Siemens RCC60.1 Manual

Siemens Termostat RCC60.1

Læs gratis den danske manual til Siemens RCC60.1 (8 sider) i kategorien Termostat. Denne vejledning er vurderet som hjælpsom af 55 personer og har en gennemsnitlig bedømmelse på 4.8 stjerner ud af 28 anmeldelser. Har du et spørgsmål om Siemens RCC60.1, eller vil du spørge andre brugere om produktet?

Side 1/8
3026
Room Temperature
Controller
RCC60.1
for two-pipe fan coil units
Modulating PI control
Output for three-position valve actuator
Outputs for three-speed fan
Automatic heating / cooling changeover
Operating modes: normal and energy saving or OFF
Operating mode changeover input for remote control
Function for avoiding damage resulting from moisture
Operating voltage AC 230 V
Use
Typical use:
Control of the room temperature in individual rooms that are heated or cooled with
two-pipe fan coil units.
For opening and closing a three-position valve actuator operating on AC 230 V and
for switching a three-speed fan.
Suited for use in systems with
automatic heating / cooling changeover
continuous heating or cooling operation.
CE1N3026en
12.06.2003 HVAC Products
Siemens Building Technologies
Functions
The controller acquires the room temperature with its integrated sensor and maintains
the setpoint by delivering three-position control commands to the valve. The controller
provides PI control. The proportional band in heating mode is 4 K and in cooling mode
2 K. The integration time is 5 minutes.
Heating mode Cooling mode
YOut [%]
XpH w
0
100
3026D01
T [°C]
YOut [%]
w
0
100
3026D02
T [°C]
XpK
T Room temperature w Room temperature setpoint
XpH Proportional band heating YB
OutB Manipulated variable
XpK Proportional band cooling
Note: the diagrams only show the proportional part of the PI controller
The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is
used by the controller to switch from heating to cooling mode, or vice versa. When the
water temperature lies above 28 °C, the controller switches to heating mode, below
16 °C it switches to cooling mode. If, immediately after switching on, the water tempera-
ture lies between the 2 changeover points, the controller will start in heating mode. The
water temperature is measured at minute-intervals and the operational status updated.
Automatic
changeover
CM
HM
T
W
[°C]
3026D03
16 28
M
CM Cooling mode
HM Heating mode
TBWB Water temperature
M Operating mode
Purging function The task of the changeover sensor is to initiate the change from heating to cooling
mode even if the two-port valves are shut down for a longer period of time. To ensure
this function, the valves are opened for one minute at 2-hour intervals during off hours.
Three-position
control signal
Outputs Y1 = opening, Y2 = closing and N = neutral are used to drive three-position
actuators with a maximum running time of 150 seconds from the fully closed to the fully
open position.
When commissioning the controller, an opening signal of 200 seconds is delivered,
followed by a closing signal of 200 seconds to ensure the actuator will be fully closed.
When the actuator has reached the position calculated by the controller, a waiting time
of 30 seconds is observed in order to stabilize the outputs.
The control outputs carry AC 230 V.
Energy saver
The room temperature setpoint can be limited in increments of 1 K by making use of
the minimum and maximum limitation facility. Arbitrary setpoint readjustments can thus
be prevented.
2/8
Siemens Building Technologies Room temperature controller CE1N3026en
HVAC Products 12.06.2003


Produkt Specifikationer

Mærke: Siemens
Kategori: Termostat
Model: RCC60.1

Har du brug for hjælp?

Hvis du har brug for hjælp til Siemens RCC60.1 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Termostat Siemens Manualer

Siemens

Siemens QAF64 Manual

28 December 2024
Siemens

Siemens RDG100T Manual

15 Oktober 2024
Siemens

Siemens DESIGO RXA Manual

5 Oktober 2024
Siemens

Siemens REV33 Manual

3 Oktober 2024
Siemens

Siemens RAA31 Manual

16 September 2024
Siemens

Siemens REV100 Manual

2 September 2024
Siemens

Siemens RDG160T Manual

1 September 2024
Siemens

Siemens RDF600KN Manual

30 August 2024
Siemens

Siemens REV23M Manual

30 August 2024

Termostat Manualer

Nyeste Termostat Manualer