JUNG W8180 Manual

JUNG Skifte W8180

Læs gratis den danske manual til JUNG W8180 (15 sider) i kategorien Skifte. Denne vejledning er vurderet som hjælpsom af 42 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 21.5 anmeldelser. Har du et spørgsmål om JUNG W8180, eller vil du spørge andre brugere om produktet?

Side 1/15
Automatic Switch 180 Automatic Switch 180
Ref.-no.: W 8180
W 8280
Operating Instructions
WG 800 Automatic Switch 180
1. Safety Instructions
Attention: The installation and assembly of electrical equipment
may only be performed by a qualified electrician. Not suitable for
safety disconnection.
To avoid electric shock, safely disconnect the automatic switch
(switch o the automatic circuit breaker) prior to working on it, or
before changing the lamp.)
Non-observance of these installation instructions may cause re or
other hazards.
2. Function
Function Principle
The automatic switches respond to thermal movements initiated by
persons, animals or objects and trigger a switching process. The
automatic switches remain switched on as long as some movements are
detected, otherwise they will switch off after their shut-off delay time has
elapsed. Optionally, the automatic Switch can also be set to short-time
operation. This facilitates the activation of acoustic signal transmitters
(bell) to observe an entrance door. The automatic switches have been
designed for operation together with a switching insert.
Important: These automatic switches are not suitable for alarm systems.
Depending on the lens used, the nominal installation height is
1.10 or 2.20 m.
The 2.20 m lens automatic switches can also be installed at
the height of 1.10 m.
Stand: Jul-10 825 187 03
Automatic Switch 180 Automatic Switch 180
Ref.-no.: W 8180
W 8280
Figure 1
Fig. 1: 2.20 m lens at an installation height of 2.20 m or
1.10 m, respectively.
Figure 2
Fig. 2: 1.10 m lens at an installation height of 1.10 m.
For how to connect the inserts, please refer to the operating
instructions of the respective insert.
Detection Field of the 1.10 m Lens Version
The 1.10 m automatic switches have a two-level detection
field with an opening angle of 180° (Fig. 3).
Figure 3
Detection field area (Fig. 3): approx. 10 m x 12 m
The information on the detection field area is referred to an
installation height of 1.10 m. For different installation heights, the nominal
working range varies.
Due to the alignment of the upper lens level, the detection field is spatially
not limited. This may, among other things, cause movements out of the
specied detection eld to trigger switching events (over-ranging).
2


Produkt Specifikationer

Mærke: JUNG
Kategori: Skifte
Model: W8180

Har du brug for hjælp?

Hvis du har brug for hjælp til JUNG W8180 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Skifte JUNG Manualer

JUNG

JUNG W8180 Manual

10 December 2024
JUNG

JUNG 201TE Manual

10 December 2024
JUNG

JUNG ASLS1280-1 Manual

20 September 2024
JUNG

JUNG ME5201DTU Manual

2 September 2024
JUNG

JUNG SL1180 Manual

28 August 2024
JUNG

JUNG AS5544.03VWW Manual

28 August 2024
JUNG

JUNG ES5201DTU Manual

28 August 2024
JUNG

JUNG SL1180-1 Manual

28 August 2024
JUNG

JUNG CD5024WW Manual

28 August 2024
JUNG

JUNG A1180-1 Manual

23 August 2024

Skifte Manualer

Nyeste Skifte Manualer