1
Cooling System .........................................................6-1
Fuel System ..............................................................6-1
Electrical System ......................................................6-1
5.4L & 6.8L Ignition Description .................................6-3
Ignition Power-up Input (“56 Line Input”) .................6-3
Ignition Enable (“14 Line Input”) ..............................6-3
Ignition Shutdown on Loss of Crank
or CAM Signals .........................................................6-3
Diagnostic Blink Patterns (Red LED Located
on the Ignition Control Board ...................................6-3
GENERAL INFORMATION .......................................7-1
Generator AC Lead Connections ..................................7-1
Alternator Power Winding Connections ........................7-1
Four-lead, Single-phase Stator ..................................7-1
3-phase Alternators ("Y" Configuration) ....................7-1
3-phase Alternators ("Delta" Configuration) ..............7-2
INSTALLATION .......................................................8-1
Installation ...................................................................8-1
Preparation Before Start-up .........................................8-1
Transfer Switch ........................................................8-1
Fuel System ..............................................................8-1
Generator Set Lubrication ........................................8-1
Prior to Initial Start-up .............................................8-1
Engine Coolant .........................................................8-1
Belt Tension ..............................................................8-1
Electrical System ......................................................8-1
Initial Inspection for QT Genset Start-up .....................8-1
Start-up Checklist ........................................................8-2
Preparation for Start-up............................................8-2
Start-up Inspection ...................................................8-2
OPERATION ...........................................................9-1
Generator Control and Operation ................................9-1
Operating Unit with Manual Transfer Switch ...............9-1
Engine Start-up and Transfer ...................................9-1
Retransfer and Shutdown .........................................9-1
Operating Unit with Automatic Transfer Switch ...........9-1
MAINTENANCE .....................................................10-1
Maintenance Performed by Authorized
Service Facilities .....................................................10-1
Every Three Months ...............................................10-1
Once Every Six Months ...........................................10-1
Once Annually .........................................................10-1
First 100 Operating Hours ......................................10-1
Every 500 Operating Hours ....................................10-1
Cooling System ..........................................................10-1
Checking Fluid Levels ................................................10-1
Check Engine Oil ....................................................10-1
Battery Fluid ...........................................................10-1
Engine Coolant .......................................................10-2
Maintenance Owner/Operator Can Perform ................10-2
Check Engine Oil Level ...........................................10-2
Check Battery .........................................................10-2
Exercise System ......................................................10-2
Inspect Cooling System ...........................................10-2
Check Engine Coolant Level....................................10-2
Perform Visual Inspection .......................................10-2
Inspect Exhaust System ..........................................10-2
Check Fan Belt ........................................................10-2
Inspect Engine Governor ........................................10-2
Changing Engine Oil ...............................................10-2
Changing the Engine Air Cleaner ............................10-3
Spark Plugs ............................................................10-3
Coolant Change .......................................................10-3
Miscellaneous Maintenance ........................................10-3
Cleaning the Generator ...........................................10-3
Battery ....................................................................10-4
Battery Maintenance ...............................................10-4
Battery Replacement ...............................................10-4
SERVICE SCHEDULE ...........................................11-1
30 kW - 150 kW Standby Gas Engine
Driven Generator Sets ............................................11-1
TROUBLESHOOTING ...........................................12-1
Troubleshooting Guide ...............................................12-1
EMISSIONS WARRANTY .......................................13-1
NOTES
EXPLODED VIEWS & PARTS LISTS
WIRING DIAGRAMS & SCHEMATICS
WARRANTY
Content026 Rev. A 10/08

1-1
INTRODUCTION
Thank you for purchasing this model of the Stationary Emergency
Generator set product line.
Every effort was expended to make sure that the information and
instructions in this manual were both accurate and current at the
time the manual was written. However, the manufacturer reserves
the right to change, alter or otherwise improve this product(s) at
any time without prior notice.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the near-
est Authorized Service Dealer for starting, operating and servicing
procedures.
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
service or operation that may be hazardous if performed incor-
rectly or carelessly. Observe them carefully. Their definitions are
as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious per-
sonal injury, including death, or property damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal
injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements that require
special emphasis.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to prevent-
ing accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:
This symbol points out important safety informa-
tion that, if not followed, could endanger per-
sonal safety and/or property of others.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equip-
ment. The manufacturer strongly recommends that the operator
read this Owner's Manual and thoroughly understand all instruc-
tions before using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and operate
the unit. This prepares them if they need to operate the equipment
in an emergency.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is performed
promptly, and to have the equipment checked periodically by
an Authorized Service Dealer. Normal maintenance service and
replacement of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials or workman-
ship within the terms of the warranty. Individual operating habits
and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensure a minimum
number of problems and keep operating expenses at a minimum.
See an Authorized Service Dealer for service aids and accessories.
Operating instructions presented in this manual assume that the
generator electric system has been installed by an Authorized
Service Dealer or other competent, qualified contractor. Installation
of this equipment is not a “do-it-yourself” project.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact
an Authorized Service Dealer for assistance. Service technicians
are factory-trained and are capable of handling all service needs.
When contacting a dealer about parts and service, always supply
the complete Model Number, Serial Number and Type Code (where
applicable) from the DATA LABEL that is affixed to the unit.
AUTHORIZED SERVICE DEALER LOCATION
To locate the nearest AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
or locate us on the web at:
www.generac.com
Stationary Emergency Generator
Important Safety Instructions
Safety 001 Rev. C 08/09

IDENTIFICATION RECORD
DATA LABEL
Every generator set has a DATA LABEL that contains
important information pertinent to the generator. The
data label, which can be found attached to the gen-
erator’s lower connection box, lists the unit’s serial
number and its rated voltage, amps, wattage capac-
ity, phase, frequency, rpm, power factor, production
date, etc.
WAUKESHA, WI
RATED KW
RATED VOLTAGE
POWER FACTOR
ENGINE RPM
ALTERNATOR SUBTRANSIENT REACTANCE
ALTERNATOR TRANSIENT REACTANCE
CLASS
MODEL
MADE IN USA
PRODUCTION DATE
GENERAC POWER SYSTEMS, INC.
HERTZ
RATED KVA
GENERATOR SET DATA
RATED AMPS
ALT RPM
PHASE
SERIAL
ROTOR STATOR WINDING INSULATION AT 25 C AMBIENT°
NOTE:
For actual information related to this particular
model, please refer to the Manual Drawing Listing
located at the end of this manual, or to the data
label affixed to the unit.
Stationary Emergency Generator Model and
Serial Number
This number is the key to numerous engineering and
manufacturing details pertaining to your unit. Always
supply this number when requesting service, order-
ing parts or seeking information.
Identification Code
Use this code to obtain important information about
the generator. For example, if the code is:
M — Designates generators capable of paralleling.
NOTE: Only 100kW and 150kW, 6.8L units
are currently available for this configura-
tion.
QT — Quiet Test Generator Series
100 — kw Rating
5.4 — Engine Size in Liters
A — Voltage Code: A = 120/240, Single-phase;
G = 120/208, Three-phase; K = 277/480,
Three-phase; J = 120/240, Three-phase;
L = 346/600, Three-phase
N — Fuel: N = Natural Gas; V = Vapor Propane
S — Enclosure Material: A = Aluminum; S
= Steel (Corrosion Resistant Aluminum
Enclosure Material, Steel is Standard)
N — Emission Equipment: N = No Equipment;
Y = Catalytic Converter and Air/Fuel Ratio
Controller
A — Industrial Dealer Product
Voltage Codes
The identification code letter following the unit’s
engine size is the generator’s “voltage code.”
Groups and Assembly Numbers
The manual drawing listing lists the groups and cor-
responding assembly numbers for each unit. The
assembly numbers refer to exploded view drawing
numbers that are applicable to the specific generator
model. These drawings are located in the back half
of this manual.
2-1
Stationary Emergency Generator
General Information
Identy001 Rev. D 10/08
M Q T 1 0 0 5 4 A N S N A

EQUIPMENT DESCRIPTION
This equipment is a revolving field, alternating cur-
rent Stationary Emergency Generator. It is powered
by a gaseous fueled engine operating at 1800 rpm for
4-pole direct drive units, 3600 rpm for 2-pole direct
drive units and 2300 - 3000 rpm for quiet drive gear
units. See the Specifications section for exact num-
bers. The unit comes complete with a sound attenu-
ated enclosure, internally mounted muffler, control
console, mainline circuit breaker, battery charger,
and protective alarms as explained in the following
paragraph.
The Stationary Emergency Generator incorporates
the following alternator features:
• Rotor and Stator insulation is Class H rated as
defined by NEMA MG1-32.6, NEMA MG1-1.66.
The generator is self ventilated and drip-proof con-
structed.
• The voltage waveform deviation, total harmonic
content of the AC waveform and telephone influ-
ence factor have been evaluated and are acceptable
according to NEMA MG1-32.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at
the factory. Use a high-quality detergent oil classi-
fied “For Service SJ or SH.” Detergent oils keep the
engine cleaner and reduce carbon deposits. Use oil
having the following SAE viscosity rating, based on
the ambient temperature range anticipated before the
next oil change:
Any attempt to crank or start the engine before
it has been properly serviced with the recom-
mended oil may result in an engine failure.
NOTE:
For temperatures below 32° F, it is strongly recom-
mended to use the optional Cold Weather Start Kit
(part number listed in the Specification Section).
The oil grade for temperatures below 32° F is 5W-
30 synthetic oil.
COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol
base anti-freeze and deionized water. Cooling system
capacity is listed in the specifications. Use only deion-
ized water and only low silicate anti-freeze. If desired,
add a high quality rust inhibitor to the recommended
coolant mixture. When adding coolant, always add
the recommended 50-50 mixture.
Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chro-
mium hydroxide (“green slime”) forms and will
cause overheating. Engines that have been oper-
ated with a chromate base rust inhibitor must
be chemically cleaned before adding ethylene
glycol base anti-freeze. Using any high silicate
anti-freeze boosters or additives will also cause
overheating. The manufacturer also recommends
that any soluble oil inhibitor is NOT used for this
equipment.
DANGER
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling
liquid or steam could result.
Ethylene glycol base antifreeze is poisonous.
Do not use mouth to siphon coolant from the
radiator, recovery bottle or any container. Wash
hands thoroughly after handling. Never store
used antifreeze in an open container because
animals are attracted to the smell and taste of
antifreeze even though it is poisonous to them.
Temperature Oil Grade (Recommended)
Above 80° F (27° C) SAE 30W or 15W-40
32° to 80° F (0° to 27° C) SAE 20W-20 or 15W-40
Below 32° F (0° C) See Note
3-1
Stationary Emergency Generator
Equipment Description
Equip005 Rev. B 10/08

Engine Parameters
Exhaust System
Combustion Air Requirements (Natural Gas)
Governor
Engine Lubrication System
Fuel Consumption - ft3/hr (Natural Gas/LPV)
Voltage Regulator
Power Adjustment for Ambient Conditions
Controller .............................................................. H-panel
6-1
Produkt Specifikationer
Mærke: | Generac |
Kategori: | Generator |
Model: | QT08054AVANA |
Har du brug for hjælp?
Hvis du har brug for hjælp til Generac QT08054AVANA stil et spørgsmål nedenfor, og andre brugere vil svare dig
Generator Generac Manualer
26 Juni 2025
19 Februar 2025
11 Januar 2025
11 Januar 2025
11 Januar 2025
11 Januar 2025
8 Januar 2025
17 September 2024
10 September 2024
10 September 2024
Generator Manualer
- Yamaha
- Sun Joe
- Fieldmann
- Herkules
- Ferrex
- PRAMAC
- Güde
- Hitachi
- Guede
- Rowenta
- ITC Power
- ThermaSol
- Sunbird Solar
- Swiss Kraft
- Trotec
Nyeste Generator Manualer
20 Juni 2025
19 Juni 2025
19 Juni 2025
18 Juni 2025
18 Juni 2025
17 Juni 2025
16 Juni 2025
16 Juni 2025
16 Juni 2025
15 Juni 2025