Honeywell F100F2025/U Manual


Læs gratis den danske manual til Honeywell F100F2025/U (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 38 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 19.5 anmeldelser. Har du et spørgsmål om Honeywell F100F2025/U, eller vil du spørge andre brugere om produktet?

Side 1/4
Tools needed to install
Enhanced Air Cleaner
Standard screwdriver
Phillips screwdriver
Metal cutter
Drill
Duct Sealant
Mounting the Media Air Cleaner
STEP ONE: Review the Installation Plan
Temporarily place the cabinet on the floor, oriented as it will be when installed. Insert and remove the cartridge to make sure the
plan allows adequate clearance for easy removal and replacement of the cartridge.
STEP TWO: Fasten the Cabinet to the Furnace
a. Align the cabinet with the return air opening.
b. Place blocks under the cabinet, as necessary, to make sure the unit sits securely.
c. Create an opening in the furnace to match the cabinet opening.
d. Attach the cabinet securely to the furnace. Attach the unit directly or fit a starting collar in the furnace opening. Either drill
holes and fasten with sheetmetal screws or rivets, or use slip joints. If you are drilling holes, use a locking pliers to help hold
the unit in place during drilling.
STEP THREE: Install Turning Vanes
Install turning vanes to help distribute air equally over the full surface of the upstream side of the media. Install them whenever
an abrupt 90 degree elbow is installed directly against the media air cleaner cabinet.
STEP FOUR: Fasten Cabinet to Ductwork
Fasten side of cabinet to the ductwork using sheet-metal screws, rivets, or slip joints, as appropriate.
STEP FIVE: Connect Ductwork
a. Connect the vertical duct section to the elbow. If the vertical drop of the duct is less than 7 in. (178 mm) from the side of the
furnace, shorten the horizontal trunk or attach an offset fitting to the elbow.
b. When ductwork is properly aligned, connect the vertical duct to the horizontal trunk.
STEP SIX: Seal Joints
Seal all joints in the return air system between the media air filter and the furnace to prevent dust from entering the clean
airstream.
Application Considerations
Air Conditioning: Mount the media air cleaner up-
stream of the evaporator coil in a cooling system.
Humidifiers: The media air cleaner is compatible
with humidifiers. Avoid applications where water mist
will reach the media.
UV Lights: Germicidal UV lights can cause degrada-
tion of the media filter. The UV light should be located
out of line of sight or a minimum of 3 feet from the
filter.
Choosing a Mounting Position
The Media Air Cleaner mounts in any position within
the return air duct, usually next to the furnace blower
compartment, but the arrow on the cartridge must
point in the same direction as the airflow.
NOTE: The media air cleaner cabinet is sturdy
enough to easily support the weight of the
furnace and evaporator coil.
Important Installation Requirements
Personal Safety
Wear safety glasses while installing the unit.
Do not cut into any air conditioning or
electrical line.
Follow professional safety standards and
all local codes for plumbing, electrical, and
mechanical considerations.
Failure to comply with these requirements
will result in voided warranty, improper
installation, and service callbacks.
M939C
Highboy furnace with side
installation.
STEP SEVEN: Install Filter Cartridge
Slide the filter cartridge into the cabinet, making sure the arrow on the cartridge
points in the direction of air flow. Replace access door. Insert the tab on the bottom
of the door into the slot in the cabinet. Swing the door closed and press it into place.
Media Air Cleaners
QUICK START GUIDE
33-00240EF-03
F100 Specifications
MERV Rating*: MERV 11
Static Pressure Drop: 0.23 (in. w.c.) at 500 FPM
Efficiency Definition*:
Small Particles: E1 = 0.3 to 1.0 microns = 32%
Medium Particles: E2 = 1.0 to 3.0 microns = 72%
Large Particles: E3 = 3.0 to 10.0 microns = 96%
0500 1000 1500 2000
0.000
0.050
0.100
0.150
0.200
0.250
0.300
12.5 X 20
16 X 20
16 X 25
20 X 20
20 X 25
FILTER SIZE
PRESSURE DROP (IN. WC)
AIRFLOW (CFM)
M34911
WHEN FIRST INSTALLED. PRESSURE DROP INCREASES AS FILTER
BECOMES LOADED. REPLACE FILTER WHEN PRESSURE DROP
REACHES 0.5 IN. WC. (0.1 kPa).
AVAILABLE ONLY IN UNITED STATES.
2
1
1
2
F200 Specifications
MERV Rating*: MERV 13
Static Pressure Drop: 0.3 (in. w.c.) at 500 FPM
Efficiency Definition*:
Small Particles: E1 = 0.3 to 1.0 microns = 63%
Medium Particles: E2 = 1.0 to 3.0 microns = 91%
Large Particles: E3 = 3.0 to 10.0 microns = 99%
0500 1000 1500 200
0
0
0.1
0.2
0.3
0.4
PRESSURE DRO (IN. WC)P
AIRFLOW (CFM)
M13662
WHEN FIRST INSTALLED. PRESSURE DRO INCREASES AS FILTERP
BECOMES LOADED. REPLACE FILTER WHEN PRESSURE DROP
REACHES 0.5 IN. WC. (0.1 kPa).
1
1
20 x 25 in.
(508 x 635 mm)
20 x 20 in.
(508 x 508 mm)
16 x 25 in.
(406 x 635 mm)
16 x 20 in.
(406 x 508 mm)
M37054
F100F SIZE
IN.
16 X 25
16 X 20
20 X 25
20 X 20
MM
406 X 635
406 X 508
508 X 635
508 X 508
DIM. A
14-7/16
14-7/16
18-7/16
18-7/16
367
367
468
468
DIM. B
16-3/16
16-3/16
20-3/16
20-3/16
411
411
513
513
23-1/4
18-1/4
23-1/4
18-1/4
DIM. C
591
457
591
457
DIM. D
25-7/16
20-7/16
25-7/16
20-7/16
646
519
646
519
IN. MM IN. MM IN. MM IN. MM
6-3/4
(170)
1-7/16 (37)
DIM. A
(SEE
TABLE)
7/8
(22)
DIM. C (SEE BLE)TA
DIM. D (SEE BLE)TA
DIM. B
(SEE
TA
BLE)
Dimensions Temperature Rating
-40° to +140°F (-40° to +60°C)
Approvals
Underwriters Laboratories, Inc.: Listed to UL 900,
Class 2.
NEED HELP?
For assistance with this product, or for the complete
installation guide, please visit honeywellhome.com
or call Customer Care toll free at .1-800-468-1502
* Minimum Efficiency Reporting Value (Media Filters Only)
* Efficiency ratings are based on American Society of Heating, Refrigerating and Air-Conditioning Engineers Standard 52.2-1999.
Replacement Air Filters
Filter Size (in.)
Part Number
F100 - MERV 11 F200 - MERV 13
16 x 20 FC100A1003 FC200E1003
16 x 25 FC100A1029 FC200E1029
20 x 12.5 FC100A1052 N/A
20 x 20 FC100A1011 FC200E1011
20 x 25 FC100A1037 FC200E1037
21.5 x 27.5 FC100A1045 N/A
Resideo Inc., 1985 Douglas Drive North
Golden Valley, MN 55422
www.resideo.com
This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502
© 2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
33-00240EF—03 M.S. Rev. 08-19 | Printed in United States


Produkt Specifikationer

Mærke: Honeywell
Kategori: Ikke kategoriseret
Model: F100F2025/U

Har du brug for hjælp?

Hvis du har brug for hjælp til Honeywell F100F2025/U stil et spørgsmål nedenfor, og andre brugere vil svare dig