Læs gratis den danske manual til Schneider WDE002959 (14 sider) i kategorien Bevægelsesdetektor. Denne vejledning er vurderet som hjælpsom af 22 personer og har en gennemsnitlig bedømmelse på 3.8 stjerner ud af 11.5 anmeldelser. Har du et spørgsmål om Schneider WDE002959, eller vil du spørge andre brugere om produktet?

Side 1/14
© 2011 Schneider Electric 1
Presence/Monitoring, KNX movement/presence detector 1336/1.0
General
Application 1336/ .0 as developed for the KNX 1 w
movement tector the de . In following the device will
be referr to as the presence ed detecto .r
The distinctive feature of the presence detector
functi is the tegrated so , hic measures on in sen r w h
brightness ntinuousl . h co y T is function is able to
measure nd valuate hanges he xternal a e c in t e
brightness aylight) even (d when artificial lighting is
switched n. Even hen eop are resent, the o w p le p
presence detector function switches off the lighting
when the external brightness is sufficient ve the (abo
brightness threshold t) or working and safe use of se f
the rooms without additional arti lighting. his ficial T
feature reduces energy consumption. he presence T
detector will not switch the lighting on until it detects
movement ont he evice when th ambient in fr of t d e
brightness is too lo . w If vement longer mo is no
detected the ated ate, t integrated in activ st he
staircase timer will switch back f. the lighting of
In contrast to this, the movement block will only
switch f when there is no more vement in front of mo
of e device - in other ords, pendently of th w inde the
brightness. he switch-on condition is however the T
same as with e presence detector ck. th blo
The ETS application includ five dependent es in
presence or movement blocks, h our output wit f
objects each.
The ech data for he resen detector be t nical t p ce may
found in the description of the device.
| Al
Not
l th
e:
e ttings described refer to TS version se E
3, but you can use all the settings and functions
with ETS version 2 as well.
The application files (vd2 and vd3) are
configured in such a way that the application
loading time is considerably reduced. When you
convert an ETS 2 project to ETS 3, you lose this
time saving. If you are working with ETS 3, use
the vd3 files.
Total possible addresses and connections:
254 addresses; 255 connections
|Note:
If you switch back to the preset values in either
ETS 2 or ETS 3 (by clicking "Standard"), all the
values that you have changed so far will be
deleted. Any group addresses which have been
parameterised will be lost.
|Note:
Because various functions depend on other
functions, these dependant functions are only
visible and selectable in the ETS when the
preceding function has been enabled. If you de-
select functions or parameters, group
addresses that have already been connected
may be removed.
Getting started quickly
When you insert the application in the ETS or click on
the "Standard" button, the ETS application will switch
automatically to minimum configuration.
In minimum configuration, it is possible to put the
presence detector into operation. For some
application cases, the minimum configuration is even
adequate for practical use. We also recommend
opening minimum configuration as a way of
familiarising yourself with the application software for
the presence detector. Here all of the extended or
more complex parameters are disabled. In "Block
configuration" only the first "Movement/presence"
block is enabled for use. In the "Telegrams" tab only
output object 1 is enabled. This is a 1 bit output object.
At the start of movement this object sends a 1
telegram and when the internal staircase timer has
elapsed it sends a 0 telegram. Each parameter can
always be tuned to its individual requirements. The
brightness threshold and the staircase timer always
need to be adjusted to suit requirements. Check the
"Brightness" and "Times" tabs.
In this way the corresponding objects are connected
to a KNX switch actuator.
To familiarise yourself with the extended and more
complex parameters see the following pages.
Presence/Monitoring 1336/1.0,
KNX movement/presence detector
1/1/1
1/1/2
Switch obj. Switch obj.
Status feedback obj.
Switch actuator
Status feedback obj.
Safety pause
Movement-/
Presence-
Detector
2© 2011 Schneider Electric
Presence/Monitoring, KNX movement/presence detector 1336/1.0
General functions
The common safety pause
When lights installed in the area of detection of the
presence detector are switched, optical feedback can
occur. The temperature difference between the
luminaires or the change in the infrared spectrum can
be interpreted as a movement by passive infrared
movement or presence detectors (optical feedback).
The application has a common safety pause system -
in other words, a safety pause triggered by the
presence detector will affect all blocks in the
application. As specified in a parameter the safety
pause can be triggered at the status feedback object
(safety pause) when there is an OFF telegram or when
there is an OFF and ON telegram.
The status feedback object of the switching/dimming
actuator must be connected to the feedback safety
pause object of the presence detector.
Once a safety pause has been started, signals from
the movement sensor will no longer be evaluated for
this period of time. An elapsed staircase timer cannot
be started by a movement during an active safety
pause and an ongoing staircase timer cannot be
retriggered by a movement.
An ongoing staircase timer is not affected by a safety
pause being activated. In other words, the staircase
timer will run through in the usual way.
|Note:
Optical feedback can only be avoided by
selecting the right installation location for the
presence detector and the lighting. The safety
pause system and the safety pause object of
the application cannot compensate for all
planning mistakes.
Communication objects
You can select the following communication objects:
General:
Parameter
|Note:
The parameter settings include various
functions which depend on other functions.
Depending on the parameter setting, some
functions or objects may or may not be
displayed in the ETS.
General brightness evaluation
The current brightness can be determined by the
internal brightness sensor, by an external
communication object or by both dependencies. The
relationship between internal and external values can
be parameterised while doing this.
Communication objects
You can select the following communication objects:
General:
Parameter
Function Object name Type Prio Flags Behaviour
Safety
pause
Status feedback
object
1 bit Low WC Receive
General
Parameter Setting
Safety pause via status feedback
object
Disabled
For OFF telegram
For ON and OFF telegram
Safety pause (1 - 20) seconds 1 - 20; preconfiguration: 2
Function Object name Type Prio Flags Behaviour
External
sensor
Actual value input 2 byte Low WCT
+
Transmit/
receive/
update
General
Parameter Setting
Actual value (brightness) From internal sensor
From object, actual value input
From internal sensor and object
Taking the separately measured
lux value (0% - 100%) into
account
0% - 100%, in 5% steps;
preconfiguration 50%