Use appropriate personal protective equipment
such as safety glasses, face shields, insulating
gloves, insulating boots, and/or insulating
mats.
Use the 3-Step Testing Method. Before each
use:
Verify tester operation by measuring a
known voltage. Apply tester to circuit under
test. And, then test on the known live volt-
age again to ensure proper operation.
Connect the black common lead to ground
before applying the red test lead to voltage.
Disconnect the red test lead from the volt-
age first.
Always work with a partner.
When using the probes, keep fingers as far
behind the probe tips as possible.
Features:
Vibration Mode with indicator movement
Independent solenoid and electronic circuitry
design provides back-up voltage indication
for added safety
Low Impedance Measuring Device
Replaceable Test Leads
Shielded probe tips
Ultrasonically welded for added durability
Accessories:
61-072 Resistor-fused test leads
C-90 Soft-sided carrying case
61-010 Leather case
To Measure AC Voltage:
Ensure that the plug for the test leads is fully
seated into the banana jacks.
Connect the tester in parallel with the load or
circuit.
The tester indicates both the voltage type and
the voltage level.
To Measure DC Voltage:
Ensure that the plug for the test leads is fully
seated into the banana jacks.
Connect the tester in parallel with the load or
circuit.
The tester indicates the voltage type, polarity,
and the voltage level.
2
Voltage Tester
Instruction Manual
WARNING
Read First: Safety Information
Use the tester only as specified in this manual;
otherwise, the protection provided by the tester
may be impaired.
Warning
To avoid possible electric shock or personal
injury, follow these guidelines:
Do not use tester if it is damaged. Visually
inspect tester to ensure case is not cracked.
Inspect and replace leads if insulation is
damaged, metal is exposed, or probes are
cracked. Pay particular attention to the
insulation surrounding the connectors.
Do not use tester if it operates abnormally as
protection maybe impaired.
Do not use during electrical storms or in wet
weather.
Do not use around explosive gas, dust, or vapor.
Do not apply more than the rated voltage to
the tester. Voltage is not to exceed 600V.
Always operate this solenoid-type tester
within the specified duty cycle on the front of
the tester. Duty cycle ratio is:
1:7 ON:OFF time for 240V or less
1:40 ON:OFF time for 240V or greater.
Maximum ON time is 15 seconds.
Caution
To protect yourself, think "Safety First":
Voltages exceeding 30VAC or 60VDC pose
a shock hazard so use caution.
Never ground yourself when taking electrical
measurements.
#61-065
ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 1
Maintenance:
Clean the case with a damp cloth and mild
detergent. Do not use abrasives or solvents.
Service, and Replacement Parts:
For replacement parts or to inquire about
service information contact
IDEAL INDUSTRIES, INC.
Attn: Repair Department
1000 Park Avenue
Sycamore, IL 60178
Technical Support: 1-877-201-9005 or visit
our website at www.testersandmeters.com.
Specifications:
VAC Ranges: 120V, 240V, 480V, 600V AC.
VAC Accuracy: Relative indication only
VDC Ranges: 120V, 240V, 600V DC
VDC Accuracy: Relative indication only
Neon bulb lights from 100-600V AC/DC
Operating Frequency: 25-60 Hz
Input Impedance: Low
Overload protection: 1000VDC/750VAC rms.
Operating Environment: 32° F to 122° F
(<70% humidity)
Storage Temp.: -4° F to 140° F
(<80% humidity)
Accessories included: Test Leads, operating
instructions
Dimensions: 7.2" (H), 2.4" (W), 1.5" (D)
Weight: 8.0 oz
Safety:
4
Applications:
Locating Blown Fuses
With power on: Place
tester across the “source”
side of one fuse and the
load side of an adjoining
fuse. If no voltage is
indicated, the fuse next to
the load side prod is blown.
If voltage is indicated, the fuse next to the
load side prod is OK. Repeat the same test
with the prods on the opposite side of the
same two fuses to check the other fuse.
On a three phase circuit, repeat the same test
as above. An indication of no voltage or
lower than normal line voltage indicates the
blown fuse.
Testing for 25 to 60 Cycle Frequency
Place tester between each side of AC line. A
low frequency hum and slow vibrations indi-
cate 25 cycle current. 60 cycle current is
indicated by a higher frequency hum and
more rapid vibrations.
Test Lead Replacement:
Replace leads only with IDEAL test leads
below.
# 61-070 Standard Test Leads with
Shielded Probe Tips
# 61-072 Resistor-fused Test Leads with
Shielded Probe Tips. Each probe tip con-
tains a special, current-limiting resistor
which acts like a fuse to limit short-circuit
current and prevents dangerous arcing
during a shorted condition. The resistors
are rated to 140Ω+/- 10%. Fusing cur-
rent is 1A at 125V. Fusing time is 30-
60ms at 125V, without causing dangerous
conditions during opening of the fuse ele-
ment. Leads need to be replaced when
fuse has opened.
3
R
ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 3


Produkt Specifikationer

Mærke: RAB
Kategori: Ikke kategoriseret
Model: 61-065

Har du brug for hjælp?

Hvis du har brug for hjælp til RAB 61-065 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret RAB Manualer

RAB

RAB NCVT-5 Manual

28 August 2024
RAB

RAB 61-065 Manual

27 August 2024
RAB

RAB 61-647 Manual

27 August 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer